DESCRIPTION

The nVent RAYCHEM NGC-UIT-ORD is a panel mounted display 

used in conjunction with other approved RAYCHEM control 

and monitoring devices. The NGC-UIT-ORD is rated NEMA 12, 

and the display can best be viewed indoors. The NGC-UIT-ORD 

kit includes all hardware required for mounting in a suitable 

electrical panel. These instructions describe how to mount the 

NGC-UIT-ORD in an electrical panel and are intended only for 

personnel experienced in panel construction.

TOOLS REQUIRED

•  Masking tape 

•  #16 (3/16) drill bit

•  11/32 inch nut driver 

•  Metal file

•  Jig saw (recommend using carbon steel blade with 24 TPI)

APPROVALS/CERTIFICATIONS

General

Supply voltage

100 – 240 Vac ±10%, .25 A max/25 VA, 

50/60 Hz 

Operating 

temperature

–40°F to 149°F (–40°C to 65°C)

EMC

Immunity – Industrial 

Emission – Commercial / Light Industrial

Vibration

Unit tested to IEC-60068-2-6

Shock

Unit tested to IEC-60068-2-27

Dimensions

10 1/4 in wide X 6 5/8 in high X 3 in deep

 

(260 mm wide X 168 mm high X 76 mm deep)

Control Outputs

Relay outputs

Three relay outputs, Form C contacts, switching 

loads up to 277 Vac/3 Amps
Relays may be assigned for alarm outputs
11 position Phoenix-style pluggable screw 

terminal connector with retaining screws

Status LEDs

Relay

Three LEDs showing the ON/OFF Status for 

each relay, LED ON indicates relay is energized

Field

Transmit and Receive activity

Local/Remote

Transmit and Receive activity

NGC-UIT-ORD

User Interface Terminal for nVent RAYCHEM NGC Systems 

Installation Instructions

LR67275

Nonhazardous Locations

Summary of Contents for NGC-UIT-ORD

Page 1: ...General Supply voltage 100 240 Vac 10 25 A max 25 VA 50 60 Hz Operating temperature 40 F to 149 F 40 C to 65 C EMC Immunity Industrial Emission Commercial Light Industrial Vibration Unit tested to IE...

Page 2: ...le screw terminal connector with retaining screws Maximum number of devices 256 Fail safe design with optional termination resistors Data Rate 2400 to 57600 baud Maximum cable length for RS 485 not to...

Page 3: ...n the panel Note The following steps are most easily accomplished if the panel door is on a horizontal surface 5 Position the gasket on the outside of the panel door Place the sealing gasket between t...

Page 4: ...a push to test alarm light and or interposing relay and test button 11 10 9 8 7 6 5 4 3 Relay 1 2 1 120 Vac Relay 1 R D CONNECT POWER AND COMMUNICATION TO THE UIT Power and Earth Ground 1 Connect 100...

Page 5: ...Comments On Off TERM R FIELD Field Port Termination Select Terminates local RS 485 network 120 Ohm Termination Enabled Factory Default Termination Disabled For the local FIELD RS 485 network If this N...

Page 6: ...6 nVent com This Page Purposely Left Blank...

Page 7: ...make sure it has printed to scale or you will damage your panel door Printers and copiers may make reduc tions from the original size Please ensure the file has printed at 100 scale by using a ruler...

Page 8: ...12 1688 Fax 86 21 5426 3167 cn thermal info nvent com Latin America Tel 1 713 868 4800 Fax 1 713 868 2333 thermal info nvent com 2018 nVent All nVent marks and logos are owned or licensed by nVent Ser...

Reviews: