Model No. PEL00589

 

MAINTAINED

LED SQUARE EMERGENCY CEILING LIGHT

Summary of Contents for PEL00589

Page 1: ...1 Model No PEL00589 MAINTAINED LED SQUARE EMERGENCY CEILING LIGHT ...

Page 2: ...upplied 8 Refit the plate assembly to it s hinge if previously removed and make connection to the mains supply using the screw terminal block attached to the plate Ensure that the correct polarities are observed i e Brown Live terminal L Blue Neutral terminal N Green Yellow Earth terminal E Link wire L to SW can be removed to change between maintained and non maintained 9 Write the current date on...

Page 3: ...3 Test Record Sheet on reverse PULL OUT ...

Page 4: ...nstallation maintenance a Location Installation date Installed by 20__ 20__ 2 Month Test Sign Date Sign Date S 1 Short 2 Short 3 Short 4 Short 5 Short 6 1 h 7 Short 8 Short 9 Short 10 Short 11 Short 12 3h ...

Page 5: ...5 and operation check record Installation test duration 20__ 20__ 20__ Sign Date Sign Date Sign Date ...

Page 6: ...6 Test Record Sheet on reverse PULL OUT ...

Page 7: ... before testing Isolate the power supply and check that the lamp remains illuminated for at least three hours Restore the power supply Each day Check that the green charging LED is lit Each month short test Isolate the power supply and check that the lamp remains illuminated Record the results on the test record sheet included with these instructions Every six months Isolate the power supply and c...

Page 8: ...minal block 6 Refit the LED plate assembly Tighten the screws and refit the diffuser 7 Restore the mains power and check the operation SPECIFICATIONS Input voltage 220 240V 50Hz Rated power 16W Lamps SMD2835 LEDs x 60pcs Luminous flux 980Lm AC 200Lm DC Continuous emergency illumination 3 hours when the battery is fully charged Battery pack Ni Cd 6V 2Ah Recharge time 24 hours approx Ambient tempera...