background image

English

Read through the Installation Instructions before you proceed 
with the installation.
In particular, you will need to read under the “Safety 
Precautions” on page 2.

Installation Instructions

Wireless Remote Controller

Model No.

 

CZ-RWSU3

Panasonic Corporation

1006 Kadoma, Kadoma City, Osaka, Japan

H0916-0

CV6233317755

Panasonic Corporation
http://www.panasonic.com

Contents

Safety Precautions ...................................... 2
Part Names ................................................... 3
Supplied accessories .................................. 3
Speci

fi

 cations .............................................. 3

Installation Precautions .............................. 4

Installation Location for the Receiver ............... 4

Mounting ...................................................... 4

Installing the Receiver ...................................... 4

Wiring ........................................................... 5

Basic Wiring Diagram ....................................... 5
Wiring for the Receiver ..................................... 5

Settings ........................................................ 6

Setting for receiver ........................................... 6
Setting for Wireless Remote Controller ............ 6
Test Operation .................................................. 8
Self-diagnostics table and 
detected contents ............................................. 9

Summary of Contents for CZ-RWSU3

Page 1: ...Kadoma City Osaka Japan H0916 0 CV6233317755 Panasonic Corporation http www panasonic com Contents Safety Precautions 2 Part Names 3 Supplied accessories 3 Specifications 3 Installation Precautions 4 Installation Location for the Receiver 4 Mounting 4 Installing the Receiver 4 Wiring 5 Basic Wiring Diagram 5 Wiring for the Receiver 5 Settings 6 Setting for receiver 6 Setting for Wireless Remote Co...

Page 2: ... Turn off the circuit breaker of the units before installation Ask your dealer or professionals for installation and electric work This controller shall be installed in accordance with National Wiring Regulations Connect and fix the specified cables for wiring securely Do not allow the connection to be exposed to the external force of the cables Choose an installation location that sufficiently su...

Page 3: ...oller 1 Remote Control Holder 1 LR03 Size Battery 2 Instructions 1 Quick Reference 1 Screw M4 16 2 Clamper 1 Specifications Wireless Remote Controller Dimensions H 182 mm W 61 mm D 18 5 mm Weight 140 g Including batteries Power Source Two LR03 size batteries Clock Accuracy 30 seconds month at 25 C Receiver Dimensions 29 7 mm H 211 8 mm W 211 8 mm D Weight 160 g Power Source DC16 V supplied from in...

Page 4: ...ndoor unit electric component box Air Inlet grille 2 Remove the corner cover Remove the screw fixing the corner cover Screw Corner cover Convex part Place a hand on both the right and left convex parts of the corner cover to remove it Corner cover Ceiling panel 3 Wire the receiver Hang the string of the receiver on the pin of the ceiling panel Receiver Pin String Pass the wiring from the wireless ...

Page 5: ...trollers cannot be used simultaneously for a single indoor unit Be careful not to connect cables to other terminals of indoor units e g power source wiring terminal Malfunction may occur Do not bundle together with the power source wiring or store in the same metal tube Operation error may occur If noise is induced to the unit power supply attach a noise filter Wiring shown below is prohibited R1 ...

Page 6: ...ddress Address Address Address ON OFF States ALL 1 2 3 4 5 6 Position of the receiver s address switch Receipt is possible at all of the address positions 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 OFF ON Setting for Wireless Remote Controller Room Temperature Sensor Settings The indoor unit and the wireless remote controller are equipped with room temperature sensors The sensing of room temp...

Page 7: ...r settings are to be changed repeat steps 2 to 4 6 When all settings have been made press the start stop button Operation procedure and function display Item Number 1 2 6 3 4 Detected contents Set Contents Factory setting 1 Operation Mode 2 Flap Display No Display 1 3 Select Fan Speed No Display 4 Display of Set Temperature C F Setting Off 2 C 5 Time Display 24 Hour No Display AM PM 24 Hour 6 Vent...

Page 8: ...e wall and check that normal receiving is possible Remove the remote controller from the remote control holder Test Operation Preparation Turn on the circuit breaker of units and then turn the power on After the power is turned on remote controller operation is ignored for approx 1 minute because setting is being made This is not malfunction Contents received while setting are disabled 1 To start ...

Page 9: ...on device P01 P09 P14 Alternately Operation of outdoor protection device P02 P08 P15 P31 Alternately Error in the indoor thermistor F01 F03 F10 F11 Alternately Error in the outdoor thermistor F04 F09 F12 F28 Alternately Error in the indoor EEPROM F29 Simultaneously Error in the outdoor EEPROM F30 F31 Simultaneously Error related to the compressor H01 H31 Error in indoor settings L01 L03 L05 L09 Si...

Page 10: ... Panasonic Corporation 2016 ...

Reviews: