User Manual 

 

 

 

 

Paperless Recorder/Datalogger 

PPR 500 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Version 2.1.1 

 

Summary of Contents for PPR 500

Page 1: ...Niedersachsenstra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com User Manual Paperless Recorder Datalogger PPR 5...

Page 2: ...ng code PPR 500 16 4 7 2 Accessories 18 4 8 Specifications 18 5 Installation and wiring 22 5 1 Unpacking 22 5 2 Installation 23 5 3 Panel mounting style 23 5 4 Setup input and output 26 5 5 Wiring of...

Page 3: ...4 Analog Output 71 7 1 5 Digital Output 71 7 1 6 External 72 7 1 7 Jobs 73 7 2 Display 76 7 2 1 Status Bar 77 7 3 Timer 78 7 4 Clock 81 7 5 Communication 82 7 5 1 Connections 84 7 5 2 Commands 85 7 5...

Page 4: ...ion Bank 123 8 2 5 How to configure Recorder 125 8 2 6 Touch Screen 125 8 2 7 Ethernet 126 8 2 8 Removable Media 128 8 2 9 Configuration 133 8 2 10 How to view Historical data 143 8 2 11 How to view R...

Page 5: ...side the re corder is prohibited Even in the case of a portable unit the protective earth terminal must remain connected if the recorder is connected to any hazardous voltage 2 Keep signal and supply...

Page 6: ...of abrasives or any sharp and hard objects which would damage the dis play 7 Do not operate the recorder if any part has been removed or disassembled Consult your nearest dealer at once 3 Static Elect...

Page 7: ...play I O cards AI AO DI DO for easy expansion On board SD card for Internal memory External solid storage media USB flash memory in high capacity 171 mm short depth Ethernet as standard and optional R...

Page 8: ...om paperless recorder Batch control log data in batches 100 msec data logging and historical data archival tools Display screens rotation Data dynamic exchange feature via PC software Search data with...

Page 9: ...48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Editing Configuration in Free and Extensive Software Extensive Software D...

Page 10: ...romesstec com I Internet www promesstec com Panel Studio Software to Edit Custom Displays 4 2 Comparison of PPR series Recorders Description PPR200 PPR500 Display Size 6 1 5 6 Analog Inputs Maximum 18...

Page 11: ...which work flexibly with the following plug play I O cards Analog Input cards part number AI206 AI203 These two cards are used for 6 3 channel analog input Each input is isolated from each other to a...

Page 12: ...ut cards AO206 Each card includes 6 channels They are used for 4 20mA 0 20mA current output 0 5V 1 5V 0 10VDC voltage output Note 1 The IO Cards should not be removed or Inserted to the PR when the Po...

Page 13: ...13 promesstec GmbH I Niedersachsenstra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com...

Page 14: ...120 seconds 1896304 days 3792608 days The above is an approximation Each record of data uses 2 bytes or 4 bytes of memory For ex Selected data size 2 bytes If the Log Speed the recording speed of meas...

Page 15: ...23 90 229 29 E Mail office promesstec com I Internet www promesstec com 4 6 Smart Mechanism The recorded data is stored in the manufacturer s special binary format It is not possible to manipulate or...

Page 16: ...ction Slot 1 A 3 universal inputs analog AI203 X 6 universal inputs analog AI206 B 6 digital inputs DI206 C 6 relay outputs RO206 E 3 relay outputs and 3 digital inputs RD233 F 6 universal outputs mA...

Page 17: ...D233 F 6 universal outputs mA and V Function Slot 4 A 3 universal inputs analog AI203 X 6 universal inputs analog AI206 B 6 digital inputs DI206 C 6 relay outputs RO206 E 3 relay outputs and 3 digital...

Page 18: ...recorder There is an additional charge for the extensive Data Acquisition Software supplied with communication of RS 232 422 485 or Ethernet 4 8 Specifications Power PPR 500 90 250VAC 47 63Hz 52VA 26W...

Page 19: ...d for 4 20 mA and 1 5V inputs Characteristics Type Range Accuracy Input at 25 C Impedance J 120 1000 C 1 C 3 12M 184 1832 F K 200 1370 C 1 C 3 12M 328 2498 F T 250 400 C 1 C 3 12M 418 752 F E 100 900...

Page 20: ...28 1112 F JPT500 200 600 C 0 4 C 2 0K 0 003916 328 1112 F JPT1000 200 350 C 0 4 C 2 0K 0 003916 328 662 F Cu50 50 200 C 0 4 C 2 0K 0 00426 58 392 F Cu100 50 200 C 0 4 C 2 0K 0 00426 58 392 F Cu50 180...

Page 21: ...Load Resistance 0 500 ohms current 10K ohms minimum voltage Output Regulation 0 01 for full load change Output Setting Time 0 1 second stable to 99 9 Isolation Breakdown Voltage 1500VAC at 50 60Hz fo...

Page 22: ...or operation 20g for transportation Operation Position no inclined restriction Dimensions Panel Mount style 144 W x 144 H x 193mm D for PR10 20 288 W x 288 H x 194mm D for PR30 Standard Panel Cutout 1...

Page 23: ...rgents to clean the equipment in order to avoid deformation The recorder is designed for indoor use and not in any hazardous area It should be kept away from shock vibration and electromagnetic fields...

Page 24: ...romesstec GmbH I Niedersachsenstra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Right Side Panel Cut Out Dimens...

Page 25: ...orf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Note Do not over tighten mounting clamp screws that could result in distortion of the...

Page 26: ...of chapter 1 To plug the card into the rear slot then power on The recorder will automatically detect the card and display the specific input type then show its source of a specific slot in Configura...

Page 27: ...lot and power on The recorder will automatically detect the card and then display the output type and its source of a specific slot in System Info mode whilst doing the configuration To set up the rel...

Page 28: ...e of a specific slot in System Info mode whilst do ing the configuration To set up the digital input card please press menu and then Config button to get into the configuration window In the configura...

Page 29: ...RD233 This card includes 3 relays rated 5 Amp 240 VAC and 3 Channels of Digital Inputs As above plug the card into rear slot and power on The recorder will automatical ly detect it and then display t...

Page 30: ...nfig button to get into the configuration window In the configuration window press up down and enter key to select AO and get into AO setting window In the AO setting window the setup steps are simila...

Page 31: ...ceeded 2 For the panel mount version it is recommended that near the equipment an external fuse and an external switch rated at 2A 250 VAC should be equipped 3 Beware not to over tighten the terminals...

Page 32: ...32 promesstec GmbH I Niedersachsenstra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Analog Input Card AI206...

Page 33: ...33 promesstec GmbH I Niedersachsenstra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Analog Input Card AI203...

Page 34: ...34 promesstec GmbH I Niedersachsenstra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Relay output card RO206...

Page 35: ...35 promesstec GmbH I Niedersachsenstra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Digital input card DI206...

Page 36: ...esstec GmbH I Niedersachsenstra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Relay output and digital input car...

Page 37: ...37 promesstec GmbH I Niedersachsenstra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Analog output card AO206...

Page 38: ...sstec GmbH I Niedersachsenstra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com 5 6 RS 232 RS 422 RS 485 wiring Fig...

Page 39: ...Memory Card There two types of external storage for the User One is the SD card and other is USB pen Flash Card We have got two slots for inserting USB flash one in the front and other in the rear si...

Page 40: ...ve Data Acquisition software on PC first The power should be turned off while inserting input and output cards It is not recommended to insert input or output cards while the unit is switched on 6 Bas...

Page 41: ...ail office promesstec com I Internet www promesstec com 6 2 Standard and Plus Version of Firmware The standard version of firmware will be having only Input configuration and does not include Math Ext...

Page 42: ...to cols Modbus TCP IP or Serial as a Master or Slave 6 4 Information Accessibility through WEB Web Server The Recorder Trend and Digital data can be viewed in any place of world as we have got Web Ser...

Page 43: ...eens Handwriting Messages on Trend Screens are very handy for process associates to highlight the important events The User can write Handwritten messages using stylus on Historical Trend Screens This...

Page 44: ...omesstec com I Internet www promesstec com The User using the stylus can write any message as shown in the below screen in Historical Trend Pages If the User wants to change the width of the written m...

Page 45: ...com I Internet www promesstec com If the User wants to change color of the pen He she can change by pressing the menu this can be shown in the below screen the arrow points the menu If the User wants...

Page 46: ...www promesstec com If the User wants to undo a part of message He she can do by pressing the menu shown in arrow and will undo the part of the message This is shown in below screen If the User wants t...

Page 47: ...an do by pressing the menu shown in arrow below and this will save the written message The same is shown in below screen 6 6 Custom Editted Display Screens We call it Custom Page on device and Custom...

Page 48: ...For normal there is only one password defined but for CFR 21 three 9 levels of password definition The related settings information can be found in Chapter 7 Configuration Section 7 7 6 11 Auto Outpu...

Page 49: ...ollowing soft buttons also appear Save Load Default and Home Soft buttons Enter key Up directional key Down directional key Home key Various options available to enter into configuration mode Option 1...

Page 50: ...n slot Home Go to home page 7 1 Channel Path Menu More Config Channel This section is to configure different type of channels Analog Input AI Digital Input DI Math Analog Output AO Digital Output and...

Page 51: ...eys ap pear Press on Shift to select special characters Press on Caps to select Capital letters Press soft key OK after entering channel name Desc The description about a specific channel on the displ...

Page 52: ...od This is method of logging measured data Select the column and press enter and then choose the Log method of Instant Average Minimum or Maximum data Instant logging in the last measured data at the...

Page 53: ...48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Type Select the sensor input type for the Channel Unit The engineering un...

Page 54: ...rrent etc Offset It is offset value to correct the sensor error Gain It is a multiplier to correct the sensor error The correct value the process value x gain offset Events The Event is frequently use...

Page 55: ...her than high limit for double warning LL Low low limit to set up another limit lower than low limit for double warning Dev Trigger event on positive deviation of process value The job or alarm is act...

Page 56: ...ept five different type of events or alarms and each event can create two jobs Please note that a job under Event is different from a job by pressing the Operate key The former is actuated by an event...

Page 57: ...e for the Digital Input Channel Max 18 characters allowed for the name Description Define detail description for the channel Type Logic Level Logic Level This selection activates digital logic which i...

Page 58: ...Digital input cards inserted in the paperless recorder Sample applications of Digital input After pressing a Start switch at site latch ON Digital Ouput1 After pressing a Pause switch at site latch O...

Page 59: ...om I Internet www promesstec com 7 1 3 Math Channel Maximum no of Math channels in various PR series Recorders are as follows PR Recorder PPR 500 Maximum Math Channels 40 Path Menu More Config Math Af...

Page 60: ...etails will be changed For ex Type Math have a different configuration details compared with Type Totalizer or Type Counter Log data type Trigger Method Speed Same as Analog Input Press Back key and t...

Page 61: ...ation table Ex A chemical tank is with non linear shape Level is 0 to 1400 cms The Record er should display 0 to 170 Tons as per following table Add Press Add soft button to add a new row into the Tra...

Page 62: ...ATG x Tan 1 x x y Remainder of x y x y xy Math Eample 1 Relative Humidity PPR 500 Math application How to Calculate Relative Humidity Theory Requirement Two Analog Inputs Type RTD AI1 To measure dry...

Page 63: ...wet bulb temperature Tw 30 C Ew 0 61078 EXP 17 269 Tw Tw 237 3 Td Tw Ew 0 61078 EXP 17 269 30 30 237 3 40 30 Ew 42 4262 millibars Ed 0 61078 EXP 17 269 Td Td 237 3 Td Tw Ed 0 61078 EXP 17 269 40 40 2...

Page 64: ...64 promesstec GmbH I Niedersachsenstra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com...

Page 65: ...ative humidity in Five events are supported for every Math channel and two jobs are available in every event same as Analog input channel Math channels are virtual channels It contains measured value...

Page 66: ...ters allowed Desc Defines the description for a specific counter on the display Type Select Counter Counter Unit Defines the unit of counter Preset Defines the preset value for the counter Event Defin...

Page 67: ...ignal indicates High pressure Low signal indicates normal pressure Reset Counter1 historical data in order to log new data for the next day Archive historical data by pressing the following Menu Event...

Page 68: ...irectional keys at the bottom to select from available Totalizers Name Defines the name of the Totalizer Maximum 18 characters allowed Desc Defines the description for a specific Totalizer on the disp...

Page 69: ...s set as Low cut then if source channel AI1 is less than 0 0 then Totalizer value will not go to negative Event Total 5 events are supported for each Math channel Defines the type Set point Log Job1 o...

Page 70: ...l water dis charged and want this information daily weekly and monthly reports Reset Totalizer1 historical data in order to log new data for the next day Archive historical data by pressing the follow...

Page 71: ...om 7 1 4 Analog Output After entering the Configuration in the Channel select AO then Press the Enter soft button to get into Analog Output Channel configuration page Desc Define detail description fo...

Page 72: ...ase if you need to get Normally Close NC at Recorder Power ON then enable Reverse for selected Digital Output The operation is Relay output shall be reversed 7 1 6 External This is to access data from...

Page 73: ...o DO 6 The relay is latched when it is activated DO Process Set digital output relay on for process high or low and then select Target Say from 1 of DO 1 to DO 6 The relay is not going to be latched w...

Page 74: ...report will be presented as details described in section Reports Reset MinMaxAve In Report function after logging the MinMaxAve data of AI and Math channels for one day for example then reset historic...

Page 75: ...logs using the average of the Ten measured data values For the same speed in the Maximum or Minimum mode then the recorder logs using the maximum or minimum of the Ten measured data values Sampling L...

Page 76: ...Mode Defines the default method of displaying data for the page Options are Trend Bar Digital Mix and Disable modes Speed This is display speed Available options are 100 msec dot 1 Sec dot 2 Sec dot 5...

Page 77: ...e Low Here is a typical example with input 0 10V Scale Low 0 00 Scale Hi 100 00 to have better resolution and vision on Bar set Display Lo 0 00 Display Hi 50 00 so that the Bar displays from value 0 0...

Page 78: ...Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Fig Status bar display in Real time 7 3 Timer Path Menu More Config Timer Press directional keys at the bottom to se...

Page 79: ...obs can be configured for each timer Timer Example 1 Switch on water pump every day at 8 00 hrs and switch off at 10 00 hrs This application requires to Daily type timer which works with Real Time Clo...

Page 80: ...ob2 No Action Timer Example 3 Timer Report A staff plans to get a daily report from the recorder about the minimum max imum and average values of the process every day After the production has finishe...

Page 81: ...e directional keys Up Down to select the col umn press Enter soft button to change the clock data Then press on Apply Time Soft button to apply it to the recorder Summer time In some countries of Nort...

Page 82: ...IP ad dress for the recorder Select User Define to manually set a fixed address for the recorder IP Address Defines the correct address of the recorder on the network Subnet Mask Defines the correct...

Page 83: ...Odd 8 1 or Even 8 1 Modbus Client Master Sample Rate Ethernet 100 msec dot 1 sec dot 2 sec Dot 5 sec dot 10 sec dot Timeout The default timeout is 100ms Serial 100 msec dot 1 sec dot 2 sec Dot 5 sec...

Page 84: ...et www promesstec com 7 5 1 Connections Total 16 connections are available Each connection can be configured as either Serial or Ethernet Name Connection name Type Serial Ethernet Slave ID If Recorder...

Page 85: ...ec com 7 5 2 Commands Total 16 commands are available Action Enable Disable To Channel First Enter first external channel details Ex Ext1 Last Enter last external channel details Ex Ext24 From Device...

Page 86: ...49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com 7 5 3 Modbus RTU Master Example1 Master Paperless Recorder Slaves External IO modules 2 nos each...

Page 87: ...esstec GmbH I Niedersachsenstra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Master Configuration Slave Configu...

Page 88: ...torf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com 7 5 4 Modbus RTU Master Example2 Master Paperless Recorder Slave PID Controller Fig E...

Page 89: ...89 promesstec GmbH I Niedersachsenstra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Slave Configuration...

Page 90: ...0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com 7 5 5 Modbus RTU Slave Example Master PC Modbus RTU OPC Server Slaves Paperless Recorders 2 nos each with 6 chan...

Page 91: ...lish Spanish Portuguese Brazil Portuguese Russian Thai Czech Danish Dutch Swedish Turkish Security Select Normal or CFR 21 security More details available at section Security Batch Control Disable and...

Page 92: ...brightness and 6 is for high est possible brightness Screensaver To prolong the life of the LCD display it is suggested to set the dis play turn off time in 1 10 20 30 40 50 or 60 minutes after the u...

Page 93: ...tes using LogOut function the user needs to key in password again It also offers audit trail function to record the us er the timing and what type work he was doing on the recorder before Incorrect pa...

Page 94: ...e is a simulation mode used as a sales tool for demonstration pur poses It was set to simulate AI analog inputs and Math To start the automatic demonstration first enable Demo mode then turn the power...

Page 95: ...less Recorder 7 9 1 USB Printer Generally USB printer support PCL protocol It means it will support Page Print but not line print We support PCL language 4 5 6 If USB printer supports ESCP protocol si...

Page 96: ...Laser ESCP printer PCL Inkjet available by default Select one from the list as per printer model connected to the Paperless Recorder Port It shows Network by default Once Printer connected to USB por...

Page 97: ...ess Recorder 7 9 2 Network Printer LPT1 Serial printer will print minimum one line and generally used for printing Real time alarms Also it can be used for printing historical data and alarms from Pap...

Page 98: ...5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Select Setup Printer press Enter soft button Select ESCP printer Then enter Net Path properly Ex PC1 LQ300 Where PC1 is comput...

Page 99: ...ained in earlier section In Paperless Recorder at Path select Menu More Config Auto Output Enter Period Select Last hours or Last days Hours Days Select no of hours or no of days as per above selectio...

Page 100: ...0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com 7 9 4 Print Reports In Paperless Recorder at Path select Menu More Config Auto Output Enter In the Mode select which kind o...

Page 101: ...GmbH I Niedersachsenstra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com 7 9 5 Print Snapshot Menu More Operate P...

Page 102: ...e recorder Memory Free Total Internal Indicates the percentage of free memory to total memory available in internal flash card External Indicates the percentage of free memory to total memory availa b...

Page 103: ...s is to upgrade firmware in paperless recorder Contact factory supplier for lat est firmware files Please download firmware file first to USB stick then insert USB stick at USB port at Paperless Recor...

Page 104: ...CD screen Carefully press and briefly hold stylus on the center of the target Re peat this procedure as the target moves around the screen Just touch the screen to complete the screen calibration This...

Page 105: ...4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Path Menu More Config Instrument Select Batch Control and press Ent...

Page 106: ...m Press OK then press Home Soft key to save these settings After Power ON Then in the Menu Batch soft key will be shown as be low Note Batch soft key will appear only after Batch Control enabled as ex...

Page 107: ...er the Lot number If Auto increment is enabled then Lot num bers will be incremented automatically by the recorder say Batch1 1 Batch1 2 Batch1 3 etc during every start of a new batch Jobs Two events...

Page 108: ...To Stop this batch press on Menu More then Pause It gives a message Saving data and updates batch data in the internal memory of the paperless re corder Batch Example 1 Operator wants to start a batc...

Page 109: ...109 promesstec GmbH I Niedersachsenstra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com...

Page 110: ...achsenstra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com How to Dump Batch data to external USB memory Press on...

Page 111: ...3 Lots means Batch1 1 Batch1 2 and Batch1 3 Note Provision not available to dump only specific lot Please refer Instrument Data Transfer Transfer and Remain Press on Yes to dump data from internal me...

Page 112: ...90 229 29 E Mail office promesstec com I Internet www promesstec com 7 12 Calibrate This function is used for calibrating Individual Analog channel For Eg If you are calibrating an AI 0 5V When you cl...

Page 113: ...0 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Please follow the next instruction inject 0V in to the input which can be seen in below screen After you in...

Page 114: ...48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Now inject 5V and click ok After you inject and select ok user can see th...

Page 115: ...PC based software By using this software you can configure the settings of the Recorder offline and online Trends of configured channels can be viewed in PC by using this This has got 4 Options 8 1 F...

Page 116: ...re from Microsoft website 2 Install the software 3 Historical viewer icon desktop shortcut will be created after installation of software 4 Historical viewer can be accessed from the following path as...

Page 117: ...ove picture squared they can view the below menu and accordingly they can select the Recorder PR and click ok After that User has to give a name to the project and select the location of project as sh...

Page 118: ...eady configured in the PC then they can select prj file to open the project To save the project file settings in PC Receive configuration Storage Media Ethernet Send configuration Storage Media Ethern...

Page 119: ...Please refer to 4 5 Communication for entering IP address subnet mask and gateway address manually at the Recorder Gateway refers to a device on a network that sends local area traffic to oth er netw...

Page 120: ...ng the Re corder to PC Notebook directly then crossover Ethernet cable should be used Straight Through Cable VR18 LAN HUB Crossover Cable VR18 PC Notebook RJ 45 PIN RJ 45 PIN RJ 45 PIN RJ 45 PIN 1 Tx...

Page 121: ...own message as No response from Record er connection fails If this is the case please check the Ethernet cable connections at both the Recorder and PC LAN HUB side Also make sure that green communica...

Page 122: ...pace in hard disk Less than 10 space generates error mes sage 8 2 2 Operating system Windows based Operating systems Windows XP Windows 7 Windows 8 etc 32 bit and 64 bit operating systems are supporte...

Page 123: ...nk It is to set path for the data transfer It s important to setup Bank properly at the firsthand to proceed further 1 Open existing Project or create a new project from RealTime viewer using one of t...

Page 124: ...0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Click at bank icon to open communication bank configuration and select the bank bank accordingly If...

Page 125: ...If Recorder is connected on Serial RS 232 or RS 485 then select Mod bus_RS232 as shown below Please select the com port baud rate as in the instrument 8 2 5 How to configure Recorder Three ways Touch...

Page 126: ...Recorder as 192 168 0 11 3 Procedure to set IP address manually at Recorder Menu More Config Communication press Enter IP Select User Define Select IP address 192 168 0 11 Default and press Enter to...

Page 127: ...Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com If the connection is working fine the user can see the below figure Upon clicki...

Page 128: ...ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Click yes to apply the settings If you have set no password just click ok And after...

Page 129: ...low 1 In Recorder pl insert empty SD card or USB stick 2 In Recorder press Menu More Config Press Save Press Yes It will save Recorder configuration files into USB stick Check contents of Removable me...

Page 130: ...229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Select PR Recorder Click OK Note Above screen appears first time if no project files available in Com puter S...

Page 131: ...l office promesstec com I Internet www promesstec com Click Yes It will open Recorder configuration screen Note The configuration screen is same as available directly in Recorder Please refer Chapter...

Page 132: ...5 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com 6 Now remove Removable media from PC Insert it into the Recorder In Recorder p...

Page 133: ...I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com 8 2 9 Configuration Please refer Chapter 4 for full details related t...

Page 134: ...134 promesstec GmbH I Niedersachsenstra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Math channel Analog Output...

Page 135: ...135 promesstec GmbH I Niedersachsenstra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com External Channel Display...

Page 136: ...136 promesstec GmbH I Niedersachsenstra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Timer Clock...

Page 137: ...137 promesstec GmbH I Niedersachsenstra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Communication...

Page 138: ...138 promesstec GmbH I Niedersachsenstra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Instrument...

Page 139: ...139 promesstec GmbH I Niedersachsenstra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com...

Page 140: ...140 promesstec GmbH I Niedersachsenstra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com...

Page 141: ...141 promesstec GmbH I Niedersachsenstra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Password Demo...

Page 142: ...2 promesstec GmbH I Niedersachsenstra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Auto Output System Informati...

Page 143: ...to view historical data in Recorder directly using the Touch screen Ethernet Note Please read the following sections first 1 How to configure Communication bank 2 How to configure Recorder Ethernet Ma...

Page 144: ...ra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Click Import measured data icon Note Time taken based on amount...

Page 145: ...Please read Historical viewer help file from software itself for all the fea tures available in Historical viewer software Removable Media Note Please read the following sections first 1 How to confi...

Page 146: ...iedersachsenstra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Select All or one of the other available options...

Page 147: ...29 E Mail office promesstec com I Internet www promesstec com Now remove USB stick from Recorder Check contents in the USB stick Open Project from Historical viewer using one of the following options...

Page 148: ...ernet www promesstec com Click Import measured data icon Note Time taken based on amount of data available in internal memory Select Yes if you wish to delete data from USB stick Select No only if any...

Page 149: ...viewer help file from software itself for all the fea tures available in Historical viewer software 8 2 11 How to view Real time data in PC It is possible to monitor Real time data from Paperless Rec...

Page 150: ...150 promesstec GmbH I Niedersachsenstra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Click No Click bank icon...

Page 151: ...ports are configured in PC to receive data from two different serial networks You may use two USB to Serial converters for this application After completing the bank setup click Save icon and close re...

Page 152: ...Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com How to open Real time viewer Two ways Click at desktop icon Start Programs Data...

Page 153: ...H I Niedersachsenstra e 4 I D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Click OK Click Save icon and close return to...

Page 154: ...ease read Real time viewer help file from software itself for all the fea tures available in Real time viewer software 8 2 14 Serial RS232 422 485 The procedure is similar to Ethernet But need to set...

Page 155: ...fice promesstec com I Internet www promesstec com Click Add Select Device Type PR Recorder Deselect checkbox at Auto updae the Tag contents Enter IP address of second Recorder Make sure to select user...

Page 156: ...dware PC with 3G GHz processor 512 MB RAM 5 0GB free space in the hard disk Ethernet port RJ 45 female 9 1 2 Operating system Windows based Operating systems Windows XP Windows 7 Windows 8 etc 32 bit...

Page 157: ...corder use Ping Instruction from the dos prompt first to verify if there is successful communication between Recorder and PC via Internet Fig Response from the Recorder for the Ping instruction from P...

Page 158: ...m In Configuration select Communication and then press Enter soft key Select IP type User Define Enter the IP Address Subnet Mask Default Gateway DNS Server Settings in the Ethernet Settings Note Make...

Page 159: ...the Recorder After completing the above steps press BACK key first then Home key to re turn to main menu It will save the configuration settings in the Recorder Now the Recorder is ready for the Web S...

Page 160: ...com Format http 192 168 1 111 Now you can see Paperless Recorder screens in browser as shown below The display includes Real time values of all channels like AI Math Counters To talizers Real time al...

Page 161: ...465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com Pressing Mode You can view the datas in Bar Graph Trend and Digital Values B...

Page 162: ...D 48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com By Pressing Bar You can view the datas in Bar Graph By pressing the Digi...

Page 163: ...229 29 E Mail office promesstec com I Internet www promesstec com Pressing Alarm You can view the List of Alarms with the details Pressing Status you can view the status of the Analog outputs Digital...

Page 164: ...48465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com By Pressing DO you can view the status of the Digital outputs By Pressing...

Page 165: ...465 Sch ttorf I Tel 49 0 5923 90 229 0 I Fax 49 0 5923 90 229 29 E Mail office promesstec com I Internet www promesstec com By pressing Counters you can view the status of the counters By Pressing Tot...