OFFICINE OROBICHE   S.r.l.              

1

/

3

 

ISTRUCTION MANUAL 

Flow Switches PLJ & PLJ EN Series 

 

 

24010 Ponteranica (Bergamo) ITALY - Via Serena, 10 - Tel. +39 035 4530211 - Fax +39 035 570546 - www.officineorobiche.it-e-mail:[email protected]

 

****************************************************************************************************************************************************************** 

NOV. 2020 

Informazioni soggette a variazioni senza preavviso 

IST/198-I

 

1. DESCRIPTION 

 
Flow switches PLJ & PLJ EN are devices meant to control the flow of liquids. 
Flow switch PLJ is available with 1” NPT-M or 1” GAS-M connection. 
Flow switch PLJ EN is available with 1” GAS-M connection and it’s in compliance with the EN 12259-5:2003 
Standard entitled «Fixed firefighting systems Part 5 - Water flow detectors». 
 

2. TECHNICAL SPECIFICATIONS 
 

 

PLJ Series 

PLJ EN Series 

Metal parts material 

Stainless steel 

Stainless steel compliant to EN-12259-5 

Maximum working pressure  25 bar 

25 bar 

Room temperature limits 

-20 °C / 85 °C 

-20 °C / 85 °C 

Liquid temperature limits 

-30 °C / 120 °C 

-30 °C / 120 °C 

Protection rating 

IP65 

IP65 

Set of vanes material 

Stainless steel 

Stainless steel compliant to EN-12259-5 

Housing material 

ABS 

Painted aluminium 

Pressacavi 

M14 

M20 

Contact 

Micro-switch SPDT 15 (8A) 
24/250 VAC 

Micro-switch SPDT 15A 125/250 VAC - 5A 
24 VDC 

 

3. ELECTRICAL CONNECTIONS 

 

The COM-NC contact closes, at the calibration value, when the flow increases. 
The COM-NO contact opens, at the calibration value, when the flow decreases. 

 

4. INSTALLATION 

 
Flow switches PLJ & PLJ EN can be mounted in any position. 
The arrow must be oriented in the direction of the flow. 
In the event of installation with vertical pipes, the instrument needs recalibrating to 
compensate for the weight of the vanes. 
Fit the instrument along a straight run of the piping, in the absence of filters, valves, etc. 
and along at least five times its diameter, both upstream and downstream. 
 
It’s possible to adjust the calibration of the instrument tightening or unscrewing the screw 
shown in the picture. 

 