background image

NPSM481 Series Instruction Manual

NPSM481 Series V3.0

www.nextys.com

Page 1/5

NPSM481 Series – Single phase / DC input switching power supply with integrated PFC

Main Features:

High efficiency and extremely compact size

Only 56mm width aluminum enclosure

Active PFC

Overload 150%

Constant current or hiccup mode limitation, user settable

Wide range of output voltage

Easy parallelable for power increase

Includes models with internal ORing circuit

Up to 60°C operating temperature with no derating

All models available as version (PH)

Codes ended with (H): include enhanced transient overvoltage protection (> 6kV)

INDEX

Page

Installation Requirements

1

Declaration of Conformity

2

User Instructions

3

Connections

4

Dimensions

4

Distances

4

Mounting

4

Dismounting

5

Input Connections

5

Environment

5

Accessory Device

5

READ THIS CAREFULLY BEFORE INSTALLATION!

LEGGERE ATTENTAMENTE PRIMA

DELL’INSTALLAZIONE!

A LIRE ATTENTIVEMENT AVANT L’INSTALLATION!

Before operating, read this document thoroughly and retain

it for future reference.

Non-respect of these instructions may reduce

performances and safety of the devices and cause danger

for people and property.

The products must be installed, operated, serviced and

maintained by qualified personnel in compliance with

applicable standards and regulations.

Don’t open the device, it does not contain replaceable

components, the tripping of the internal fuse (if included) is

caused by an internal failure.

Don’t repair or modify the device, if malfunction or failure

should occur during operation, send unit to the factory for

inspection. No responsibility is assumed by Nextys SA for

any consequences deriving from the use of this material.

Prima dell’installazione, leggere attentamente questo

documento istruzioni e conservarle per future consultazioni.

L’inosservanza delle presenti istruzioni può compromettere le

caratteristiche e la sicurezza dell’apparecchio e causare

pericolo per le persone e le cose.

Il prodotto deve essere installato, utilizzato e riparato da

personale qualificato e nel rispetto delle normative vigenti.

Non aprire il prodotto, esso non contiene componenti sostituibili,

il guasto del fusibile interno (se previsto) è causato da un

guasto interno. Non tentare di riparare o modificare il prodotto,

se durante il funzionamento si verificano guasti o anomalie,

inviarlo al produttore per il controllo.

Nextys SA non si assume nessuna responsabilità per

qualunque conseguenza derivante dall’uso di questo materiale.

Lisez ces instructions avant l'installation, conservez ce

manuel pour référence future.

Défaut de se conformer à ces instructions peut affecter les

caractéristiques et la sécurité du dispositif de danger et de

causer aux personnes ou aux biens.

Les produits doivent être installés, exploité et entretenus par

personnel qualifié et en conformité avec les règlements.

N'ouvrez pas le produit, il ne contient aucune pièce réparable,

le déclenchement du fusible interne (le cas échéant) est

causé par un défaut interne. Ne pas essayer de réparer ou

modifier le produit ; si des défaillances se produisent pendant

le fonctionnement ou les dysfonctionnements, le retourner au

fabricant pour inspection. Nextys SA n'assume aucune

responsabilité des conséquences éventuelles découlant de

l'utilisation des produits.

CAUTION

ATTENZIONE

AVVERTISSEMENT

RISK OF BURNS, EXPLOSION, FIRE, ELECTRICAL

SHOCK, PERSONAL INJURY.

Never carry out work on live parts! Danger of fatal injury!

The product’s enclosure may be hot, allow time for cooling

product before touching it. Do not allow liquids or foreign

objects to enter into the products.

To avoid sparks, do not connect or disconnect the device

before having previously turned-off input power and wait for

internal capacitors discharge (minimum 1 minute).

RISCHIO USTIONI, ESPLOSIONE, INCENDIO, SCOSSA,

LESIONI GRAVI.

Non effettuare mai operazioni sulle parti sotto tensione! Pericolo

di lesioni letali! Il contenitore può scottare, lasciar quindi

raffreddare il dispositivo prima di toccarlo. Non far entrare liquidi

o oggetti estranei nel dispositivo.

Per evitare scintille, non collegare o scollegare

l'apparecchiatura prima di avere tolto tensione di ingresso e

prima che sia avvenuta la scarica dei condensatori interni (min.

1 minuto).

RISQUE DE BRULURES, EXPLOSION, INCENDIE,

ELECTROCUTION, DOMMAGE AUX PERSONNES.

Ne jamais effectuer des opérations sur les parties sous

tension! Danger de mort! Le récipient peut produire des

brulures, le laisser refroidir avant de toucher l'appareil. Ne

faites pas pénétrer des liquides ou des corps étrangers dans

l'appareil. Pour éviter des étincelles, ne pas connecter ou

déconnecter l'équipement jusqu'à ce que vous avez supprimé

la tension d'entrée et avant qu'elle n'ait lieu de décharge des

condensateurs internes (minimum 1 minute).

Summary of Contents for NPSM481 Series

Page 1: ...onamento si verificano guasti o anomalie inviarlo al produttore per il controllo Nextys SA non si assume nessuna responsabilità per qualunque conseguenza derivante dall uso di questo materiale Lisez ces instructions avant l installation conservez ce manuel pour référence future Défaut de se conformer à ces instructions peut affecter les caractéristiques et la sécurité du dispositif de danger et de...

Page 2: ...ng power supply IN 120 240Vac 110 345Vdc OUT 36Vdc 14A Increased surge protection NPSM481 36P Single phase with integrated PFC switching power supply IN 120 240Vac 110 345Vdc OUT 36Vdc 14A ORing circuit NPSM481 36PH Single phase with integrated PFC switching power supply IN 120 240Vac 110 345Vdc OUT 36Vdc 14A ORing circuit Increased surge protection NPSM481 48 Single phase with integrated PFC swit...

Page 3: ...eter to a wide range see Fig 1 Check Uout before connecting the power supply to the load With output voltage set to the max value the continuous current x voltage must not exceed the nominal power 8 Parallel connection and redundancy power supplies can be connected in parallel to increase power For paralleling for power set the Ilim jumper to C C algorithm Uout must be set uniformly 100mV on each ...

Page 4: ...gative DC I earth ground Output Positive DC Negative DC Dry contact NC Dimension W D H mm inch 56 2 20 117 4 60 140 5 51 Distance A B mm inch 20 0 8 100 3 9 Fig 4 Mounting Dismounting Instructions For DIN rail fastening according to IEC 60715 TH35 7 5 15 Mounting as shown in figure with input terminals on lower side with suitable cooling and maintaining a proper distance between adjacent devices a...

Page 5: ...7 Input connections AC Line DC Line Fig 8 Environment Operating temperature Derating 40 C 70 C 5 95 r H non condensing UL Certified up to 50 C at 120Vac UL Certified up to 60 C at 240Vac Overtemperature protection 7 6W C over 50 C at 120Vac 7 2W C over 60 C at 240Vac Note Data may change without prior notice in order to improve the product Please refer to the latest version of the Instruction Manu...