manualshive.com logo in svg
background image

‘’

CLASSIC LIGHT‘’ SERIES FOR NON MAINTAINED 

/

 

ΜΑΙΝΤΑΙΝΕ

EMERGENCY LUMINAIRES

 

GR-109/12L/180

 GR-108/12L/90

220-240V AC/50-60Hz

3 hours

90 min

24 h

Battery charging LED

TEST button

From overcharge and deep discharge

IP20

3.6V/600mAh

3.6V/1Ah

  40lm / 100lm 

  38lm / 100lm 

  12 white LED’s 

3W / 3.5VA

2.5W / 3VA

EN 60598-1, EN 60598-2-22

, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

5 to 40  C

o

Up to 95% 

ABS/PC, PC

3 years 

(1 

year for the battery

)

262

 

x 100 x 69 mm

Page 1 of 3

GENERAL

o

These  luminaires  are  used  indoors 

(

ta  40 C

)

 

where emergency light is needed.
Each luminaire must be permanently connected 
to mains power supply

.

In normal operation the battery is charging and 
the 2 yellow LED’s light in the screen.
In  case  of  a  mains  power  supply  failure  the   
luminaire will light the led strip automatically in 
emergency  mode.  When  the  mains  power   
supply  is  restored  the  device  turns  to  normal 
operation.

MAINTAINED / NON-MAINTAINED 
OPERATION

There  is  an  option  to  select  the  maintained  or 
non-maintained operation by placing the jumper 
to  the  appropriate  place  according  to  step  4 
(page 2)

.

ΑΤΤΕΝΤΙΟΝ

!!!

1.  Operations  for  installation,  maintainance  or 
testing  must  be  done  by  authorized  personnel 
only

.

2. 

The device must be connected to the mains 

power supply through a fuse dependent by the 
total amount of the line’s  power load

.

3. 

It  is  suggested  to  check  every  month  the 

indication  LED  for  battery  charging,  and  by 

pushing the TEST button to check the emergency 
circuit. The  led  strip  should:  a)  light  with  bigger 
intensity as long as the TEST button is pressed 
(maintained operation),
b)  light  as  long  as  the  TEST  button  is  pressed 
(non-maintained  operation).

4. 

It  is  suggested  to  check  every  6  months  the 

minimum autononous duration by disconnecting 
the mains power supply

Count the time that  the 

led strip lights and in case of less time than the 
minimum autonomous duration the battery must 
be replaced. If the measured time is considerably 
less  than  the  minimum  autonomous  duration 

 In case of battery or led strip 

replacement, these must be replaced by parts of 
the  same  type,  by  the  manufacturer  or  by  a 
competent person.

t  i

 

in  battery  recycling 

points.

 

Do not incinerate.

  If  the  luminaire 

doesn’t  work  as  described  above  contact  the 
installer.

 

contact the installer.

5. 

In case of inactive use for a period greater than 

2  months,  disconnect  the  battery  by  pulling  out 
the battery’s connector.

 

6. 

I

s  not  allowed  to  discard  batteries  into 

common  trash  bins,  they  must  be 
discarded  only 

5

35gr

545

gr

923109004_

0

9_010

Thank you for your trust in our products  

Olympia Electronics - European manufacturer

TECHNICAL CHARACTERISTICS

 

(for LED MODULE Specifications see page 

2

)

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY

EXTERNAL DIMENSIONS 

CONSTRUCTION MATERIALS 

TYPICAL WEIGHT

GUARANTEE 

OPERATION VOLTAGE

MAXIMUM POWER CONSUMPTION
BATTERIES

 (

Ni-Cd

)

CHARGING TIME

INDICATIONS 

CONTROLS

BATTERY PROTECTION

MINIMUM AUTONOMOUS DURATION

DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH

EMERGENCY ILLUMINATION

ILLUMINATION SOURCE

Отзывы: