background image

Philips Lighting North America 
Corporation 
200 Franklin Square Drive 
Somerset, NJ  08873, USA 
Phone:  855-486-2216 

www.philips.com/luminaires

 

Remote 
Connector

 

(Optional)

 

NORMAL OPERATION/MANUAL TEST

 

OP-PANEL INDICATORS/OPERATION:

 

 

Green Status: Solid indicates system normal and AC power is on. 

NOTE:  To start the Manual test, simply press the Green Indicator (button) as indicated below. To Reset/Cancel a test press the Green Indicator 

(button) once during any test. When Unit is in test mode the Green Indicator LED is flashing. 

 

1 Press: perform a 5 sec brief lamp test, all Lamps operating from battery only.

 

 

2 Presses:   perform a 1-min diagnostic test, all Lamps operating from battery 
only. 

 

3 Presses:   perform a 90-min diagnostic test, all Lamps operating from battery 
only. 

 

6-Sec Continuous Press:  perform a RESET operation.

 

 

CONTINUOUS MONITORING:  The system monitors the following continuously: 

1) Battery, 2) Lamps, 3) Charger, 4) Transfer function.

 

 

The battery requires at least 72 hours of charge time to perform any extended diagnostic test. If the battery has not charged for 72 hours after 

installation and a diagnostic test is requested, the charger light will come on and stay on for one minute indicating that the battery is not fully charged 

for attempted test. (The 5-sec brief lamp test is always allowed.)

 

OPTIONAL FACTORY EQUIPPED ITEMS:

 

REMOTE: Unit will be supplied with pigtail connector cable required to control and operate a remote of up to rated MAX. wattage.

 

TIME DELAY (TD): After a power failure and power is restored, the lamps will remain lit for a 15-min period (provided battery capacity remains).

 

 

 
 
 
 
 
 
 
 
 
 

 

 

Flexible Conduit 

Only

 

 

No Rigid Conduit

 

Emergency Lighting

 

COMPAC Thermoplastic Combos

 

CCAX/CCTX Series

 

INSTRUCTION SHEET

 

 

 

Note: The Green power indicator LED will flash slowly during the 15-min. period.

 

LASER TEST (LX): To operate using a laser pen: use laser pen and point the laser beam over the remote sensor (see below), thereby duplicating the 

manual button (1,2,3) pushes. The laser must impact the remote sensor for at least 0.2 seconds to be recognized.

 

FIRE ALARM INTERFACE (FI): Unit will be supplied with a connector at the FAFI location and an interface cable to connect to the building system (per 

wiring diagram).

 

 

FLASHING EM (F): Unit will flash the EXIT sign when operation from the battery only. (Flash rate is 1 flash/sec with a 70”-on duty cycle. 
BUZZER EM (B): Unit will buzz for approx. ½ -sec during power-up sequence or after a reset operation. Buzzer does not activate during either manual or 

automatic testing. Buzzer will only activate when operating from the battery and only due to AC power loss.

 

LESS SELF-TEST (LS): Monthly automatic self-tests will not be performed. (Lamps will not energize on an automatic monthly schedule.)

 

TROUBLE  INDICATORS/TROUBLESHOOTING

 

IMPORTANT SAFEGUARDS

 

READ AND FOLLOW ALL  SAFETY INSTRUCTIONS

 

 

WARNING: Electrical Shock Potential!! Do not attempt to install, maintain or relamp without disconnecting all 
power. Failure to disconnect power can result in electrocution, shock, or severe burns.

 

 

CAUTION: This fixture is designed for permanent installation in ordinary (NON-HAZARDOUS) locations in 
accordance with the National Electrical Code and all applicable local codes. Do not use in areas of limited ventilation or 
in high ambient enclosures. The lamp and fixture operate at high temperatures; contact with combustible material can 
cause fire and personal contact can cause severe burns. When using electrical

 

TEST 

Button

 

 

 
 
 
 
 
 
 
 
 
 

REMOTE SENSOR

 

(IF EQUIPPED)

 

Xtest  DISPLAY  PANEL  INDICATOR:

 

 

 

GREEN - Status:  solid indicates system normal and AC power is on and flashes during any manual/auto test 
cycle.

 

 

RED CHARGER FLASHING:  a charger failure requires the diagnostic charger board to be replaced.  

 

RED BATTERY FLASHING:  battery is disconnected or if it is connected, a replacement is needed.  

 

RED LAMP FLASHING:  Lamp(s) is disconnected or if it is connected, a replacement is needed. (If

 

4-pin remote pigtail is connected to diagnostic charger board and no remote lamp is attached, the

 

LAMPS indicator will flash. Connect a remote lamp or disconnect remote pigtail.)

 

 

 

ALL 3 RED FLASHING:  bad transfer; battery and lamps are disconnected or if they are connected a 
replacement diagnostic charger board is needed.

 

equipment, basic safety precautions should always be followed; including the following:

 

 

READ AND FOLLOW ALL SAFETY INSTRUCTIONS.

 

 

Do not use outdoors.

 

 

Do not let power supply cords touch hot surfaces.

 

 

Do not mount near gas or electric heaters.

 

 

Use caution when servicing batteries. Battery acid can cause burns to skin and eyes. If acid is spilled on 

skin or in eyes, flush acid with fresh water and contact a physician immediately.

 

 

Equipment should be mounted in locations and at heights where it will not readily be

WIRING INFORMATION

 

 

 

               Transformer Inputs

 

 

BLACK - 120V

 

WHITE - Common or 
Neutral

 

RED - 277V

 

 

 

 

 

 

 

 

 

 

 

 

 
 

FIRE-ALARM (If 
Equipped)

 

Factory Cable- Two 
White wires; No 
polarity required.

 

subjected to tampering by unauthorized personnel.

 

 

The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.

 

 

CAUTION:  Halogen  cycle  lamp(s)  are  used  in  this  equipment.  To  avoid  shattering:  Do  not  operate  lamp  in 

excess  of  rated  voltage,  protect  lamp  against  abrasion  and  scratches  and  against  liquids  when  lamp  is 

operating, dispose of lamp with care.

 

 

Halogen cycle lamps operate at high temperatures. Do not store or place flammable materials near 

lamp.

 

 

Battery Connector

 

                                                                                                              Diagnostic  Charger  Board

 

 

 

Do not use this equipment for other than intended use.

 

 

Servicing of this equipment should be performed by qualified personnel only.

 