background image

Raychem WinterGard self-regulating heating cables provide 

convenient, reliable freeze protection for a wide variety of pro-

fessionally installed residential and commercial water-pipe and 

roof-and-gutter de-icing applications in nonhazardous areas. 

This data sheet is designed to assist in cable and accessory 

selection and basic circuit design of pipe-freeze-prevention 

applications.  
Complete design guidelines, installation instructions, and safety 

information are provided in the Commercial and Residential 

Self-Regulating Heating Products Application and Design Guide 

(H53585), the H900 Power Connection Kit, the H908 Plug-in 

Power Connection Kit, and the H921 120-V ground-fault protect-

ed junction box.
For detailed information on roof and gutter de-icing applica-

tions, please refer to the WinterGard Wet Design, Installation 

and Maintenance Guide (H56804).

16 AWG 

bus wires

Conductive

core (black)

Inner jacket

(blue or red)

Tinned

copper braid

Water-proof

outer jacket 

(black)

H612, H622 only

 

Construction

 

Pipe Applications

WinterGard systems must be installed correctly to 
ensure proper operation and to prevent shock or 
fire. Carefully read and follow the Commercial and 
Residential Self-Regulating Heating Products 
Application and Design Guide and the H900 series 
connection kit installation instructions. 
• Use only in ordinary (nonhazardous) areas. Do not 

expose to any chemicals, oil or grease. 

• In wet areas, use only WinterGard Wet.
• To minimize the danger of fire from sustained elec-

trical arcing if the heating cable is damaged or 

improperly installed, and to comply with the 

requirements of Pentair Thermal Management, 

agency approvals, and national electrical codes, 

ground-fault equipment protection must be used 

on each heating cable branch circuit. Arcing may 

not be stopped by conventional circuit protection.

• This selection guide does not take the place of the 

installation instructions included in the 

Commercial and Residential Self-Regulating 

Heating Products Application and Design Guide and 

in the H900 series accessory kits. 

• System approvals and performance are based on 

the use of only H900 series accessories with 

WinterGard heating cables. These accessories 

must be used. Do not substitute parts.

Water pipes in dry areas:

H311/H611/H621

Water pipes in wet areas and refrigeration 

condensate drains:

H612/H622

WARNING:

Product Specifications and Data

WinterGard

H311100

H311250

WinterGard Plus

H611050

H611100

H611250

WinterGard Plus

H621050

H621100

H621250

WinterGard Wet

H612050

H612100

H612250

H612500

H6121000

WinterGard Wet

H622050

H622100

H622250

H622500

H6221000

Service voltage

120 V

120 V

240 V

120 V

240 V

Power output at 40°F (W/ft)

3

6

6

6

6  

Power output in refrigeration condensate 
drains at 32°F (W/ft)

n/a

n/a

n/a

8

8

Weight per 100 ft (lb)

6

6

6

7

7   

Nom. cable width (in)

0.380

0.380

0.380

0.415

0.415   

Nom. cable thickness (in)

0.180

0.180

0.180

0.215

0.215   

Bus wire gauge (AWG)

16

16

16

16

16   

Braid wire gauge equivalent (AWG)

14

14

14

14

14   

Insulating jacket type

Modified polyolefin      

Outer jacket type

n/a

n/a

n/a

Modified polyolefin

Maximum exposure temp. (°F)

150

150

150

150

150   

Environment

Use only in ordinary (nonhazardous) areas. Do not expose to any chemicals.

Agency approvals*

1, 3

1, 3

1, 3

1, 2, 3

1, 2, 3   

*

1 = UL System Listed 718K Pipe Heating Cable;   2 = UL System Listed 877Z De-Icing and Snow Melting Equipment;   3 = CSA Certified LR21133