Ranges and Resolution

Resolution is fixed as indicated below
3-1/2 digit model ranges are limited by number of display digits: 2, 
20, 200, and 2000 ranges display 1.999, 19.99, 199.9, and 1999.

psig

 

Gauge reference pressure

psig vacuum

  Vacuum gauge, minus sign not used

psia

 

Absolute reference (open port reads atmospheric 

 

pressure, reads zero at full vacuum)

Available Ranges

15.00 psig vacuum 

 

30.0 inHg vacuum 

 

±15.0 psig 

 

3.00 psig 

 

5.00 psig 

 

15.00 psia 
15.00 psig 
30.0 psia 

 

30.0 psig 

 

60.0 psig 
100.0 psia 
100.0 psig 
199.9 psig 
300 psig 

 

500 psig 
1000 psig (1KG) 
1999 psig (2KG) 
3000 psi (3KG) * 
5000 psi (5KG) *
Bold

  Standard ranges. Contact Omega Engineering or other  

 

engineering units such as kPa, atm, bar, mbar, inHg,  

 

mmHg, inH2O, ftH2O, torr, kg/cm

2

, cmH2O, oz/in

2

.

 

DPG1001L , DPG1101L (high accuracy) not available in 

 

3 psi, 5 psi, vacuum, or bipolar ranges. 

 

DPG1001L , DPG1101L (high accuracy) applies to output 

 

only due to limitation of 3-1/2 digit display.

*

 

4 digit range. All others 3-1/2 digit

Accuracy

Includes linearity, hysteresis, repeatability
DPG1000L, DPG1100L:  ±0.25% of full scale ±1 LSD
DPG1001L, DPG1101L:  ±0.1% of full scale ±1 LSD 
±0.1% accuracy not available with 3 psig, 5 psig, absolute, 
vacuum, or bipolar ranges
Sensor hysteresis:  ±0.015% FS, included in accuracy 
Sensor repeatability:  ±0.01% FS, included in accuracy

DPG1100L, 

DPG1101L, 

Ranges >2000

DPG1000L, 

DPG1001L, 

Ranges >2000

DPG1100L, 

DPG1101L

DPG1000L, 

DPG1001L

The DPG1000L/DPG1100L series is a 2-wire pressure transmit-
ter with a digital display. It is powered by the 4-20 mA current 
loop and produces an analog output signal. The output is filtered 
to improve noise immunity. It may also be connected to a low 
voltage DC supply for use as a pressure indicator. 
Ranges up to 1999 have a 3.5 digit display and true analog 
output. Ranges 2000 and above are microprocessor based 
and use a 4 digit display with an alphanumeric lower display. 
The output is a 12,000 count analog 4-20 mA signal updated 
approx. 16 times per second.
Models are designed for continuous operation. Warm-up time is 
negligible. The display will show the system pressure/vacuum 
and the loop current will be proportional to the system pressure/
vacuum; 4 mA = Zero or low end, 20 mA = Span, full-scale or 
high end.
The TEST button, when depressed, switches the display and 
output loop to a preset level determined by the setting of a Test 
potentiometer. This is useful for testing the 4-20 mA output 
signal without having to alter system pressure.

Display

Resolution is fixed. Some ranges may not use all display digits.
Ranges to 1999: 3-1/2 digit LCD, 1/2" digit height 
 

3 readings/sec. nominal display update

Ranges >2000:  4 digit LCD, 0.4" digit height with 5 character 
 

0.25" H alphanumeric lower display 

 

4 readings/sec. nominal display update

Power

Any DC supply/loop resistance that maintains 8-32 VDC at 
gauge terminals. 
May be operated as a 4-20 mA loop transmitter or a DC pow-
ered pressure indicator.
Reverse polarity protected. Designed for continuous operation.
3 ft long, 2-conductor 22 AWG cable with stripped wire ends

Output Characteristics

Ranges to 1999:  Analog output, 50 msec. typical response  
 time
Ranges 2000-up: 12,000 counts over sensor range 
 

Updated approximately 16 times per second

Low Loop Warning

Ranges to 1999:  Colon appears on display at approximately 
 

7.8 VDC. Below 7.8 VDC erratic operation  

 

may occur.

Ranges 2000-up:  All decimal points flash. Below 7.8 VDC  
 

erratic operation may occur and gauge may 

 

shut off.

Test Function

TEST button, when depressed sets loop current and display 
to output test level, independent of pressure input, to allow 
testing of system operation. 
Output test adjustment:  0-100% or range

Calibration

Ranges to 1999:  Front zero, span and test potentiometers 
 

Non-interactive zero and span, ±10% range 

 

Internal potentiometers: Loop 4 mA and 20 mA

Ranges 2000-up:  User set pass code for calibration mode 
 

zero, midpoint, span as required for each range

Process Connection and Material

1/4” NPT male  
Sensor and all wetted parts are 316L stainless steel 

DPG1000L, DPG1001L, DPG1100L, DPG1101L

DPG1000L 

4-20 mA Loop Powered 

DPG1001L 

4-20 mA Loop Powered, High Accuracy 

DPG1000L 

4-20 mA Loop Powered, NEMA 4X 

DPG1101L 

4-20 mA Loop Powered, High Accuracy, NEMA 4X

M4890/0818

4-20 mA Loop Powered Pressure 

Transmitters

INSTRUCTION

SHEET

Shop online at omega.com  e-mail: [email protected] 

For latest product manuals: www.omegamanual.info

TM

Housing

Standard: Epoxy powder coated aluminum case and rear 
cover, ABS/polycarbonate bezel, polycarbonate label, front and 
rear rubber gaskets
NEMA 4X: UV stabilized ABS/polycarbonate case and  
gasketed rear cover with six captive stainless steel screws. 
polycarbonate label

Weight

Gauge: 9 ounces, shipping weight: 1 pound (approximate)

Overpressure, Burst, Vacuum

3000 psig sensor:  5000 psig overpressure, 10,000 psi burst 
5000 psig sensor:  7500 psig overpressure, 10,000 psi burst 
All other sensors:  2 X sensor range overpressure 
All other sensors:  4 X sensor range burst
>2X overpressure will permanently damage sensor
Vacuum service: ±15 psig, 15 psia, 15 psig, 30 psia, 100 
psig, 100 psia, 200 psig sensors. Vacuum on all others will 
permanently damage sensor 
4 digit ranges (3000 psi, 5000 psi) 
112.5% full scale out-of-range display: 1– – – or 1 –.–.–.– 
Under-range display (non-vacuum sensors): –Err

Environmental

Storage Temperature: 

–40 to 203°F (–40 to 95°C)

Operating Temperature: 

–4 to 185°F (–20 to 85°C)

Compensated Temperature:  32 to 158°F (0 to 70°C)

¼" NPT

2.88"

3.38" Standard 

3.5" NEMA 4X

0.75"

2.0"

Cecomp Electronics / Made in USA

1.65"

NEMA 4X

3.0"

Standard

PSIG

Span

Zero

Test

TEST

Potentiometer  

covers (3)
Standard:  

plastic caps
NEMA 4X:  

nylon screws  

with o-rings

Turn at hex 

fitting only

Allow 1" 

clearance

Allow 1" 

clearance

Turn at hex 

fitting only

TEST

s

t

¼" NPT

0.75"

X X X X X

88888

2

OMEGA Engineering Inc. / Made in USA

3.38" Standard 

3.5" NEMA 4X

Low voltage 

indicator

3 ft long 2 

conductor 22 

AWG cable 

with stripped 

and tinned 

wire ends

Ranges >2000