manualshive.com logo in svg
background image

Group

+44 (0) 1250 872261    
www.proctorgroup.com

For more information contact us:

CUST

QTY

LOT NO

ACOUSTIC SOLUTIONS

Group

Profloor Excel Batten

Type 58 / 72 / 82

INSTALLATION GUIDE

Products MUST NOT be stacked 
Products must be kept dry AT ALL TIMES

BEWARE

Packs/Boards exceeds 15Kg

Fold the Profloor Flanking Strip onto the flooring board, apply weight to compress the system 
(tradesman’s weight is normally sufficient) and fix the skirting so that it rests on the flanking strip. 
Trim the edge of the Profloor Flanking Strip flush with the skirting. See figure 20 & 21.

10 

SKIRTING BOARDS

Fig. 20 Timber Installation

Continue the perimeter Excel Batten past the door opening. Where butt joints are formed 
at thresholds, place a continuous length of Excel Batten directly beneath the joint of adjacent 
boards with each board securely fixed to it.

The joint must be glued and where deemed necessary, for secure fix, screws should be used 
to secure both edges of the butt joint to the same batten. Allow a gap between the batten, 
flooring and doorframe for the Profloor Flanking Strip. See figure 16 & 17.

Care should be taken at the design stage to ensure that fire stops are fitted to the same 
standard as that required for the fire doors. Technical advice can be provided for individual 
projects. 

DOORWAYS

Fig. 16 Timber Installation

When a concentrated floor loading is in excess of 1.5kN/m2, i.e. kitchens, bathrooms, 
cupboards containing water heaters etc… it is necessary to modify the batten installation to 
provide additional support. It is also recommended that hallways, both internal and common, 
be treated in the same manner to accommodate the combination of high foot traffic and small 
floor areas.

Profloor Excel Battens should be installed with spacing closed to 300mm centres. See figure 
18 & 19.

 Where night storage heaters are to be supported off the floating floor, additional battens 
should be installed to sufficiently support the increased load. Contact the A. Proctor Group 
Tech Desk for further advice.

Fig. 18 Timber Installation

KITCHEN / BATHROOM (areas of increased loadings)

Fig. 13 Timber Installation

Fig. 15 

Fig. 14 Concrete Installation

Where ends of flooring boards fall between a line of battens, place a continuous length of 
batten for support with each board securely fixed to it following advice given in 4 Fixing 
Flooring.

SUPPORTING NOGGINS

Where access is required to services below the flooring system, the necessary hatch can be 
cut in the floor finish material. Additional battens should be placed around the perimeter of 
the hatch to support the main floor and the hatch cover. The floor finish is fixed to the battens 
in the normal manner. Ensure correct specification of batten depth to accommodate services 
allowing 1-2mm for compression of the foam.

*in cases of Robust Detail constructions, the gap between batten ends where battens have 
been cut to accommodate perpendicular service runs, should be no more than 50mm.

**other than radiator legs.

Fig. 17 Concrete Installation

Fig. 19 Concrete Installation

Fig. 21 Concrete Installation

Отзывы: