IK-E363-001 

 
 

ADDRESSABLE 

GAS DETECTORS 

TYPE PSG-6000

 

 

 
 

Installation and Maintenance Manual 

IK-E363-001 

 

Edition II 

 

 

Summary of Contents for PSG-6000

Page 1: ...1 IK E363 001 ADDRESSABLE GAS DETECTORS TYPE PSG 6000 Installation and Maintenance Manual IK E363 001 Edition II ...

Page 2: ...eclaration of Conformity is available at www polon alfa pl Prior to starting assembly and operation please read the contents of this manual Failure to follow the instructions of this manual may be dangerous or cause violation of applicable regulations The Polon Alfa manufacturer is not liable for damages resulting from use contrary to this instruction A worn out product not suitable for further us...

Page 3: ...gas undetectable by the senses Slightly lighter than air very easily mixed with it Carbon monoxide as a product of incomplete combustion is practically always present in exhaust gases of motor vehicles and in boiler rooms It is perfectly absorbed into the body better than oxygen permanently binding to haemoglobin which may result in serious hypoxia LPG autogas the most popular gas fuel in vehicles...

Page 4: ...anol at low extent Working conditions 20 50 C humidity 10 90 The storage conditions 0 40 C humidity 10 80 Protection level IP54 in the recommended mounting position Housing material ABS PC Cable connectors cable diameter M12 gland 3 6 5 mm Dimensions with connectors 160x124x68 mm 120x124x68 mm Mass 0 3 kg 0 25 kg Frequency of service inspections Recommended in 3 months maximum 12 months Sensor lif...

Page 5: ...5 IK E363 001 Figure 1 The interior of the PSG 6000 detector magnetic field sensor location sensor module sensor cover sensor module power terminals detection line terminals ...

Page 6: ...st 48 hours of uninterrupted power supply The built in short circuit isolator allows detection of faults and damage to the installation In the case of using a loop line damage to the line in one place does not disconnect the detectors from the central unit The detector s alarm condition is signalled by a pulsed red LED light The indicator enables quick detection of the alarming detector and is hel...

Page 7: ...below the ceiling or on the ceiling 6 2 Mounting position Detectors of the PSG 6000 series are recommended to be installed in a vertical position with the gas inlet down this position guarantees the best protection against dust and splashes In the case of methane detectors due to the mounting height a horizontal position increased susceptibility to dust accumulation in the gas inlet element or cei...

Page 8: ... the procedure 8 1 After a positive result you can install the detector covers making sure that the sensor covers are mounted and located in the correct position Lack of the sensor cover reduces the protection of the enclosure to IP43 and the work of the detector without the sensor cover is forbidden The detector connection diagram is shown in Figure 5 Figure 4 Connection diagram of the detector 7...

Page 9: ...of the sensor module disconnect the external power supply in the case of detectors of the PSG 6100 type disconnect the detection lines disassemble the detector cover grip the sensor s plate with your fingers and gently pull it out mount the detector cover PLEASE NOTE Lack of the sensor module will reduce the protection of the enclosure to IP43 Installation of the sensor module disconnect the exter...

Page 10: ...when using efficient equipment and tools Special attention should be paid to the stability of ladders lifts etc Power tools should be used with observance of the conditions of their safe operation specified in the relevant manufacturer s instructions 9 3 Eye protection against dust During work that causes the formation of a large amount of dust especially drilling holes in the ceilings to attach d...