PERTRONIC INDUSTRIES LTD
PS1-T3 Sounder - Installation Instructions
Pertronic Industries Pty Ltd
1
0312-PS1-T3 Sounder Issue 1.2, 200902
+ -
Bells
Alert
Overview:
The
PS1-T3
generates ‘Evacuation’ tones compliant to AS2220 or ISO8201
The
PS1-T3 Sounder
has a maximum sound pressure level of 98dBA with a sound
distribution pattern shown below. The sound level may be adjusted by a Volume control.
The
PS1-T3 Sounder
is normally connected to the monitored Bell or Sounder circuit of a
Fire Alarm Panel and is activated when the Sounder circuit voltage polarity is reversed in
the ‘Alarm’ state.
The
PS1-T3 Sounder
may be mounted in a standard single-gang electrical flush-box
fitting and is supplied with a protective plastic cover for installation and building
construction use.
Specification:
Dimensions:
117 x 74 x 12
H x W x D (mm) - depth above flush-box.
- designed to fit into a standard electrical flush-box fitting.
Colour Options:
Red or White.
Sound Level Output:
Sound pressure level at 1m (peak
±
3dB)
Evacuation, Alert:
98dBA
(@24Vdc)
Power Requirements:
BELL IN
terminal - supplied from the Bell circuit:
Operating Voltage 9.5Vdc to 30Vdc
Quiescent current (Non-Alarm state)
0.4
µ
A
(@24Vdc)
Operating current (Alarm state – T3 tone)
9mA average, 25mA peak
(@24Vdc)
(Alarm state – AS2220 tone)
14mA average, 28mA peak
(@24Vdc)
Controls:
Third wire for ‘AS2220 / T3 Evacuation’ tone control.
- 0V on Alert terminal for the ‘AS2220’ tone.
Volume Control:
Potentiometer to adjust sound output level – range = 20dB.
Tone Characteristics:
Sound Pressure Distribution:
PS1-T3 Terminal:
Connector Layout
WALL PS1-T3
-45deg 45deg
0deg
PS1-T3 Sound Distribution at 1 metre
Horizontal
Plane
PS1-T3
Mounted in Wall
9
5
d
B
8
5
d
B
8
5
d
B
9
5
d
B