background image

 

USER MANUAL 

ONLINE UPS 

UPS I1000/2000/3000   

 

 

 

 

 
 

 

 

 

Uninterruptible Power Supply 

www.pinnacle.co.za 

Summary of Contents for UPS I1000

Page 1: ...USER MANUAL ONLINE UPS UPS I1000 2000 3000 Uninterruptible Power Supply www pinnacle co za...

Page 2: ...el Description 8 5 Connection and Operation 12 5 1 Inspection 12 5 2 Connection 12 5 3 Battery charge 14 5 4 Turn on the UPS 14 5 5 Test function 15 5 6 Turn off the UPS 15 5 7 Audible alarm mute func...

Page 3: ...29 10 Technical Data 30 10 1 Electrical specifications 30 10 2 Operating Environment 30 10 3 Typical backup time Typical values at 25 C in minutes 31 10 4 Dimensions and weights 31 11 Communication Po...

Page 4: ...ht or near heat Do not connect appliances or items of equipment which would overload the UPS e g laser printers etc to the UPS output Place cables in such a way that no one can step on or trip over th...

Page 5: ...ion Do not disconnect the mains cable on the UPS or the building wiring socket grounded shockproof socket during operation as this would remove the ground to the UPS and of all connected loads The UPS...

Page 6: ...ng socket components inside the UPS are still connected to the battery which are potentially dangerous Before carrying out any kind of service and or maintenance disconnect the batteries Verify that n...

Page 7: ...can cause injury to the skin and eyes It may be toxic Please replace the fuse only by a fuse of the same type and of the same amperage in order to avoid fire hazards Do not dismantle the UPS except t...

Page 8: ...1 Harmonic Current IEC EN 61000 3 2 Voltage Fluctuation and Flicker IEC EN 61000 3 3 EMS ESD IEC EN 61000 4 2 Level 4 RS IEC EN 61000 4 3 Level 3 EFT IEC EN 61000 4 4 Level 4 SURGE IEC EN 61000 4 5 Le...

Page 9: ...6 2 Description of Commonly Used Symbols Some or all of the following symbols may be used in this manual It is advisable to familiarize yourself with them and understand their meaning...

Page 10: ...powers the inverter On the basis of this DC voltage the inverter generates a sinusoidal AC voltage which permanently supplies the loads Computers and periphery are thus powered entirely by the mains...

Page 11: ...nverter is off At this moment if Bypass is enabled then the output sockets are supplied with voltage via the bypass if the mains power is available Select Button If the UPS system is No output or Bypa...

Page 12: ...ayed from 0 to 99Hz Indicates the input Line current value which could be displayed from 0 to 99 9A Indicates the input Line voltage is higher than the SPEC value and the UPS would be in the battery m...

Page 13: ...nt and the left first grid represent 30 load the left two grids represent 60 load the three grids represent 90 load all the grids represent 100 load Indicates the load percent W is displayed when the...

Page 14: ...the UPS is working in fault mode Indicates some warnings occur which need be attention Indicates no any warnings or fault occur UPS setting Information The four value of the output voltage could be se...

Page 15: ...for I3000 S If the UPS is connected via wires it is recommended to select the 2 5mm2 wire and the GND terminal should be grounded first by using the green yellow wire The wiring is shown as the follo...

Page 16: ...ut Socket pcs I1000 S 3 IEC type I2000 S 6 IEC type I3000 S 4 IEC type Terminal block The wiring configuration is shown as the following procedure a Remove the small cover of the terminal block b Use...

Page 17: ...EPO connector is closed with a wire on the rear panel Once the connector is open the UPS would stop the output until the EPO status is disabled Enable the EPO status Disable the EPO status 5 3 Batter...

Page 18: ...r bypass mode is no output after UPS is connecting utility power and breaker is turned on This can be configured by monitoring the LCD panel or firmware 5 5 Test function Test the function of the UPS...

Page 19: ...S 8 pcs of 12V batteries Connection of batteries more than or less than required will cause abnormality or permanent damage 2 One hard wiring type battery terminal on the rear panel is used for connec...

Page 20: ...he UPS to the load Then turn on the mains switch or connect the power cord of the UPS to utility power supply the battery would start to be charged Model No DC breaker VOLTAGE CURRENT I1000S 48Vac 50A...

Page 21: ...come forth then all previous warnings would not be shown again but only the fault code is presented Operating mode code Operating mode code No output mode 00 Overload fault 07 Bypass mode 01 Over tem...

Page 22: ...2 Battery mode The LCD display in battery mode is shown in the following diagram The information about the utility power the battery the UPS output and the load could be displayed The Battery and 03...

Page 23: ...output and the load could be displayed The UPS will beep once every 2 minutes in bypass mode The Bypass and 01 code indicate the UPS is working in the bypass mode The UPS does not have the backup func...

Page 24: ...ayed The 00 code indicates the UPS is working in the No output mode 6 5 Abnormal mode In abnormal mode such as Bus fault etc the corresponding fault code would be shown to indicate the operating mode...

Page 25: ...pass Enable in turn And if pressing the Enter button for more than one second at this time the flickering black dot would turn to flickerless and the output voltage or frequency or bypass state settin...

Page 26: ...ut voltage from 220Vac to 230Vac through the LCD panel Setp 1 One flickering black dot would appear before 208Vac after pressing the Select button Setp 2 The flickering dot would move to 230Vac after...

Page 27: ...tp 3 The dot before 230Vac would turn to flickerless after pressing the Enter button and the flickering dot would move to the next 240Vac Setp 4 The output voltage would be 230Vac after the UPS is tur...

Page 28: ...ut mode 0 Bypass mode 1 Line mode 2 Battery mode 3 Battery test mode 4 ECO mode 5 Converter mode 6 Warning Code Site fail 09 Fan fail 10 Battery over voltage over charged 11 Battery low 12 Charge fail...

Page 29: ...1 in LCD even though the power supply is available Inverter not switched on Press On Switch I Display Mode code 3 in LCD and audible alarm sounding every 1 beep in every 4 seconds Mains power supply...

Page 30: ...h Check the ventilation of the UPS check the ambient temperature Ambient temperature high The ambient temperature is too high Check the environment ventilation Line voltage high OVCD action Input powe...

Page 31: ...circuit Make sure the short circuit is removed and the UPS has no internal faults before turning on again Bus short UPS internal fault Notify dealer Please have the following information at hand befo...

Page 32: ...locations subject to high temperatures 9 3 Battery Replace If the battery service life has been exceeded the batteries must be replaced Battery replacement should be performed only by qualified perso...

Page 33: ...W Voltage 200 208 220 230 240 1 2 VAC Frequency 50 60 0 2Hz Battery mode Wave form sinusoidal Derating to 90 when the output voltage is adjusted to 208VAC Derating to 80 when the output voltage is adj...

Page 34: ...es Model No 100 Load 50 Load I1000 5 14 I2000 9 21 I3000 5 15 10 4 Dimensions and weights Model No Dimensions W D H mm Net Weight kg I1000 145 400 220 13 I1000S 145 400 220 7 I2000 192 460 347 31 I200...

Page 35: ...put 5 GND Input 11 3 AS400 Interface Option Except for the communication protocol as mentioned above this series UPS has AS400 card an optional accessory for AS400 communication protocol Please contac...

Page 36: ...33 DB 9 Interface of AS400 communication protocol...

Page 37: ...ontrol any UPS on the same LAN no matter how far from the UPSs Installation procedure 1 Go to the website http www ups software download com 2 Choose the operation system you need and follow the instr...

Page 38: ...35 Appendix Rear panel Back View of I1000 Back View of I1000S...

Page 39: ...36 Back View of I2000 Back View of I2000S...

Page 40: ...37 Back View of I3000 Back View of I3000S...

Page 41: ...38 614 09358 00...