Detector

The detector sends to the main panel an analogue value which depends on the 

o

heat.  The  value  is  100  at  57 C  (A1R  or  A1S)  or  89°C  (CS)  and  increases 

o

proportionally  to  120  at  90 C  (A1R  or  A1S),  or  120°C  (CS).  When  a  sudden 
increase in temperature is detected the detector sends the value of 121.

The 

BS

R

-

61

5

7/MAR

 

is  an  analogue  addressable  smoke  detector  which 

integrates functions of optical smoke and heat detection and

 

it can work with 

any fire panel supports Olympia A Protocol. It can be adjusted to detect multiple 
levels  of  smoke  and  heat  offering  flexibility  and  rich  functionality.  Also,  it 
integrates a short circuit isolation circuit which is automatically activated and 
disconnects  the  defective  node  from  the  remaining  loop,  allowing  it  to  be 
located by the panel.

The 

BS

R

-

61

55

/MAR

  is  an  analogue  addressable  smoke  detector  which 

integrates the function of optical smoke detection and it can work with any fire 
panel supports Olympia A Protocol. It can be adjusted to detect multiple levels of 
smoke offering flexibility and rich functionality. Also, it integrates a short circuit 
isolation circuit which is automatically activated and disconnects the defective 
node from the remaining loop, allowing it to be located by the panel.
The detector sends to the main panel an analogue value which depends on the 
concentration of smoke. The value is 100 in concentration of 0.107dB/m (small 
amount  of  smoke)

 

and  increases  proportionally  to  120  in  concentration  of 

0.300dB/m.
By default the panel is set to sound an alarm when the concentration of smoke is 
0.107dB/m. The user can change this setting from the panel for each detector 
and define any level of smoke concentration between the lower and the upper 
limits, specifying the sensitivity of the system depending on the requirements of 
each site.

The detector sends to the main panel an analogue value which depends on the 
concentration  of  smoke  and  heat.  The  value  is  100  in  concentration  of 

o

0.107

dB/m (small amount of smoke) or a temperature of 57 C

 

and increases 

o

proportionally to 120 in concentration of 0.300dB/m or a temperature of 90 C. 
When a sudden increase in temperature is detected the detector sends the value 
of 121.
By default the panel is set to sound an alarm when the concentration of smoke is 
0.

107

dB/m or the temperature is 57 C. The user can change this setting from the 

o

panel  for  each  detector  and  define  any  level  of  smoke  concentration  or 
temperature between the lower and the upper limits, specifying the sensitivity 
of the system depending on the requirements of each site. Also, the user can 
select A1R

 

or A

1

S working mode through the panel.

The user have to read carefully the following instructions, in order to be properly 
informed and keep them for future use.

The 

BS

R

-

6160/MAR

 is an analogue addressable heat detector which integrates 

the function of rate-of-rise heat detection and it can work with any fire panel 
supports Olympia A Protocol. It can be adjusted to detect multiple levels of heat 
offering  flexibility  and  rich  functionality.  Also,  it  integrates  a  short  circuit 
isolation circuit which is automatically activated and disconnects the defective 
node from the remaining loop, allowing it to be located by the panel.

INSTALLATION

By default the panel is set to sound an alarm when the temperature reaches the 
lower level of each working mode, namely 57°C (A1R or A1S),  or 89°C (CS). The 
user can change this setting from the panel for each detector and define any level 
of temperature between the lower and the upper limits, specifying the sensitivity 
of the system depending on the requirements of each site. Also, the user can 
select A1R, A1S, or CS working mode through the panel.

They are composed by two parts. A plastic base which is placed on the ceiling and 
the main body of the detector which fits on the plastic base with a simple rotation 

o

to the right. The detectors have a 360  visible led and a remote led driver which 
are light up constantly in case of detection of fire, till cancelled from the panel. 
Also, they are staying lit even if the sirens are silenced from the panel, so the 
detector which detected the alarm is visible. They are turned off only when a 
reset command is given from the panel. The indicator led blinks every 10 sec 
indicating the connection status with the main panel.

The  detectors  should  be  placed  in  the  ceiling  in  visible  points  without  side 
obstacles, away from places that are barely ventilated or with strong air currents 

2

and water vapor. Each detector BSR-6155/MAR covers an area of 100m  and each 

2

detector BSR-6157/MAR & BSR-6160/MAR covers an area of 50m . For distances 
and mounting points consult the local/national regulation.   Also, they must be 
placed at least 50 cm away from fluorescent lamps. Cable cross-section should be 

2

from 

0

.

to 

2

.

5mm .

MAINTENANCE & FUNCTIONAL TESTING

CAUTION !!

After  installation  the  device  must  not  be  covered  with  dust  or  be  painted  or 
anything  else  happen  that  will  block  the  smoke  to  get  to  the  sensor.  Special 
attention must be given during the installation and the use of the device, since the 
user assumes full responsibility for proper operation afterwards.

Additional features of the device

 

:

Dust compensation and automatic generation of cleaning notifications. 

Stable level of detection regardless of detector’s working hours.

Compensation of smoke measurements based on ambient temperature 

which ensures high precision measurements even under extreme 
environmental conditions

-

 

Automatic fault diagnosis.

Adjustable smoke and temperature alarm level for maximum flexibility.

Integration of dynamic algorithms for noise and false alarm rejection.

360  

o

optically visible LED.

UID: 

I

n  every  device  there  is  a  double  sticker  with  the  UID  (Unique  Identifier) 

number. This number is unique for each device.

The  detector  has  fault  diagnosis  and  dust  compensation  functions,  which 
automatically informs you when replacement or cleaning actions are required. 
These  functions  combined  with  periodic  manual  testing  ensure  maximum 
security level. The manual testing procedure is carried out by spraying a small 
amount of smoke into the detector with a testing spray or a counterpart product. 
It is suggested to carry out a test every 6 months or after a change in the position 
of the sensor. A key element of its proper function is the air to be able to freely 
circulate inside it. So be careful not to block the openings of the outer cover. 
Before the manual testing it is suggested to enable the special “walk in test” mode 
from the panel.

Adjustable smoke alarm level for maximum flexibility.

Remove the detector from its base rotating to the left till the side marks are 
aligned.

Fasten the base with the supplied mounting accessories.

Package Contents

Mounting Accessories

General

Installation Instructions

1
1
1

Manual

1

Detector

 

Base

During site works place the plastic cover to the detector (only for BSR-6155/A & 
BSR-6157/A) as shown in the picture above to protect the device from dust.