background image

ATTENTION!!!

ZLD-XX/EM/ADR

ADDRESSABLE 

SELF TESTING MAINTAINED 

EMERGENCY ILLUMINATION SIGNS

IP40

922502862_09_009

922502862_09_009

4

5

C:

 Including inhibiting mode

LABELING EXPLANATION:

B:

 Including remote test mode

NOTE:

 LED= Light Emitting Diode

X:

 Self contained

1:

 Maintained operation 

(*) 

A:

 Including test device

G:

 Internally illuminated safety sign

(*) 

Maintained operation: The luminaire lights its illumination source, when it is powered 

by the mains power supply or not

Non  Maintained  operation:  The  luminaire  lights  its  illumination  source,

 

only  in  mains 

power supply’s failure.

180:

 3 hours duration

Warranty

Olympia Electronics guarantees the quality, condition and operation of the goods. The period of warranty is 
specified in the official catalogue of Olympia Electronics and also in the technical leaflet, which accompanies 
each product. This warranty ceases to exist if the buyer does not follow the technical instructions included in 
official  documents  given  by  Olympia  Electronics  or  if  the  buyer  modifies  the  goods  provided  or  has  any 
repairs  or  re-setting  done  by a  third  party,  unless  Olympia  Electronics  has  fully  agreed  to  them  in  writing. 

Products  that  have  been  damaged  can  be  returned  to  the  premises  of  our  company  for  repair  or 
replacement, as long as the warranty period is valid.

Olympia Electronics reserves the right to repair or to replace the returned goods and to or not

 

charge the 

buyer  depending  on  the  reason  of  defection.  Olympia  Electronics  reserves  the  right  to  charge  or  not  the 
buyer the transportation cost.

European
manufacturers

72

nd

 

km

O

.

N

.

R

Thessaloniki-Katerini

P.C. 60300 P.O. Box 06 Εginio Pierias Greece

www.olympia-electronics.com

[email protected]

Non

maintained

NM

Thank you for your trust in our products  

Olympia Electronics - European manufacturer

16m

30m

38m

Maintained

Μ

Warranty

The light source of this luminaire is not replaceable when the light source reaches 
its end of life the whole luminaire shall be replaced.

Battery Replacement

Dimensional Drawings (mm)

Olympia Electronics S.A

.

8.5- 10.5V DC

1200mW

1400mW

1600mW

1111153

1211153

1311153

45 °C max. across the board

Non reversible connection between main pcb and led module

LED Characteristics

MANUFACTURER
MODEL NUMBER

VOLTAGE RANGE

CONNECTIONS

NOMINAL POWER

TEMPERATURE (tc)

220-240V AC

 

/ 50-60Hz

3.8W / 6.5VA

28mA

1.3

0.60

0.62

4W / 6.7VA

29mA

19V

4.3W / 6.9VA

30mA

Technical Characteristics

OPERATION VOLTAGE

MAXIMUM POWER CONSUMPTION
SUPPLY CURRENT

3.6V / 1.5

 

Ah

BATTERY (Ni-MH)
INSULATION BETWEEN SUPPLY & BATTERY CIRCUIT

WIRE CROSS SECTION

U-OUT
EOFi

Basic insulation

2

2

0.3mm  - 3.3mm  (22-12AWG)

BATTERY PROTECTION

18

 

white

 

LEDs

21

 

white

 

LEDs

24

 

white

 

LEDs

3h

CHARGE TIME

MINIMUM DURATION
LIGHT SOURCE

24 hours

LED Charge, Lamp Fault LED, Battery Fault LED

EN 60598-1, EN 60598-2-22, ΕΝ 55015,
ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

IP40

16m

30m

38m

VIEWING DISTANCE

DEGREES OF COVER PROTECTION

PRODUCED IN ACCORDANCE WITH

OPERATION TEMPERATURE RANGE

o

5

 to 40  C

Aluminum, Acrylic Plate, ABS/PC

1145gr.

1585gr.

780gr.

290 x 38 x 172 mm

350 x 38 x 242 mm

450 x 38 x 295 mm

RELATIVE HUMIDITY

CONSTRUCTION MATERIAL

EXTERNAL DIMENSION (L x W x H)

WEIGHT
GUARANTEE

Up to 95% 

3 years (1 year for the battery)

INDICATIONS

Deep discharge and overcharge protection / the control gear will recharge the battery normally after the test of 22.3

270 - 360mA

310mA

270 - 370mA

315mA

255 - 360mA

290mA

140 - 165mA

MIN MAX. DISCHARGE VOLTAGE
MIN MAX. DISCHARGE CURRENT
Rated CURRENT @3.6V
MIN MAX. CHARGE CURRENT
MAX CHARGE VOLTAGE

3 - 4.2V

5V

LIGHT SOURCE LUMINOUS FLUX (MAINS / EMERGENCY)

125lm/125lm

145lm/125lm

170lm/125lm

CONTROL GEAR WITH AUTOMATIC
TEST FUNCTION

125/145/170lm

Light output

Ni-MH

Battery

2

2

1

1

It can be done only by a competent person and after the mains interruption

.

Remove  the  old  battery  and  place  a  new  one  of  the  same  type  and  characteristics  and 
assembly the luminaire.

WARNING

!!

 

Use a maximum torque of 

0,25Ν

m

 

to tighten the screws

.

A B C G

1

X

1 8 0

ZLD-28/EM/ADR

ZLD-28/EM/ADR: 290 x 38 x 172mm

ZLD-34/EM/ADR

ZLD-34/EM/ADR: 350 x 38 x 242mm

ZLD-28/EM/ADR

ZLD-34/EM/ADR

ZLD-44/EM/ADR

ZLD-44/EM/ADR

ZLD-44/EM/ADR: 450 x 38 x 295mm

172

290
350
450

242 295

38

36

50

182

100

46

44
70

Controlgear classification in accordance with IEC 62034: with automatic test function

The controlgear has mains-connected windings of transformer

The controlgear 

is suitable for LED modules only

The controlgear is proof against supply voltage polarity reversal

 The lamp controlgear relies upon the luminaire enclosure for protection against accidental contact with live part (7.2 BS EN 61347-2-7)

Integrated SPD

3h

Duration

ADR