manualshive.com logo in svg
background image

EXTERNAL MODEM KIT

Instruction Manual

October 2002

EXTERNAL

MODEM

KIT

Siemens Hardware

Содержание VT-Modem-1 WW

Страница 1: ...EXTERNAL MODEM KIT Instruction Manual October 2002 XTERNAL MODEM KIT ...

Страница 2: ...n electronic version We encourage users to purchase authorized bound manuals or to view electronic versions as designed and authored by Siemens Milltronics Process Instruments Inc Siemens Milltronics Process Instruments Inc will not be responsible for the contents of partial or whole reproductions of either bound or electronic versions While we have verified the contents of this manual for agreeme...

Страница 3: ... Instrument 9 RS 232 Modem Kit Instruments 9 EnviroRanger ERS 500 9 Accumass BW500 SF500 10 AiRanger with SmartLinx Modbus RTU card 11 Open Channel Meter OCM III 12 RS 232 Modem to PC Connection 12 RS 485 Modem Kit Instruments 13 Modem Dip Switch Settings 13 MultiRanger 100 200 HydroRanger 200 13 IQ Radar 300 14 AiRanger with SmartLinx Modbus RTU Card for multidrop applications 14 EnviroRanger ERS...

Страница 4: ...Page ii External Modem Kit INSTRUCTION MANUAL 7ML19981DP02 ...

Страница 5: ... rail or flat panel mountable refer to SIXNET modem manual and CD Power Supply Siemens 120 V AC 230V AC input 24V 1 3A output DIN rail or flat panel mountable refer to Siemens power supply manual Compatible Instruments MultiRanger 100 MultiRanger 200 HydroRanger 200 IQ Radar 300 AiRanger with Smartlinx Modbus RTU card for multi drop applications EnviroRanger ERS 500 with option card for multi drop...

Страница 6: ...ide and RS 232 and RS 485 Modem kit for device side When connecting to the OCM III Siemens Milltronics recommends using Flow Reporter software When working with Modbus RTU we recommend the Modbus Serial driver by Kepware www kepware com Components RS 232 Modem Kit RS 485 Modem Kit SIXNET VT Modem 1 WW Modem SIXNET VT Modem 3 WW Modem modem programming cable DB 9 modem programming cable DB 9 Siemen...

Страница 7: ...AL Page 3 Dimensions RS 232 Modem RS 485 Modem 120 7mm 2 92 80 5mm 3 11 74 2mm 2 92 RJ 11 jack DB 9 connector power terminal block RJ 11 jack RS 485 terminal block DB 9 connector dip switches power terminal block 74 2mm 2 92 120 7mm 4 75 80 5mm 3 11 ...

Страница 8: ...Page 4 External Modem Kit INSTRUCTION MANUAL 7ML19981DP02 Power Supply 57 2mm 2 25 88 9mm 3 50 69 8mm 2 75 ...

Страница 9: ...rogramming cable when finished 5 Connect the Siemens Milltronics product to the external modem using the appropriate wiring code see Configuring Instruments on page 9 6 Program the Siemens Milltronics product using the correct parameters listed in Configuring Instruments section Connect external modem to analog phone line using RJ 11 telephone cable in the modem s line jack 7 Configure the interna...

Страница 10: ...2 6ms EnviroRanger ERS 500 Accumass BW500 Accumass SF500 AiRanger with Smartlinx Modbus RTU Card SMPI_OCM 6ms OCM III SMPI_modbus485 6ms MultiRanger 100 200 HydroRanger 200 IQ Radar 300 AiRanger with Smartlinx Modbus RTU Card multi drop applications SMPI_ocm_master 6ms PC connecting to OCM III via FlowReporter SMPI_modbus_master 6ms PC connecting to Siemens Milltronics Modbus devices Notes If the ...

Страница 11: ...7ML19981DP02 External Modem Kit INSTRUCTION MANUAL Page 7 4 Choose the COM port for your computer 5 Click Next 6 Click Next 4 5 6 ...

Страница 12: ...hes RS 485 modem only write configuration file to the modem 9 Click Finish The external modem is now configured for 9600 baud communication For communication from the PC use either the RS 232 Modem Kit see page 12 for PC connection or use an internal PC modem The internal modem Modbus Master must be set up for Modbus RTU 8 data bits 1 stop bit no parity no flow control See Configuring Internal Mod...

Страница 13: ...0 Rack and Panel Mount 1 Use an ohmmeter to rung out the communication cable Determine which pin connects with each wire of the cable 2 Connect the communication cable to the ERS 500 as follows Parameter Description P770 2 3 Modbus RTU slave P771 2 1 Modbus slave address of 1 P772 2 9 6 9600 baud P773 2 0 no parity P774 2 8 8 data bits P775 2 1 1 stop bit P776 2 0 no flow control P777 2 0 no key u...

Страница 14: ...er Description P770 1 3 Modbus RTU slave P771 1 1 Modbus slave address of 1 P772 1 2 9600 baud P773 1 0 no parity P774 1 8 8 data bits P775 1 1 1 stop bit P778 1 1 modem attached P779 1 300 Modem inactivity timeout 300 Note After setting Port 1 parameters for the BW500 and SF500 you must cycle power to the unit for them to take effect 19 RXD RXD DB 9 CONNECTOR ERS 500 TERMINAL BLOCK GND GND 20 TXD...

Страница 15: ...ters Wiring Diagram for Connection to AiRanger with SmartLinx Modbus RTU card 1 Use an ohmmeter to rung out the communication cable Determine which pin connects with each wire of the cable 2 Connect the communication cable to the AiRanger as follows Parameter Description P751 3 9600 baud P752 0 no parity P753 1 station address 1 P758 15 interframe spacing 15 ms 31 TX TX DB 9 CONNECTOR BW 500 TERMI...

Страница 16: ...Modem and PC 1 Connect the modem to PC serial port 1 or 2 2 On the Start Menu click SETTINGS and click CONTROL PANEL 3 Double click MODEMS 4 Click Add Modem 5 Check Don t detect my modem I will select it form a list and click NEXT 6 Select Manufacturers Standard Modem and then select Modem Standard 9600 bps Modem 7 Select all the defaults until modem is installed Parameter Description P37 5 9600 b...

Страница 17: ...primary index secondary index 0 Wiring Diagram for Connection to MultiRanger 100 200 HydroRanger 200 1 Connect the communication cable to the MultiRanger 100 200 or HydroRanger 200 as follows Parameter Description P770 2 3 Modbus RTU slave P771 2 1 Modbus slave address of 1 P772 2 9 6 9600 baud P773 2 0 no parity P774 2 8 8 data bits P775 2 1 1 stop bit P778 2 1 modem attached P779 2 300 Modem ina...

Страница 18: ...drop applications SmartLinx Modbus RTU Card port configuration for RS 485 transmission AiRanger Port 1 set up parameters Parameter Description P770 3 Modbus RTU slave P771 1 Modbus slave address of 1 P772 9 6 9600 baud P773 0 no parity P774 8 8 data bits Parameter Description P751 3 9600 baud P752 0 no parity P753 1 station address 1 P758 15 interframe spacing 15 ms 3 6 COM TD RS 485 Modem Termina...

Страница 19: ...rs to the primary index secondary index 0 Parameter Description P770 3 3 Modbus RTU slave P771 3 1 Modbus slave address of 1 P772 3 9 6 9600 baud P773 3 0 no parity P774 3 8 8 data bits P775 3 1 1 stop bit P776 3 0 no flow control P777 3 0 no key up delay P778 3 1 modem attached P779 3 300 modem inactivity timeout 300 3 B GND RS 485 MODEM TERMINAL BLOCK AIRANGER WITH SMARTLINX MODBUS RTU CARD MULT...

Страница 20: ...EnviroRanger ERS 500 Wall Mount as follows Connect the communication cable to the EnviroRanger ERS 500 Rack and Panel Mount as follows 101 COM GND RS 485 Modem Terminal Strip Enviroranger ERS 500 Wall Mount Terminal Block B TD 102 A TD 103 6 5 4 49 COM GND RS 485 Modem Terminal Strip Enviroranger ERS 500 Rack Mount Terminal Block B TD 50 A TD 51 6 5 4 ...

Страница 21: ...ble click MODEMS 3 Highlight the internal modem being used and then click PROPERTIES 4 Select the GENERAL tab Set speed to 9600 using Maximum Speed dropdown menu 5 Select the CONNECTION tab Under Connection Preferences set data bits to 8 parity to NONE stop bits to 1 6 Click ADVANCED at bottom right of Connection screen 7 Verify the Use error control and Use flow control boxes are not checked 8 Ve...

Страница 22: ...the internal modem being used and then click PROPERTIES 4 Select the GENERAL tab Set speed to 9600 using Maximum Speed dropdown menu 5 Select the CONNECTION tab Under Connection Preferences set data bits to 8 parity to NONE stop bits to 1 6 Click ADVANCED at bottom right of Connection screen 7 Verify the Use error control box is not checked 8 Verify that the Use flow control box is checked and tha...

Страница 23: ......

Страница 24: ... 7ml19981dp02 2 Rev 2 1 ...

Отзывы: