PowerView

 - Model PV101 V2.2 – Fuel Sender Calibration 

Setting Fuel Level Analog Input 

Introduction 

This option enables the operator to configure the PV101 to accept the optional Murphy Fuel Sender (Model ES2F 
recommended) for fuel level information or to program the unit to accept the non-Murphy fuel sender*. 

The PV101 is set from the factory to accept a backlight dimmer input. These instructions show exactly what needs 
to be completed to set the PV101 analog input to read Model ES2F Murphy Fuel Sender and how to program the 
unit for use with a non-Murphy fuel sender*. 

*A linear curve is used to calibrate a non-Murphy fuel sender. 

 

Navigation Buttons 

 

MENU

 

Pressing 

[MENU]

 will take you the menu or it will exit the option, return the display to 

the UTILITIES MENU and discard any changes. 

 

LEFT ARROW 

Pressing 

[LEFT ARROW] 

will decrement the number. 

 

RIGHT ARROW 

Pressing 

[RIGHT ARROW] 

will increment the number. 

 

ENTER 

Pressing 

[Enter]

 will select the option displayed much like the ENTER key on a keyboard. 

Location 

To begin the process, locate the ANALOG INPUT option is located in the Utilities menu. 

 

 

Summary of Contents for PowerView PV-101

Page 1: ...leted to set the PV101 analog input to read Model ES2F Murphy Fuel Sender and how to program the unit for use with a non Murphy fuel sender A linear curve is used to calibrate a non Murphy fuel sender Navigation Buttons MENU Pressing MENU will take you the menu or it will exit the option return the display to the UTILITIES MENU and discard any changes LEFT ARROW Pressing LEFT ARROW will decrement ...

Page 2: ...Select ANALOG INPUT Select Fuel Level The next screen displayed is the BACKLIGHT DIMMER FUEL LEVEL selection screen Select FUEL LEVEL 2 ...

Page 3: ...left arrow keys to navigate the menu There are two pages to this screen NOTE When Fuel Setpoints OFF is set these screens are displayed but they are not available for modification For a non Murphy fuel sender see the USING A NON MURPHY FUEL SENDER in this document NOTE The asterisk indicates that the setpoint has been set Continue to press the right arrow key to scroll the menu and to see page two...

Page 4: ...Murphy Standard Fuel Sender settings are preloaded in the device To view these settings select SHOW FUEL SETPOINTS The following screen is displayed NOTE The numbers displayed on the above screen are Murphy Standard settings 4 ...

Page 5: ...se or decrease the set point Select MENU to cancel or ENTER to confirm the setpoint NOTE To change the setpoint from backlight dimmer input to fuel level input the ENTER OK selection must be made Using a Non Murphy Fuel Sender The next screen displayed is the FUEL SENDER SETUP screen The FUEL SETPOINTS ON must be shown to work with a non Murphy fuel sender With the FUEL SETPOINTS ON displayed the ...

Page 6: ...Standard settings NOTE The SET EMPTY POINT SET 1 4 POINT SET 1 2 POINT SET 3 4 POINT and SET FULL POINT must be programmed before continuing Set Empty Point First select SET EMPTY POINT with fuel tank empty NOTE The fuel tank must be empty to begin this process NOTE Once the setpoints have been cleared the asterisks are removed 6 ...

Page 7: ...e PV101 will have a new low fuel setpoint setting Once the new settings are set the menu will be displayed NOTE Once the setpoint has been set an asterisk is displayed to the right of the setpoint Set 1 4 Point 1 2 Point and 3 4 Point Add fuel to 25 of the tank s capacity and select the quarter tank set the 1 4 point setpoint The following screen is displayed Select YES while sending the resistive...

Page 8: ... and select SET FULL POINT The following screen is displayed and now the resistive value that represents the Full point from the non Murphy fuel sender must be sent to the PV101 While sending the resistive value select YES and the PV101 will have a new Full fuel setpoint setting Now that the Non Murphy fuel sender calibration process is completed the FUEL SENDER SETUP SCREEN will be displayed Sele...

Page 9: ...ng Low Fuel Level Setting To change the Low Fuel Level setpoint use the left and right arrows to increase or decrease the setpoint Select the menu button to cancel or the enter button to confirm To change the setpoint from backlight dimmer input to fuel level input the enter OK must be selected Show Fuel Setpoints To Sender settings are preloaded in the device To view these settings select SHOW FU...

Page 10: ...rs displayed on the above screen are examples only The numbers displayed on the newly set PV101 will be different NOTE Once these setpoints are complete you can add them to your configuration via the Configuration tool and they can become default values ...

Page 11: ......

Reviews: