GENERAL

This  luminaire  is  used  in  places  where 
emergency luminaires are needed.
E a c h   l u m i n a i r e   m u s t   b e   p e r m a n e n t l y  
connected to mains power supply

.

In normal operation  the led strip lights and the 
capacitor is charging.
In  case  of  a  mains  power  supply failure  the 
luminaire  will  light the led strip  automatically 
in emergency mode.  When the  mains  power  
supply    is    restored  the  device  turns  to  normal 
operation.

INSTALLATION

To  install  the  luminaire  follow  the  installation 
instructions on page 3.

Capacitor charging

The  capacitor  charging  is  completely  and 
accurately  controlled

In  this  case,  is

 

achieved 

the  perfect  capacitor  maintenance

as  well  as 

the  elongation  of  its  duration

When  the 

capacitor  has  completely  charged

it  charges 

with a maintenance current.

Capacitor Cut-off

The luminaire enters in this operation when the 
mains power supply fails

 

and capacitor has lost 

its  energy

During  this  operation  the  luminaire 

enters  the  idle  state

 

and  the  capacitor’s 

consumption is negligible.

Manual

 Test

The  manual  test  can  be  conducted  only  if  the 
main  power  supply  and  the  capacitor  is 
connected.  By  pressing  the  TEST/RESET 

button  briefly  (page  3)  an  emergency  operation 
test  is  initiated.  During  this  test  period  all 
indication  LEDs  are  OFF  and  the  whole 
emergency circuit is monitored. 

Automatic Operational Test

This test includes all the operations that provide 
the  manual  test  and  is  conducted  automatically 
every  15  days.  In  order  to  be  performed,  the 
main power supply and the capacitor should be 
connected. 

Manual Autonomous Test

If  the  Test  button  is  pressed  for  a  period 
between  5  to  10  seconds  (with  the  capacitor   
fully  charged),  the  illumination  sign  will  enter  in 
counting  autonomy  condition. 

If  the  capacitor  is 

not fully charged this command is ignored

.

The  BAT  FAULT  LED  blinks  during    the 
measurement,  indicating  this  process  to  the 
user.  This  measurement  duration  is  equal  with 
the  nominal  autonomous  duration  of  the 
luminaire  and  at  the  end  of  the  process,  if  the 
measured  duration  was  at  least  the  nominal 
autonomous  duration,  the  BAT  FAULT  LED  is 
turned 

OFF, 

in 

the 

other 

hand 

stays 

continuously  ON  indicating  to  the  user  that  the 
capacitor must be replaced.          

Automatic Autonomous Test

The  Automatic  Autonomous  Test  is  conducted 
and  measures  the  luminaire’s  sign’s  back  up 
operation  and  emergency  duration.  This  test  is 
conducted  automatically  every  six  months

In 

order  to  be  performed,  the  main  power  supply 

Page

 1

 from

 

4

GR-900/30L/SC

 Waterproof Self Testing Maintained Emergency Luminaire 

220-240V AC/50-60Hz

TECHNICAL CHARACTERISTICS

 

(for LED module specifications see page 4)

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY

EXTERNAL DIMENSIONS (L x W x H) 
TYPICAL WEIGHT

GUARANTEE 

OPERATION VOLTAGE

MAXIMUM POWER CONSUMPTION
BACK UP  SOURCE

CHARGING TIME

INDICATIONS - CONTROLS

CAPACITOR PROTECTION

MINIMUM AUTONOMOUS DURATION

DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH

LIGHT SOURCE INTENSITY 

ILLUMINATION SOURCE

3h

CHARGE, LAMP FAULT, BAT FAULT

TEST button

From overcharge

o

-40 to 65  C

Up to 95% 

10 years

363 x 145 x 73 mm 

  White LEDs 

6W / 6.5VA /PF: 0.92

IP65

60 min

  250lm (230V AC) / 90lm (emergency) 

1012gr.

Super Capacitor A-900/SC

Page

 

4 from

 

4

Important notice for the installed luminaires in one area !!!

The installer must connect the capacitor’s connector first and then should power the luminaire. 
The capacitor connection must have at least a time variation of 1.5 minute for each luminaire. 
With this variation, it is ensured that the non synchronized Automatic Autonomous Test for two or 
more luminaires installed in one area, is not conducted in the same day.

    

EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

Super capacitor replacement

 

 (Α-900

/SC

)

It  can  be  done  only  by  a  competent  person  and  after 
the mains interruption

1. 

Unfasten the 4 screws (step 8 page 3) and remove the 

diffuser

.

  Unfasten  the  2  retaining  screws  and  remove  the 

reflector (step 7 page 3).

2. Disconnect the connector and remove the old 

capacitor 

pack by untastening the retaining screws       .

    

 

3. Connect the new 

capacitor pack (step 4

 of the installation

 

procedure

place it in the position 

of the old one

 and fasten the removed screws

.

4. 

Refit the removed parts in previous steps

 and power the

 

device. 

   

s

Thank you for your trust in our products  

Olympia Electronics -  European manufacturer

(*)

 

Maintained operation: The luminaire lights its 

illumination source, when it is powered by the mains 
power supply or not

Non Maintained operation: The luminaire lights its 
illumination source,

 

only in  power supply’s failure.

Note!! T

he installer should fill in

, on the specification 

label,

 the letter 

G

 if the luminaire is used as a safety 

sign

.

NOTE: 

LED= Light Emitting Diode

LABELING EXPLANATION:
X: 

Self contained 

  

1: 

Maintained 

(*)

A: 

Including test device

G: 

Internally illuminated safety sign 

 

60: 

1 hour duration  

The light source contained in this luminaire shall only be replaced by the manufacturer, or his 

agent, or a similar qualified person.

NOTE! The light source is non-user replaceable.

WARRANTY

Olympia Electronics guarantees the quality, condition and operation of the goods. The period of 
warranty is specified in the official catalogue of Olympia Electronics and also in the technical leaflet, 
which accompanies each product. This warranty ceases to exist if the buyer does not follow the 
technical instructions included in official documents given by Olympia Electronics or if the buyer 
modifies the goods provided or has any repairs or re-setting done by a third party, unless Olympia 
Electronics has fully agreed to them in writing. 

Products that have been damaged can be returned to 

the premises of our company for repair or replacement, as long as the warranty period is valid.

Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge 
the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or 
not the buyer the transportation cost.

HEAD OFFICE

72

nd

 

km

O

.

N

.

R

Thessaloniki-Katerini

P.C. 60300 P.O. Box 06 Εginio Pierias Greece

www.olympia-electronics.gr
[email protected]

LED MODULE CHARACTERISTICS

Manufacturer

Model Number
Voltage Range

Connections

Nominal Power

Temperature (tc)

Olympia Electronics S.A.

45 °C max. across the board

Cable connection with non reversible connectors

17.4-21.6V DC

2W

GR-900/30L/SC

1505153

923900000_09_010

923900000_09_010

X

1

6

0

A

G

S

S