FOR USE IN RESIDENTIAL OR MANUFACTURED HOME APPLICATIONS.

Installation must conform with local codes, or in the absence of local codes, the National Fuel Gas Code, ANSI Z223.1 / NFPA 

54 - latest edition and/or the Natural Gas and Propane Installation Code CSA B149.1 - latest edition.

When applicable, installation must conform with the Manufactured Home Construction and Safety Standard, Title 24 CFR, 

Part 3280 or the Canadian Standard CAN/CSA-Z240 MH Mobile Homes, Series M86.

PB Heat reserves the right to discontinue, or change at any time, the designs and/or specifications of its products without 

notice.

Contact Pavilion Customer Center at 1-855-443-8468, if you have any questions or concerns.

CONDENSING TANKLESS GAS WATER HEATER

Installation Manual

Model : UT199DV (GQ-C3260WX-FF PB US)

Requests to Installers

•  In order to use the Water Heater safely, read 

this installation manual carefully, and follow the 

installation instructions.

•  Failures and damage caused by erroneous work 

or work not as instructed in this manual are not 

covered by the Pavilion Limited Warranty.

•  Check that the installation was done properly in 

accordance with this Installation Manual upon 

completion.

•  After completing installation, either place this 

Installation Manual and Owner’s Guide (the 

warranty registration information included) in 

a plastic pouch and attach it to the side of the 

Water Heater (or the inside of the pipe cover 

or recess box if applicable), or hand it to the 

customer to retain for future reference. For the 

warranty conditions and limitations, see the 

Owner’s Guide.

CAUTION

If the information in these instructions is not 

followed exactly, a fire or explosion may result 

causing property damage, personal injury or 

death.
•  Do not store or use gasoline or other 

flammable vapors and liquids in the vicinity of 

this or any other appliance.

•  WHAT TO DO IF YOU SMELL GAS 

  - Do not try to light any appliance. 

  -  Do not touch any electrical switch; do not use 

any phone in your building. 

  -  Immediately call your gas supplier from a 

neighbor’s phone. Follow the gas supplier’s 

instructions. 

  -  If you cannot reach your gas supplier, call the 

fire department.

•  Installation and service must be performed by 

a qualified installer, service agency or the gas 

supplier.

WARNING

Low NOx Approved by SCAQMD

14 ng/J or 20 ppm

(Natural Gas Only)

SBB819E-1

Rev. 11/20

PB HEAT, LLC

Summary of Contents for GQ-C3260WX-FF PB US

Page 1: ...heck that the installation was done properly in accordance with this Installation Manual upon completion After completing installation either place this Installation Manual and Owner s Guide the warranty registration information included in a plastic pouch and attach it to the side of the Water Heater or the inside of the pipe cover or recess box if applicable or hand it to the customer to retain ...

Page 2: ...neral Requirements 17 6 3 Select a Vent Type 23 6 4 Vent Pipe Installation Direct Vent 24 6 5 Vent Pipe Installation Non Direct Vent 30 6 6 Outdoor Installation 36 7 Connecting the Gas Supply 37 8 Connecting the Water Supply 41 8 1 Installation 41 8 2 Water treatment 43 9 Connecting the Condensate Drain 45 10 Connecting Electricity 47 10 1 Water Heater 47 10 2 Remote Controller 47 10 3 Recirculati...

Page 3: ...er to the Venting the Water Heater section for details If PVC CPVC or Category IV listed pipe is already installed check for punctures cracks or blockages and consult with the vent pipe manufacturer before reusing If the flexible PP pipe is already installed replace to the new flexible PP pipe Improper venting may result in fires property damage or exposure to Carbon Monoxide Check the Gas Check t...

Page 4: ... installed on the next adjacent floor level Detector s must be installed by qualified licensed professionals APPROVED CARBON MONOXIDE DETECTORS Each carbon monoxide detector shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified SIGNAGE A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight 8 ft above grade...

Page 5: ...2 1 Included Accessories 2 2 Optional Accessories NOTE Additional vent pieces are available consult the latest product catalogue for details Remote Controller Cord 26 ft 7 9 m 1 Stock Code 1810 PVC Concentric Termination 1 2 in 50 mm Stock Code 1813 3 in 75 mm Stock Code 1813 1 2 in SV Conversion Kit 1 Stock Code 1814 90 Elbow With Inlet Screen 2 in 3 in Increaser coupling 2 in Pipe Installation M...

Page 6: ...mited Warranty To prevent the Heat Exchanger damage the water must be treated with a Southeastern Filtration Scale StickTM 3M Aqua PureTM scale inhibitor or other scale inhibitor system Low Profile Termination Kit 2 in Stock Code 1820 3 in Stock Code 1820 1 ULC S636 UL 1738 certified for use in both Canada and USA Plastic Rain Cap Stock Code 1821 Not approved for use in Canada Neutralizer 1 Stock ...

Page 7: ...Drain NPT 1 2 in Power Supply Supply 120 VAC 60 Hz Consumption NG 96 W LP 80 W Freeze Prevention 114 W Maximum Current 4 Amps Materials Casing Front Cover Hot dipped zinc aluminum magnesium alloy coated steel w Polyester Coating Casing Zincified Steel Plate Polyester Coating Flue Collar PP Primary Heat Exchanger Stainless Steel Sheeting Stainless Steel Tubing Secondary Heat Exchanger Stainless Ste...

Page 8: ... 690 0 5 12 3 0 5 12 1 6 40 RECTANGLE HOLE 10 2 260 1 6 40 2 2 56 3 9 100 5 2 132 6 7 169 8 1 206 4 Φ0 5 Φ13 2 0 4 0 24 10 6 OBLONG HOLE 4 0 24 0 6 6 15 OBLONG HOLE 0 4 10 26 0 661 25 9 658 1 1 27 3 5 89 WALL MOUNTING BRACKET INCLUDED ACCESSORY 7 2 183 2 1 5 3 7 Φ0 2 Φ6 About the Water Heater ...

Page 9: ...WATER OUTLET 3 4 WATER DRAIN VALVE WATER FILTER COLD WATER INLET 3 4 WATER DRAIN VALVE 17 8 452 14 2 362 8 7 220 2 4 60 27 0 687 AIR INLET FLUE COLLAR I DΦ2 4 Φ61 I DΦ2 4 Φ61 10 5 266 5 1 130 18 5 471 17 8 451 WIRING THROUGHWAY CONDENSATE DRAIN 1 2 GAS INLET 3 4 WATER DRAIN VALVE WIRING THROUGHWAY 9 7 246 11 3 288 1 7 42 5 7 144 2 2 56 3 3 83 6 0 152 15 4 392 15 6 397 About the Water Heater ...

Page 10: ...llation Water Supply Valve Condensate Drain Pipe Water Drain Valve with Water Filter Pressure Relief Valve Hot Water Valve Intake Pipe Exhaust Pipe Flex Vent 2 in Conversion Kit Gas Supply Valve Outdoor Vent Cap Outdoor Installation About the Water Heater ...

Page 11: ...tion against water damage is required to be installed under the Water Heater in case of leaks WARNING Do not install in the following places A location where it is not free from obstacles and stagnant air Near staircases or emergency exits A place where it may be threatened by falling objects such as under shelves On common walls as the appliance will make some operational noises while it is runni...

Page 12: ...ater heating appliance the potential for leakage at some time in the life of the product does exist The manufacturer will not be responsible for any water damage that may occur Water quality If this Water Heater will be installed in a location where the hardness of the supply water is high scale Build up may cause damage to the Heat Exchanger Perform suggested treatment and maintenance measures in...

Page 13: ...tion Before installing check for the following Install in accordance with relevant building and mechanical codes as well as any local state or national regulations or in the absence of local and state codes refer to National Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition In Canada see the Natural Gas and Propane Installation Code CSA B149 1 latest edition for detailed requirements WARNING Requir...

Page 14: ... Installation Required Clearances From the Water Heater Maintain the clearances from both combustible and non combustible materials 24 in 610 mm or more 36 in 910 mm or more Outdoor Vent Cap 3 in 76 mm or more 4 3 For Quick Connect Multi System Surrounding the area of installation When installing the Water Heater in a common side corridor 47 in 1 194 mm or more 84 in 2 134 mm or more the bottom ed...

Page 15: ...g Bracket Lower to the wall by 2 screws Anchoring Screw Mounting Bracket Lower 1 Ensure that the Wall Mounting Bracket is leveled Drill holes for the Wall Mounting Bracket and affix the Wall Mounting Bracket securely to the wall by 5 screws Finally make sure the bracket can support the weight of the Water Heater IN OUT The bracket has marking to assist with ensuring properly aligned connections Al...

Page 16: ...f the vent pipe has already been installed After installing the condensate drain pipe make sure that the area around the Water Heater is well ventilated open a window or a door if necessary Then operate the Water Heater and verify that condensate is coming out of the condensate drain pipe During normal use of the Water Heater condensate will begin to discharge from the condensate drain pipe within...

Page 17: ...if applicable the venting system manufacturer s instructions 1 Install the Water Heater 2 Determine the termination method horizontal or vertical etc 3 Determine proper location for wall or roof penetration for each termination NOTE Do not exceed maximum allowed vent lengths as described in this manual This Water Heater must be vented with plastic pipe materials as specified in the table below Ven...

Page 18: ...ted For 2 in flexible PP material Flex Vent 2 in Conversion Kit must be used when using 2 in flexible PP pipe for vent pipe installation Refer to the instructions provided with Flex Vent 2 in Conversion Kit for additional detail During the installation of Flex Vent 2 in Kit ambient temperatures must be greater than 40 F 5 C Afterwards installation site ambient temperature must be greater than 4 F ...

Page 19: ... combustion air to the Water Heater A separate combustion air intake pipe routed back to the Water Heater can be used in the remaining space if required the Water Heater venting system is approved for zero clearance and can be run directly beside the combustion air intake pipe Bolt or screw joints together to avoid sag Flexible pipe vertical offsets must not exceed 45 and are limited to a maximum ...

Page 20: ...he DIP switches Failure to perform this step will result a 73 code displayed on the Remote Controller and a cease in operation If this occurs disconnect then reconnect the electrical power to the Water Heater to reset the system Do not store hazardous or flammable substances near the vent termination and check that the termination is not blocked in any way Steam or condensed water may come out fro...

Page 21: ...ch 7 Maximum Vent Length Configurations For flexible pipe for chimney DuraVent Flex Through Chimney w Air Intake Only 3 in The vent length condition setting depends on the flexible pipe length the rigid pipe length and number of elbows Calculate an each ventilation system equivalent length then adjust the DIP switch Vent length condition DIP switch 7 Maximum equivalent vent length V Vertical H Hor...

Page 22: ...elect Long length Centrotherm Flex Through Chimney w Air Intake Only 3 in The vent length condition setting depends on the flexible pipe length the rigid pipe length and number of elbows Calculate an each ventilation system equivalent length then adjust the DIP switch Vent length condition DIP switch 7 Maximum equivalent vent length Equivalent length Short length OFF Exhaust vent V Vertical H Hori...

Page 23: ...the surrounding indoor air Combustion air Exhaust Non Direct Vent with Flex Vent 2 in Conversion Kit The Water Heater can be installed outside using the Outdoor Vent Cap Combustion air Exhaust Outdoor with Outdoor Vent Cap This Water Heater is suitable for Common Vent System To make a Common Vent System refer to the Common Vent installation manual or contact Pavilion Customer Center at https www p...

Page 24: ... line of the regulator vent outlet to a maximum vertical distance of 15 ft 4 5 m J Clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 6 in 15 cm for appliances 10 000 Btuh 3kW 12 in 30 cm for appliances 10 000 Btuh 3kW and 100 000 Btuh 30 kW 36 in 91 cm for appliances 100 000 Btuh 30 kW 6 in 15 cm for appliances 10 000 Btuh 3kW 9 in 23 cm fo...

Page 25: ...snow level Ceiling Interior Wall e g Hood Termination installation e g Hood Termination installation e g Low Profile Termination installation Exhaust 3 in 75 mm or 2 in 50 mm Intake 3 in 75 mm or 2 in 50 mm Intake Intake Overhang Exhaust Exhaust Exterior Wall If 3 ft 0 9 m distance between Intake and Exhaust cannot be ensured the installation can be carried out only in the installation method show...

Page 26: ...ections other than directly downward will increase the risk of freezing Reversing the air intake and exhaust pipes is not allowed Carbon Monoxide CO emissions and noise due to vibration will increase WARNING NOTE Do not use Hood termination Exhaust Intake Interior View Exterior View Interior View Exterior View Interior View Exterior View Exhaust Intake Exhaust Intake NOTE Upper side is exhaust low...

Page 27: ...ncentric Termination installation 2 in or 3 in Concentric Termination Install a securing strap to prevent movement of the termination For Horizontal PVC Concentric Termination PVC CPVC Material Only The concentric termination may be shortened but not lengthened from its original factory supplied length 2 in 50 mm or 3 in 75 mm PVC or CPVC pipe may be used with the concentric termination Maintain t...

Page 28: ...in End of 90 Elbow Bird Screen is not supplied with water heater order separately To prevent excessive condensation formation only the vent termination should be located on the exterior of the building When the vent termination is located not less than 8 ft 2 4 m from a vertical wall or similar obstruction terminate above the roof at least 2 ft 0 6 m but not more than 6 ft 1 87 m in accordance wit...

Page 29: ...ouplings are required Increaser couplings need to be used just prior to 3 in Concentric Termination The length of the pipe between the Increaser couplings and the Exhaust and Intake Flue of the Water Heater and the concentric termination vent pipe connections should be up to 6 in 152 mm For Vertical PVC Concentric Termination PVC CPVC Material Only The concentric termination may be shortened but n...

Page 30: ...mum vertical distance of 15 ft 4 5 m J Clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 6 in 15 cm for appliances 10 000 Btuh 3kW 12 in 30 cm for appliances 10 000 Btuh 3kW and 100 000 Btuh 30 kW 36 in 91 cm for appliances 100 000 Btuh 30 kW 4 ft 1 2 m below or to side of opening 1 ft 300 mm above opening K Clearance to a mechanical air su...

Page 31: ...ing property damage personal injury or death Refer to the instructions provided with the conversion kit for additional details WARNING For SV Conversion Kit For Flex Vent 2 in Conversion Kit 1 Secure the Flex Vent 2 in Conversion Kit to top of the Water Heater Refer to the instructions provided with Flex Vent 2 in Conversion Kit for additional detail 2 Disconnect the electrical power and then turn...

Page 32: ...in H Outdoor make up air is provided Direct or Vertical ducts 50 in example 10 in W 5 in H Horizontal ducts 100 in example 20 in W 5 in H If the Water Heater is installed in a mechanical closet a minimum of permanent clearance of 4 in or more in front of the Water Heater is required In order to facilitate maintenance and repair a minimum clearance 24 in or more should be met If combustion air will...

Page 33: ...ert Bird Screen in End of Termination Bird Screen is not supplied with water heater order separately It is not necessary to use Bird Screens with the Hood Termination Either a tee or the Hood Termination termination may be used for the vent termination Hanger Straps Slope the horizontal vent 1 4 in upwards for every 12 in 305 mm toward the termination Above Grade Maximum snow level 12 in 305 mm Mi...

Page 34: ...e vent pipe manufacturer s instructions A short horizontal section is required to prevent debris from falling into the water heater When using a horizontal section slope the horizontal vent 1 4 in upwards for every 12 in 305 mm toward the termination to drain condensate About the termination Insert Bird Screen in End of 90 Elbow Bird Screen is not supplied with water heater order separately To pre...

Page 35: ...t 2 ft 0 6 m but not more than 6 ft 1 87 m in accordance with the National Fuel Gas Code ANSI Z223 1 NFPA 54 or Natural Gas and Propane Installation Code CSA B149 1 Roof Flashing Storm Collar When the vent penetrates a floor or ceiling and is not running in a fire rated shaft a firestop and support is required Round 3 in or 4 in B Vent used as chase for 2 in flexible PP pipe Firestop The aluminum ...

Page 36: ...turn ON DIP switch 2 if outdoor installation Refer to page 56 for the location of the DIP switch bank and how to change the DIP switch Failure to perform this step will result a 73 code displayed on the Remote Controller and a cease in operation If this occurs disconnect then reconnect the electrical power to the Water Heater to reset the system Here 6 6 Outdoor Installation Venting the Water Heat...

Page 37: ...onversion kits available for some models The conversion kit shall be installed by a qualified service agency in accordance with the manufacturer s instructions and all applicable codes and requirements of the authority having jurisdiction The qualified service agency is responsible for the proper installation of this kit Improper installation of this kit will void the Pavilion Limited Warranty Con...

Page 38: ...eath WARNING Calculation Example A partial set of sizing tables are printed on page 40 In cases where these tables are not appropriate refer to the NFPA 1 Draw a sketch of a piping system Enter the system information e g Point of delivery Outlet A clothes dryer 35 000 Btu h Outlet B range oven unit 75 000 Btu h Outlet C water heater 199 900 Btu h Outlet D furnace 100 000 Btu h 2 Determine the gas ...

Page 39: ...ired demand for the section is found Read up to find the size Repeat for each section of piping Enter this size in the table below 5 Enter the input rating for each appliance in the table below For natural gas appliances enter the input rating in Btu h 1000 ft3 h For propane appliances enter the input rating in Btu h Enter the outlet length from each appliance to the point of delivery in the table...

Page 40: ...e Drop Pipe Size Length including fittings 10 ft 20 ft 30 ft 40 ft 50 ft 60 ft 70 ft 80 ft 90 ft 100 ft 125 ft 150 ft 175 ft 200 ft 3 m 6 m 9 m 12 m 15 m 18 m 21 m 24 m 27 m 30 m 38 m 45 m 53 m 60 m 1 2 in 364 250 201 172 153 138 127 118 111 105 93 84 77 72 3 4 in 762 524 420 360 319 289 266 247 232 219 194 176 162 151 1 in 1 440 986 792 678 601 544 501 466 437 413 366 332 305 284 1 1 4 in 2 950 2...

Page 41: ...lves may be used The pressure relief capacity must not exceed 150 psi Do not install a shutoff valve between a relief valve and the Water Heater The relief valve must be installed such that the discharge will be conducted to a suitable place for disposal when relief occurs No reducing coupling or other restriction may be installed in the discharge line The discharge line must be installed to allow...

Page 42: ...umulating and clogging fixtures NOTE Do not use lead PVC iron or any piping which has been treated with chromates boiler seal or other chemicals Outdoor Installation Perform the following insulation measures for prevention of freezing Take appropriate heat insulation measures e g wrapping with heat insulation materials using heat tape electric heaters solenoids or pipe covers according to the clim...

Page 43: ...ef Valve to allow for flushing 3 See the page 6 for more detail information about Scale Inhibitor 4 Flushing is required if a water treatment device is not installed NOTE Damage to the Water Heater as a result of the items below is not covered by the Pavilion Limited Warranty Water in excess of 12 gpg 200 mg L of hardness Poor water quality See the Water Quality List on page 12 The Remote Controll...

Page 44: ...Exchanger when the code C1 appears 1 2 3 4 9 The factory default of this service reminder is disable If desired the customer or installer needs to enable the service reminder connect the red connector marked SERVICE REMINDER When the code C1 appears Flush the Heat Exchanger Refer to the Procedure for flushing the Heat Exchanger on page 65 After completing the flushing the code will be reset To dea...

Page 45: ...e nearest drain is above the Water Heater Require the use of a condensate pump Size the pump to allow for a maximum condensate discharge of 2 GPH from the Water Heater Material of the condensate drain piping Use plastic pipe such as PVC for the drain line NOTE Do not use steel black iron or any other material which can corrode when placed into contact with acidic condensate Floor drain The end of ...

Page 46: ...ndensate is freely flowing from the condensate drain piping Condensate will begin flowing out of the Water Heater within 15 minutes after operation has started Freeze prevention Take measures to prevent the condensate drain lines from freezing insulation heat tape electric heaters etc Drain pipe Drain connecting supply Heat insulation material Connecting the Condensate Drain ...

Page 47: ...e the Water Heater Putting the redundant length of cord inside the Water Heater may cause electrical interference and faulty operation NOTE Do not let the power cord contact the gas piping Do not disconnect the electrical power when not in use When the power is off the freeze prevention in the Water Heater will not activate resulting in possible freezing damage Ground To prevent electrical shock p...

Page 48: ...on Pump Use a relay for larger pumps Ground Wire NOTE A dummy plug is inserted from the factory This connector must be removed before connecting the pump power connector Press lightly on the connector to release the dummy plug 5 Connect the ground wire green color wire to the screw at the base of the Water Heater 6 Reattach the front cover 4 screws 4 Pass the Remote Controller Cord through the wir...

Page 49: ...isconnect unnecessary Remote Controller prior to installing the Quick Connect Cord The Remote Controller can be connected to either Water Heater A or B only 1 Red 2 Black 3 White 4 Green 5 Blue 6 Blue 1 Red 2 Black 3 White 4 Green 5 Blue 6 Blue 1 Red 2 Black 3 White 4 Green 5 Blue 6 Blue 1 White 2 Green 3 Red 4 Black 5 Blue 6 Blue A B Quick Connect Cord Quick Connect Cord 2 tag The wire coloring o...

Page 50: ...ed in an easily accessible location Install the Remote Controller on an even wall surface Installing it on an uneven wall surface may cause the Mounting Bracket and the Remote Controller to be damaged and lead to failures Be sure to check the positions of wall studs or other obstructions when determining the installation location for the Remote Controller NOTE Avoid installing in a place where wat...

Page 51: ...peration See Owner s Guide Press the button approximately 5 seconds after connecting the electrical power to the Water Heater Check that the display appears on the Remote Controller Adjusting the Temperature Water Quantity Display 3 Press the button and hold it in for 2 seconds or more 4 Press the button several times until the item number 12 is displayed 5 Select F gal C L using the buttons F gal...

Page 52: ... 125 140 F In 5 F intervals For Celsius C 55 C 60 C 4 Set the button to ON when continuing to use the unit as is Otherwise let the unit sit for approximately 30 seconds When changing the temperature make sure to confirm with the customer that the temperature of the Hot Water will be very high and that there is a risk of scalding Hot water temperatures over 125 F 52 C can cause severe burns instant...

Page 53: ... Use the Flat Head Tapping Screws to attach the Mounting Bracket The Dry Wall Anchor and Flat Head Machine Screws are not used NOTE Never use electric drivers impact drivers etc Tightening with excessive force may result in deformation of the Mounting Bracket and or failures Mounting Bracket included part Dry Wall Anchor included part Flat Head Tapping Screw included part Confirm the orientation o...

Page 54: ...emote controller wires through the notch Winding around the notches For exposed wiring For wiring inside the wall Mounting Bracket Remote controller wires 6 Attach the Remote Controller to the Mounting Bracket Main remote controller Mounting Bracket Insert the bottom of the Main remote controller into the groove at the bottom of the Mounting Bracket Groove Do not install on the Mounting Bracket by...

Page 55: ...ontroller 1 Turn the Water Heater off by pressing the Power button on the Remote Controller 2 Disconnect then reconnect the electrical power to the Water Heater NOTE The setting must be done within the first 10 minutes of connecting the electrical power to the Water Heater Limiting the Maximum Output Temperature The maximum output temperature can be limited to prevent discharging hot water at too ...

Page 56: ...9 m ON OFF 4 001 7 000 ft 1 220 2 134 m OFF ON 7 001 10 000 ft 2 135 3 048 m ON ON For adjusting to accommodate longer vent runs When using PVC CPVC PP material Change DIP switch 7 and 8 by following the table below Vent length condition DIP switches 7 8 Less than 33 ft using 2 in 50 mm pipe OFF OFF 33 ft or more using 2 in 50 mm pipe ON OFF Less than 75 ft using 3 in 75 mm pipe OFF ON 75 ft or mo...

Page 57: ...ur or the gas supply fail to shut off turn off the manual control valve to the appliance Procedure to follow after step 5 for both installation of a single Water Heater and installation with a Quick Connect Multi System 6 Make sure that there are no obstructions blocking the condensate drain line from discharging condensate Be sure to check that condensate is freely flowing from the condensate dra...

Page 58: ...by the Pavilion Limited Warranty NOTICE Shutdown Instructions 1 Stop any water demand 2 Turn off the electrical power 3 Turn the gas control manual valve clockwise to the off position This Water Heater does not have a pilot It is equipped with an ignition device that automatically lights the burner Do not try to light the burner by hand 1 Read the safety information in the installation manual or o...

Page 59: ... pipe are properly installed Make sure that the vent system comforms with local codes state codes or national codes as ANSI NFPA and CSA Connecting the Gas Supply See page 37 40 Yes No Make sure that the gas type is compatible with the type indicated on the Water Heater s rating plate Clean out any debris from the gas piping before connecting the Water Heater Make sure that the gas piping size is ...

Page 60: ...Cord is correctly installed For installation with a recirculation pump Make sure that it is installed by the following method When using a pump 100 W or less connect the pump power cord to the pump control wires When using a large pump greater than 100 W a relay circuit is constructed Installation of the Remote Controller See page 50 55 Yes No Make sure that the location of the Remote Controller i...

Page 61: ...the set output temperature An aquastat is the minimum pump control requirement in order to maintain the full recirculation warranty Service Valve Kit with Pressure Relief Valve It is recommended the use of Service Valve Kit with Pressure Relief Valve with the installation The kit includes an integrated shut off and service valve with unions and a pressure relief valve Gas Supply Service Valve Kit ...

Page 62: ...essary to prevent cycle Service Valve Kit with Pressure Relief Valve It is recommended the use of Service Valve Kit with Pressure Relief Valve with the installation This kit includes an integrated shut off and service valve with unions and a pressure relief valve Mixing Valve If the system requires water for space heating at temperatures higher than required for other uses a means such as a mixing...

Page 63: ...laced upstream of the cold water branch Size the piping to allow for the maximum flow rates of the Water Heaters Make this distance as short as possible The hot water temperature will become unstable as the pipe length increases Service Valve Kit with Pressure Relief Valve Typical Plumbing Insulate or apply heating materials to both the cold water supply piping and the hot water supply piping to p...

Page 64: ...must be blue clear and stable The image of normal or abnormal flame is as shown figure below If the flame does not appear normal the burner may need to be cleaned by qualified service technician Pressure relief valve Operate the pressure relief valve once a year to ensure that it is functioning properly and there is no obstruction Turn the power off to the Water Heater before opening the pressure ...

Page 65: ... to the electrical power when flushing the Heat Exchanger The preparation of the flushing system 1 Close the gas supply valve 2 Close the water inlet valve V1 and the water outlet valve V2 3 Connect the one drain hose H1 to the drain valve V3 and then the other to the circulation pump 4 Connect the drain hose H2 to the circulation pump 5 Connect the drain hose H3 to the drain valve V4 6 Pour 1 gal...

Page 66: ...late the flushing solution through the Water Heater for 1 hour at a rate of 1 5 GPM or more 5 CCC Water Drain Valve 6 Turn off the circulation pump NOTE The Water Heater has a Water Drain Valve on the bottom of the Water Heater Place a bucket under the Water Heater to drain water from the Water Drain Valve Carefully unscrew the Water Drain Valve to rinse flushing solution out of the Water Heater f...

Page 67: ... Connect Multi System 1 Open the front covers 2 Connect the blue connector marked FLUSH for Water Heater needing to be flushed The Water Heater is isolated from Quick Connect Multi system when the blue connector marked FLUSH for flushing is connected Do not need to disconnect the Quick Connect Cord Sub Water Heater Main Water Heater Quick Connect Cord Do not need to disconnect Remote Controller Ci...