GENERAL

o

These  devices  are  used  indoors 

(

ta  40 C

)

 

in places where emergency luminaires are 
needed.  The  luminaires

 

GR-270  and  GR-

272  are  suitable  for  corridors  lighting  and 
the

 

GR-271  and  GR-273  for  open  area 

lighting

.

 Each device must be permanently 

connected  to  mains  power  supply

.

  In 

normal operation the battery is charging. In 
case  of a mains power supply failure  the 
device  will  light  the  illumination  led 
automatically  in  emergency  mode.  When 
the    mains    power    supply  is  restored  the 
device turns to normal operation.

INSTALLATION

To install the luminaire follow the 
installation instructions 

ο

n page 2.

ΑΤΤΕΝΤΙΟΝ

!!!

1. Operations for installation, maintainance 
or  testing  must  be  done  by  authorized 
personel only

.

2. 

The  device  must  be  connected  to  the 

mains power supply thru a fuse dependent 
by  the  total  amount  of  the  line’s    power 
load

.

3. 

It is sugested to check every month the 

indication LED for battery charging, and by 
pushing the TEST button (use a pointy tool 

with    diameter  of  2mm  max.)  to  check  the 
emergency  cirquit.  The  illumination  LED 
should  light  as  long  as  the  TEST  button  is 
pressed

.  In  the  opposite  condition  contact 

the installer.

 

4. 

It  is  sugested  to  check  every  6  months 

the  minimum  autononous  duration  by 
disconnecting  the  mains  power  supply

.

 

Count the time that  the luminaire lights and 
in  case  of  less  time  than  the  minimum 
autonomous  duration  the  battery  must  be 
r e p l a c e d .   I f   t h e   m e a s u r e d   t i m e   i s  
considerably  less  than  the  minimum 
autonomous  duration 

 

contact  the  installer.

I n   c a s e   o f   b a t t e r y   o r   l i g h t   s o u r c e  
replacement,  these  must  be  replaced  by 
parts of the same type, by the manufacturer 
or by a competent person.

5. 

In  case  of  inactive  use  for  a  period 

greater  than  2  months,  disconnect  the 
b a t t e r y   b y   p u l l i n g   o u t   t h e   b a t t e r y ’s  
connector.

 

6. 

I s not allowed to discard batteries in 

t i

to common trash bins, they must be 
discarded  only 

 

in  battery  recycling 

points. Do not incinerate.

NON MAINTAINED SPOT LIGHT EMERGENCY 

LUMINAIRES WITH 1 WHITE POWER LED

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL

EXTERNAL DIMENSION
WEIGHT

GUARANTEE

OPERATION VOLTAGE

MAXIMUM POWER CONSUMPTION
BATTERY (Ni-MH)

CHARGE TIME

INDICATIONS - CONTROLS

BATTERY PROTECTION

MINIMUM DURATION

DEGREES OF COVER PROTECTION

PRODUCED IN ACCORDANCE WITH

EMERGENCY ILLUMINATION

LIGHT SOURCE

220-240V AC / 50-60Hz

3 hours

1.5 hour

24 hours

Deep discharge and overcharge protection

IP40

3.6V/1.5Ah

  160lm 

  120lm 

  1 white

 

power LED

o

5 to 40  C

Up to 95% 

ABS/PC, PC

3 years

 (1 

year for the battery

)

380gr.

Ø125 x 65 mm

EN 60598-1, EN 60598-2-22

, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

Charge

TEST button

 GR-27

0

 GR-271

 GR-272

 GR-273

2.4W / 2.7VA

TECHNICAL CHARACTERISTICS

 

(for LED MODULE specifications see page 4)

Thank you

 for your 

trust in our 

product

s

  

Olympia Electronics - European manufacturer