background image

E6 Series

Commercial Emergency Lighting

Page 1 of 2

Job Information 

Type:

Job Name:

Cat. No.:

Notes:

Features

Illumination:

 Illumination 

is provided by two fully-

adjustable polycarbonate lamp 

heads. Each lamp head utilizes 

a high-performance parabolic 

reflector in conjunction with a 

6 VDC, 5.4 W T-5 wedge base 

tungsten lamp. High-impact 

acrylic refractors minimize 

glare and maximize optic 

control.

Housing: 

Constructed of 

impact resistant , UL 94 V-0,

5 VA thermoplastic, completely 

self-contained. White housing 

is standard, with an optional 

black housing available.

Operating Temperature 

Range: 

Damp Location

68°F (20°C) to 104°F (40°C) 

Diagnostic Electronics 

(standard): 

120/277 VAC 

dual voltage input with surge-

protected, solid-state charging 

circuitry provides for a reliable 

charging system. Charging 

system is complete with 

low voltage disconnect, AC 

lockout, brownout protection, 

AC indicator lamp and test 

switch.

Self-Testing Diagnostics

(optional): 

Continuously 

monitors the critical functions 

of the equipment, including: 

battery disconnect, battery 

failure, charger failure, 

transformer failure and lamp 

failure. Self-Testing routine 

performs a one-minute test 

every 30 days, a 30-minute 

test on the 6th month and a 

90-minute test annually. 

Electrical Specifications: 

0.045 A (120 VAC)

0.020 A (277 VAC)

Code Compliance

UL 924 and UL damp location 

listed. NFPA 101, NEC, BOCA, 

OSHA and IBC illumination 

standards.

Warranty

Three year full electronics 

warranty. One year full plus 

four year prorated battery 

warranty.

E611

16.0"

(40.6 cm)

5.0"

(12.7 cm)

11.87"

(30.15 cm)

Reviews: