background image

© Panasonic Corporation 2015.

 
 

Order No: PAPAMY1505101CE 

 

 

 

 

Mono bloc Unit

 
 

WH-MDC12G6E5
WH-MDC16G6E5

Destination

Europe

Turkey

 

 

 

 

 

WARNING 

This service information is designed for experienced repair technicians only and is not designed for use by the general public. 
It does not contain warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product. 
Products powered by electricity should be serviced or repaired only by experienced professional technicians. Any attempt to 
service or repair the product or products dealt with in this service information by anyone else could result in serious injury or death. 

 

PRECAUTION OF LOW TEMPERATURE 

In order to avoid frostbite, be assured of no refrigerant leakage during the installation or repairing of refrigerant circuit.

 

Summary of Contents for WH-MDC12G6E5

Page 1: ...dvise non technical individuals of potential dangers in attempting to service a product Products powered by electricity should be serviced or repaired only by experienced professional technicians Any attempt to service or repair the product or products dealt with in this service information by anyone else could result in serious injury or death PRECAUTION OF LOW TEMPERATURE In order to avoid frost...

Page 2: ...ire 3 Do not tie up the power supply cord into a bundle by band Abnormal temperature rise on power supply cord may happen 4 Do not insert your fingers or other objects into the unit high speed rotating fan may cause injury 5 Do not sit or step on the unit you may fall down accidentally 6 Keep plastic bag packaging material away from small children it may cause suffocation 7 Do not use pipe wrench ...

Page 3: ...bloc unit 2 Do not release refrigerant during piping work for installation re installation and during repairing a refrigeration parts Take care of the liquid refrigerant it may cause frostbite 3 Make sure the power supply cord does not contact with hot part i e water piping High temperature may cause insulator of power supply cord damage hence electrical shock or fire 4 Do not touch the sharp alum...

Page 4: ...nput Power W Output Power W 60 Fan Speed rpm Cooling 600 Top Fan 640 Bottom Fan Heating 510 Top Fan 550 Bottom Fan Heat Exchanger Fin material Aluminium Pre Coat Fin Type Corrugated Fin Row Stage FPI 2 51 18 Size W H L mm 903 7 1295 4 38 1 Item Unit Mono Bloc Unit Dimension Height mm inch 1410 55 1 2 Width mm inch 1283 50 1 2 Depth mm inch 320 12 19 32 Net Weight kg lbs 147 324 Noise Level dB A Co...

Page 5: ...ch 15 00 19 32 Pump Motor Type DC Motor No of Speed 7 software selection Input Power W 112 Hot Water Coil Type Brazed Plate No of Plates 36 Size H W L mm 65 120 376 Water Flow Rate l min m3 h Cooling 35 0 2 1 Heating 45 9 2 8 Pressure Relief Valve Water Circuit kPa Open 300 Close 265 and below Flow Switch Magnetic Lead Switch Protection Device A Residual Current Circuit Breaker 30 Expansion Vessel...

Page 6: ...r protector to protect compressor Serviceability Improvement Breakdown Self Diagnosis function System Status Check Buttons for servicing purpose System Service Mode Button for servicing purpose Front maintenance design for Mono bloc unit Operation Condition Water outlet temperature C Ambient temperature C COOLING Maximum 20 43 Minimum 5 16 HEATING Maximum 55 35 Minimum 25 20 NOTICE When the outdoo...

Page 7: ...10 4 Location of Controls and Components 4 1 Mono Bloc Unit Air inlet rear Air outlet Air inlet side Handle 2 pieces front and 2 pieces behind Cabinet Front Plate Top Plate ...

Page 8: ... way Valve cable 3 min 0 5mm Booster Heater cord 3 min 1 5mm Room Themostat cable 4 or 3 min 0 5mm Tank OLP cable 2 min 0 5mm Tank Sensor cable 2 min 0 3mm External Controller cable 2 min 0 5mm Solar Three way Valve cable 3 min 0 5mm Solar Pump Station cable 2 min 0 5mm Type designation 60245 IEC 57 or heavier cord cable Remote Control Power Supply 1 Power Supply 2 7 It is advisable to avoid more ...

Page 9: ...20 5 Dimensions 5 1 Mono Bloc Unit 579 400 356 154 1410 615 426 5 175 275 413 30 c c 70 277 320 152 1283 256 30 293 318 5 50 45 45 45 83 5 Unit mm Top View Front View Back View Side View Side View ...

Page 10: ... Air Purge Valve Water Flow Switch Water Pump Water Inlet Connect to Sanitary Tank Water Outlet Connect to Sanitary Tank Drain Refrigerant Cycle Heating Water Cycle Heat Exchanger Heat Exchanger Strainer Strainer Receiver 4 Way Valve 2 Way Valve Gas Side 3 Way Valve Liquid Side 3 Way Valve Pressure Switch High Pressure Sensor Compressor Water Pressure Gauge Capillary Tube Expansion Valve Refrigera...

Page 11: ...L2 YLW HT1 L2 ORG O Y W CN OLP1 WHT B B OLP 80 3 C 1 2 CN FLOW YLW CN TH1 WHT CN TH3 WHT CN TH2 WHT CN OLP2 WHT CN RCV2 WHT CN THERMO WHT FLOW SWITCH WATER OUTLET TEMP SENSOR THERMISTOR WATER INLET TEMP SENSOR THERMISTOR REFRIGERANT TEMP SENSOR THERMISTOR BL 2 1 1 6 3 3 BL 1 1 HEX WATER OUTLET TEMP SENSOR THERMISTOR 1 1 1 2 3 2 NOISE FILTER CIRCUIT G 1 4 5 6 7 BL RECTIFICATION CIRCUIT RECTIFICATIO...

Page 12: ...WHT WHITE RED DC P CN EV 6 2 CN RY1 SWITCHING POWER SUPPLY CIRCUIT RECTIFICATION CIRCUIT PFC CIRCUIT DCN IN AC C BLUE DC N BLACK 2 DCN 2 BLACK FUSE 1 CN FM2 WHITE 1 4 7 7 4 2 CN FM1 CN PS W1 LOWER FAN MOTOR BLACK V U U RED P N V BLUE RED BLUE BLACK FG201 GREEN 3 2 WAY VA LVE MS R 1 DC P IN WHITE BL CAPACITOR ELECTRONIC CONTROLLER AC C BLACK B 1 CN ACL RY V1 AC BLK01 OPTIONAL 4 REA CTOR W GR W RELA...

Page 13: ... the pump speed 4 Press OFF ON button to exit PUMP SPEED ADJUST MODE During PUMP SPEED ADJUST MODE we can select AIR PURGE function by pressing FORCE button In AIR PURGE function the pump will operate ON and OFF for 10 minutes to purge the air in the hydraulic system Press again the FORCE button to exit AIR PURGE function PUMP SPEED ADJUST MODE will stop operation 0 10 13 20 30 40 50 70 60 WATER F...

Page 14: ... temperature 7 C DBT 6 C WBT Indoor water inlet temperature 30 C Indoor water outlet temperature 35 C Outdoor Temperature C Capacity kW Outdoor Temperature C Input Power kW 1 000 2 000 3 000 4 000 5 000 6 000 1 10 000 11 500 13 000 14 500 16 000 17 500 15 11 7 3 1 5 9 13 17 21 25 15 11 7 3 1 5 9 13 17 21 25 ...

Page 15: ...ure 35 C DBT C WBT Indoor water inlet temperature 12 C Indoor water outlet temperature 7 C Outdoor Temperature C Capacity kW Outdoor Temperature C Input Power kW 1 000 2 000 3 000 4 000 5 000 6 000 16 19 22 25 28 31 34 37 40 43 6 000 8 000 10 000 12 000 14 000 16 000 16 19 22 25 28 31 34 37 40 43 ...

Page 16: ... 12000 2960 12000 3390 12000 4100 25 12000 1380 12000 1660 11800 1940 11700 2230 11400 2740 is rating based on T 8 18 2 2 WH MDC16G6E5 Water Out C 30 35 40 45 55 Outdoor Air C Capacity W Input Power W Capacity W Input Power W Capacity W Input Power W Capacity W Input Power W Capacity W Input Power W 15 10600 4090 10300 4380 10000 4670 9700 4960 7900 4840 7 11900 4030 11400 4430 10800 4830 10300 52...

Page 17: ...10000 1730 25 12080 2900 15700 3050 10000 1970 35 10000 3560 12000 3670 10000 2150 43 7800 3800 11100 3190 8000 2850 18 3 2 WH MDC16G6E5 Water Out C 7 14 18 OD Ambient C Capacity W Input Power W Capacity W Input Power W Capacity W Input Power W 16 9200 1620 16400 2580 12200 2450 25 14400 3920 19200 3830 12200 2790 35 12200 4760 15000 4980 12200 2960 43 7750 3400 13800 5950 9700 4000 ...

Reviews: