background image

Descriptive Technical
Documentation

- Model-dependent -

DTD no. 12-9800

Model(s): T 9800, T 9820

05.12.2006, US_am

This information should not be duplicated or passed on without Miele approval. All rights reserved.

Summary of Contents for T 9800

Page 1: ...escriptive Technical Documentation Model dependent DTD no 12 9800 Model s T 9800 T 9820 05 12 2006 US_am This information should not be duplicated or passed on without Miele approval All rights reserved ...

Page 2: ...This information should not be duplicated or passed on without Miele approval All rights reserved 05 12 2006 US_am ...

Page 3: ...4 4 4 Door lock A2 Remove 020 4 030 Drum rear bearing sensor heater bank 1 Technical Data 030 2 2 Function 030 4 2 1 No load detection 030 4 2 2 Residual moisture measurement 030 4 2 3 Heater control 030 5 2 4 Temperature limiter with manual reset 1F1 2F1 3F1 030 5 2 5 NTC temperature sensor drying air 1R30 030 5 2 6 NTC temperature sensor heating drying 2R30 030 5 2 7 Drum light H3 6 Interior dru...

Page 4: ...ption 090 3 2 2 Programming function 090 3 2 2 1 Reset 090 3 2 2 2 Programming function drying outcome residual moisture Cottons Hot 090 3 2 2 3 Programming function drying outcome residual moisture Permanent press 090 3 2 2 4 Memory 090 3 2 2 5 Programming function Additional cooldown phase 090 3 2 2 6 Programming function Prompt to clean air ducts 090 3 2 2 7 Acoustical acknowledgment 090 4 2 2 ...

Page 5: ... heater is on for 3 seconds 090 14 3 13 F 55 Overriding time limit exceeded approx 180 min 090 14 3 14 F 66 Air leakage 090 16 4 Service 090 17 4 1 Programming mode summary 090 17 4 2 Demonstration mode Activate Deactivate 090 19 4 3 Service mode summary 090 20 4 4 Program selection module EW Service view 090 22 4 5 Program selection module EW and fascia support panel Remove 090 22 100 Electrical ...

Page 6: ...Descriptive Technical Documentation 4 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 12 2006 US_am ...

Page 7: ...ponents x Danger Danger of high voltages when working on small components In a 1 board control as in this Control Program Power module EPWL 3xx there is no structural galvanic potential disconnection to the power supply Therefore be careful when working on small components these may be carrying voltage if the dryer is not disconnected completely from its power supply As a matter of standard practi...

Page 8: ... to make sure they are sealed If there is a gas odor odorized gas shut the gas tap Avoid sparks or any fire source air the rooms x Warning Before starting any service or repair work it is essential to disconnect the dryer from its gas supply Descriptive Technical Documentation A 2 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 12...

Page 9: ...e unit under test has been checked and found to be satisfactory Dangerous voltages may exist on defective appliances as well as on accessible conductive parts that are not connected to ground Note Do a touch current measurement on the following accessible conductive parts none Descriptive Technical Documentation DTD no 12 9800 A 3 05 12 2006 US_am This information should not be duplicated or passe...

Page 10: ...Descriptive Technical Documentation A 4 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 12 2006 US_am ...

Page 11: ...X Olaf Meyer zu Drewer Revised Version 1 Start of production beginning of 2007 Descriptive Technical Documentation DTD no 12 9800 B 1 05 12 2006 US_am This information should not be duplicated or passed on without Miele approval All rights reserved ...

Page 12: ...Descriptive Technical Documentation B 2 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 12 2006 US_am ...

Page 13: ...tric 5 8 kW USA CDN 0 3 kW 4 9 kW MEX Natural gas Output 40 1 MJ m3 Natural gas Pressure Net Supply pressure 17 4 mbar Exhaust pipe vented dryers only Connecting pipe nominal diameter DN 100 Washer Dryer stack Under counter Washer Dryer stand Optional Liquid propane conversion optional PC interface x WLAN interface IEEE802 11 miele home WLAN ready accessory Table 1 Technical Data General Descripti...

Page 14: ...Descriptive Technical Documentation C 2 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 12 2006 US_am ...

Page 15: ...s Optical PC interface x Layout 1 1 PC LED Optical PC interface Descriptive Technical Documentation DTD no 12 9800 D 1 05 12 2006 US_am This information should not be duplicated or passed on without Miele approval All rights reserved ...

Page 16: ...ure sensor Drum rib 13 WLAN Wireless Local Aera Network optional 14 C5 Capacitor Motor M5 15 M5 Motor Drying air and drum drive 16 1R30 NTC Temperature sensor Drying air 17 3F1 Temperature limiter with manual reset 18 2F1 Temperature limiter with manual reset 19 2R30 Temperatur sensor Heating Drying 20 1F1 Temperature limiter with manual reset Descriptive Technical Documentation D 2 DTD no 12 9800...

Page 17: ...citor Motor M5 13 M5 Motor Drying air and drum drive 14 1R30 NTC temperature sensor Drying air 15 Y57 1 Gas solenoid valve 16 Y57 2 Gas solenoid valve 17 E1 1 Ignitor electrode 18 2F1 Temperature limiter flame flashback with manual reset 19 B1 16 Flame sensor radiant output sensor 20 1F1 Temperature limiter with manual reset 21 2R30 Temperature sensor Heating Descriptive Technical Documentation DT...

Page 18: ...Descriptive Technical Documentation D 4 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 12 2006 US_am ...

Page 19: ...010 Housing Front panel x Descriptive Technical Documentation DTD no 12 9800 010 1 05 12 2006 US_am This information should not be duplicated or passed on without Miele approval All rights reserved ...

Page 20: ...on side walls embossed for reinforcement Table 1 Technical data Housing Front panel Descriptive Technical Documentation 010 2 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 12 2006 US_am ...

Page 21: ...e raised head screws completely A Press in on the raised head screws A Lift the lid at the front and slide it toward the rear thereby releasing it from its retainers Take the lid off Descriptive Technical Documentation DTD no 12 9800 010 3 05 12 2006 US_am This information should not be duplicated or passed on without Miele approval All rights reserved ...

Page 22: ...nel Remove 090 4 5 A Take the door off refer to Door Remove 020 4 1 x Note Remove the door so it doesn t get damaged as the front panel is being removed Fig 2 A Release the front panel attachment Descriptive Technical Documentation 010 4 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 12 2006 US_am ...

Page 23: ...nt panel refer to Front panel Remove 010 4 2 x Fig 3 A Remove the side panel retaining screws A Take the side panel off Descriptive Technical Documentation DTD no 12 9800 010 5 05 12 2006 US_am This information should not be duplicated or passed on without Miele approval All rights reserved ...

Page 24: ...Descriptive Technical Documentation 010 6 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 12 2006 US_am ...

Page 25: ...e reversed Lock Manual pull open lock Door lock contact switch A2 Drum door open contact open Table 1 Technical data Door Lock Descriptive Technical Documentation DTD no 12 9800 020 1 05 12 2006 US_am This information should not be duplicated or passed on without Miele approval All rights reserved ...

Page 26: ...stered by a microswitch in the door lock Microswitch in door lock A2 Drum door open Contact open Descriptive Technical Documentation 020 2 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 12 2006 US_am ...

Page 27: ...the front panel off refer to Front panel Remove 010 4 2 A Detach the hinge attachment from the front panel take the washer and the hinge off Descriptive Technical Documentation DTD no 12 9800 020 3 05 12 2006 US_am This information should not be duplicated or passed on without Miele approval All rights reserved ...

Page 28: ... that the welded seam of the seal is at the hinge 4 4 Door lock A2 Remove x Fig 3 Descriptive Technical Documentation 020 4 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 12 2006 US_am ...

Page 29: ...Remove 010 4 2 A Take the door lock A2 off and pull the connecting plug off Descriptive Technical Documentation DTD no 12 9800 020 5 05 12 2006 US_am This information should not be duplicated or passed on without Miele approval All rights reserved ...

Page 30: ...Descriptive Technical Documentation 020 6 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 12 2006 US_am ...

Page 31: ...um rear bearing sensor heater bank x Descriptive Technical Documentation DTD no 12 9800 030 1 05 12 2006 US_am This information should not be duplicated or passed on without Miele approval All rights reserved ...

Page 32: ... F1 with manual reset 16 A Table 2 Technical data Heater bank electrical Temperature F C Resistance kΩ 32 0 340 41 5 261 50 10 203 59 15 159 68 20 126 77 25 100 86 30 80 2 95 35 64 8 104 40 52 7 113 45 43 1 122 50 35 5 131 55 29 4 140 60 24 5 149 65 20 5 158 70 17 3 167 75 14 6 176 80 12 5 185 85 10 6 194 90 9 13 199 93 8 34 203 95 7 86 212 100 6 80 230 110 5 14 248 120 3 95 266 130 3 07 284 140 2...

Page 33: ... 45 5 42 122 50 4 52 131 55 3 78 140 60 3 19 149 65 2 70 158 70 2 29 167 75 1 96 176 80 1 68 185 85 1 45 194 90 1 25 199 93 1 15 203 95 1 09 212 100 1 06 230 110 0 73 248 120 0 569 266 130 0 449 284 140 0 358 302 150 0 289 Table 4 NTC temperature sensor 1R30 drying air Resistance values Descriptive Technical Documentation DTD no 12 9800 030 3 05 12 2006 US_am This information should not be duplica...

Page 34: ... Resistance measurement The residual moisture is calculated based on the electrical resistance of the damp laundry The electrical resistance of the damp laundry is measured by a sensor between a drum rib and the drum casing x Note In 1 rib sensing only one rib is used for measuring The value of the electrical resistance depends on the type of laundry the degree of moisture the laundry load weight ...

Page 35: ...C detects temperatures lower than 5 F 15 C or higher than 320 F 160 C the NTC must be considered defective 2 6 NTC temperature sensor heating drying 2R30 An open circuit in the NTC temperature sensor heating drying 2R30 can only be detected at temperatures higher than 57 F 14 C Since lower temperatures can exist during operating sensor readings will only be evaluated after the heater has been runn...

Page 36: ...he door is opened Switch off delay 5 minutes When the door is closed the light is always switched off Descriptive Technical Documentation 030 6 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 12 2006 US_am ...

Page 37: ... the air vents exhaust vents Cause Drum is sluggish Remedy A Check the front bearing seals front and back needle felting for correct position A Check the bearing of the front support roller and adjust it Cause Intermediate V belt power transmission is faulty Remedy A Check the intermediate V belt for dirt deposits wear and tear and tension Descriptive Technical Documentation DTD no 12 9800 030 7 0...

Page 38: ...elt for dirt deposits wear and tear and tension tension spring of intermediate drive Descriptive Technical Documentation 030 8 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 12 2006 US_am ...

Page 39: ...de panel refer to Side panel Remove 010 4 3 x Fig 1 A Remove the service panel door at the dryer back A Take the wire out of the heater bank wiring harness rear of appliance housing A Disconnect the plugs Descriptive Technical Documentation DTD no 12 9800 030 9 05 12 2006 US_am This information should not be duplicated or passed on without Miele approval All rights reserved ...

Page 40: ...e V belt off the intermediate drive A In electrically run dryers Detach the heater bank attachment and take the heater bank off refer to Heater bank Replace 030 4 1 x Fig 2 Bearing housing attachment A Unscrew the bearing housing attachment Descriptive Technical Documentation 030 10 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 ...

Page 41: ...off A Unlock the drum bearing at the back and take it off Descriptive Technical Documentation DTD no 12 9800 030 11 05 12 2006 US_am This information should not be duplicated or passed on without Miele approval All rights reserved ...

Page 42: ...Descriptive Technical Documentation 030 12 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 12 2006 US_am ...

Page 43: ...031 Heating Gas T 9820 x Descriptive Technical Documentation DTD no 12 9800 031 1 05 12 2006 US_am This information should not be duplicated or passed on without Miele approval All rights reserved ...

Page 44: ... Temperature sensor heating drying 2R30 Temperature limiter Two 3 4 bi metal temperature limiters 1F1 2F1 with manual reset 16 A 120 C 100 C 5 K Safety time refer to 031 2 1 3 Safety time 90 seconds Table 1 Technical data Heating Gas Descriptive Technical Documentation 031 2 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 12 2006 ...

Page 45: ...n only opens when the maintaining coil Y57 1 and the booster coil Y57 1 carry voltage Once gas solenoid valve Y57 1 is open it remains in this state as long as the maintaining coil Y57 1 carries voltage 2 1 2 Gas ignition x Fig 1 1 Temperature sensor heating 1R30 2R30 in heating duct 2 Gas solenoid valve Y57 3 Gas solenoid valve Y57 2 4 Gas solenoid valve Y57 1 5 Maintaining coil gas solenoid valv...

Page 46: ... electrode E1 1 receives voltage and slowly starts to glow Since not both gas solenoid valves Y57 2 and Y57 1 switched in sequence are open gas does not yet flow x Fig 3 Once the heat radiance on flame sensor B1 16 is strong enough the thermostat opens Now the ignitor electrode E1 1 no longer carries voltage However now the gas solenoid valve Y57 2 receives voltage via the low ohmic ignitor electr...

Page 47: ...e until gas solenoid valve Y57 2 closes and stops the gas flow Safety time refer to 031 2 1 3 Safety time If the burner overheats the thermostat temperature limiter 1F1 2F1 interrupts the voltage circuit of gas solenoid valve Y57 gas solenoid valve Y57 1 und Y57 2 shuts off 2 1 3 Safety time The safety time is the time span between the point when the flame goes out and the gas supply shuts off Des...

Page 48: ...rs 1F1 2F1 with manual reset at the burner The bi metal temperature limiter 1F1 at the burner exit serves to detect any overheating of the burner due to insufficient air or air leakage The bi metal temperature limiter 2F1 at the burner entrance serves to detect any flame flashback Descriptive Technical Documentation 031 6 DTD no 12 9800 This information should not be duplicated or passed on withou...

Page 49: ...h the burner running This pressure can only be measured with functional burner while operating A Check the temperature limiter 1F1 2F1 for continuity x Warning If the front temperature limiter 2F1 has tripped it has to be assumed that the burner and the connecting cables have sustained thermal damage by a flashback In this case replace the burner complete with connecting cables At the same time ch...

Page 50: ...o gas flow since gas solenoid valve Y57 2 is closed Fig 6 Port for measuring jet pressure A Check that no gas flows out measure gas tapping pressure refer to 031 Fig 6 A Check if the ignitor electrode E1 1 carries voltage and starts glowing A With the ignitor electrode E1 1 glowing check if flame sensor B1 16 opens A Check if now the gas solenoid valve Y57 2 receives voltage via the low ohmic igni...

Page 51: ... refer to 031 2 1 3 Safety time 4 2 Gas solenoid valve Remove A Remove the dryer lid refer to Lid Remove 010 4 1 A Remove the front panel refer to Front panel Remove 010 4 2 A Remove the left side panel refer to Side panel Remove 010 4 3 x Fig 7 A Pull the plugs off the gas regulation valve Descriptive Technical Documentation DTD no 12 9800 031 9 05 12 2006 US_am This information should not be dup...

Page 52: ...r maintain counter pressure on the valve A Remove the retaining bracket of the gas regulation valve Tools 7 mm Allen wrench and Phillips screwdriver A Take the gas regulation valve off the burner Descriptive Technical Documentation 031 10 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 12 2006 US_am ...

Page 53: ... regulation valve Tools 7 mm Allen wrench and Phillips screwdriver x Fig 9 A Tools Two 17 mm wrenches Attach the gas connecting line to the gas regulation valve Fasten the connecting nut and turn all the way to its stop x Fig 10 Descriptive Technical Documentation DTD no 12 9800 031 11 05 12 2006 US_am This information should not be duplicated or passed on without Miele approval All rights reserve...

Page 54: ... mm open end wrench x Fig 11 A Connect the 2 plugs and the ground lead to the gas regulation valve A Attach the right side panel A Attach the front panel A Attach the fascia panel A Attach the dryer lid Descriptive Technical Documentation 031 12 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 12 2006 US_am ...

Page 55: ... Remove A Remove the dryer lid refer to Lid Remove 010 4 1 A Remove the front panel refer to Front panel Remove 010 4 2 A Remove the left side panel refer to Side panel Remove 010 4 3 A Remove the gas solenoid valve refer to Gas solenoid valve Remove 031 4 2 x Fig 12 Descriptive Technical Documentation DTD no 12 9800 031 13 05 12 2006 US_am This information should not be duplicated or passed on wi...

Page 56: ...stall 031 4 3 A Attach the left side panel refer to Side panel Remove 010 4 3 A Attach the front panel refer to Front panel Remove 010 4 2 A Attach the fascial panel A Fit the dryer lid refer to Lid Remove 010 4 1 Descriptive Technical Documentation 031 14 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 12 2006 US_am ...

Page 57: ... normal gas pressure check the gas connections for tight seal using a spray such as Leak Test Check the function of the dryer Descriptive Technical Documentation DTD no 12 9800 031 15 05 12 2006 US_am This information should not be duplicated or passed on without Miele approval All rights reserved ...

Page 58: ...Descriptive Technical Documentation 031 16 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 12 2006 US_am ...

Page 59: ...040 Motor Fan Descriptive Technical Documentation DTD no 12 9800 040 1 05 12 2006 US_am This information should not be duplicated or passed on without Miele approval All rights reserved ...

Page 60: ...ume flow free flowing Approx 471 cubic yards h 360 m3 h 20 m pipe d 4 100 mm straight run without additional structures Table 1 Technical data Motor Fan Descriptive Technical Documentation 040 2 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 12 2006 US_am ...

Page 61: ...050 Air duct Front bearing Descriptive Technical Documentation DTD no 12 9800 050 1 05 12 2006 US_am This information should not be duplicated or passed on without Miele approval All rights reserved ...

Page 62: ...yonet closure activation via relay on the Program Power module EPWL USA 120 V 15 W Table 1 Technical data Air duct Front bearing Descriptive Technical Documentation 050 2 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 12 2006 US_am ...

Page 63: ...scia panel Control Power electronic Descriptive Technical Documentation DTD no 12 9800 090 1 05 12 2006 US_am This information should not be duplicated or passed on without Miele approval All rights reserved ...

Page 64: ...kwise Up to Rotary iron no reversing Starting with Rotary iron reversing cycle times 600 30 seconds clockwise counterclockwise Residual moisture sensing Target values residual moisture sensor B3 1 1 rib sampling Insufficient air detection via temperature sensor heating drying 2R30 and temperature sensor drying air 1R30 Table 1 Technical data Fascia panel Electrical system Descriptive Technical Doc...

Page 65: ...et more damp or more dry to suit customer preference x Permanent press more damp standard more dry Normal dry 4 2 0 Table 2 Residual moisture Permanent press 2 2 4 Memory When the memory function is activated the extra features selected at the start of a program are saved When the same program is selected again these extra features are automatically called up 2 2 5 Programming function Additional ...

Page 66: ...nd by With stand by activated the control lights and the drum light H3 6 are dimmed after 5 minutes to save energy 2 3 Residual moisture sensing The electronic detects the conductivity µS of the textiles via the residual moisture sensor B3 1 The residual moisture of the laundry is based on the measured conductivity value 2 4 Overriding time control A fixed maximum time of approx 180 minutes is imp...

Page 67: ...fficient air is displayed If the temperature at the temperature sensor heating drying 2R30 exceeds 356 F 180 C fault code F 66 leaking air is issued 2 6 Operating hours meter The time is counted from program start to the end of cool down without the time for delay start and anti crease action Descriptive Technical Documentation DTD no 12 9800 090 5 05 12 2006 US_am This information should not be d...

Page 68: ...ltage circuit is high ohmic the residual moisture sensor has no load detection this is not a technical fault No load detection refer to 030 2 1 No load detection Remedy A Correct the load or switch to a timed program Cause Defective residual moisture sensor B3 1 Check the residual moisture sensor B3 1 A Check the residual moisture sensor B3 1 for low ohmic continuity status refer to Service mode s...

Page 69: ...lint filter refer to operating instructions A Clean the lint filter in the door casing and in the fill ring XXX A Clean the air paths in the dryer Cause The fault message Clean air paths is issued prematurely Remedy A Adjust the fault message indication Clean air paths refer to operating instructions or Programming mode summary 090 4 1 Descriptive Technical Documentation DTD no 12 9800 090 7 05 12...

Page 70: ...Program stop cooling air phase buzzer sounds intermittently for 2 minutes Fault code F 1 or F 2 in the fault memory NTC temperature sensor heater bank short circuit or open circuit Cause NTC temperature sensor heater bank short circuit or open circuit Remedy A Check the lines and plugs of temperature sensor heating drying 2R30 for short circuit and open circuit A Temperature sensor heating drying ...

Page 71: ...ircuit A Temperature sensor heating drying 2R30 characteristic curve refer to 030 Table 3 Cause Heater bank is not heating Unheated the sensor is below the measuring threshold of 68 F Remedy A Electric Check the heater element R1 for short circuit and open circuit Cause Electric Defective heater relay K1 1 Remedy A Check the heater relay K1 1 Cause Electric Temperature limiter with manual reset F1...

Page 72: ...e Cause Demo mode is activated Remedy A Deactivate the demo mode refer to Demonstration mode Activate Deactivate 090 4 2 3 7 F 0 No fault Cause No fault is saved in the fault memory of the power module ELP Remedy A None Descriptive Technical Documentation 090 10 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 12 2006 US_am ...

Page 73: ... in NTC temperature sensor heating drying 2R30 Symptom Program stop cooling air phase intermittent buzzer tone Only the timed program cold air still works The LED Rotary iron flashes The LED Clean air paths flashes Opening and closing the door deletes this fault code indication Cause Open circuit of temperature sensor heating drying 2R30 68 F evaluation only after the heater has been run for at le...

Page 74: ...Cause Electric Temperature limiter with manual reset F1 has tripped Remedy A Reset the temperature limiter F1 A Find the cause for the temperature limiter tripping and rectify it Cause Gas Gas burner not heating Remedy A Check the gas burner refer to Gas burner Check 031 4 1 Descriptive Technical Documentation 090 12 DTD no 12 9800 This information should not be duplicated or passed on without Mie...

Page 75: ...TC temperature sensor drying air 1R30 Open circuit Symptom Program stop cooling air phase intermittent buzzer tone Only the timed program cold air still works The LED Hand iron flashes The LED Clean air paths flashes Opening and closing the door deletes this fault code indication Cause Open circuit 60 F in temperature sensor drying air 1R30 XXXTemperaturfühler Prozessluft 1R30 Unterbrechung 15 C R...

Page 76: ...Symptom Only in residual moisture programs This fault occurs in the normal operating mode Program stop cooling air phase intermittent buzzer tone for 2 minutes The LED Anti Crease End lights up solid The Fault Vent LED lights up solid Opening and closing the door deletes this fault code indication The safety time has been exceeded refer to 090 2 4 Overriding time control Cause Laundry too wet or d...

Page 77: ...perature limiter SOD F2 Remedy A Check the temperature limiter SOD F2 for open circuit Cause Defective residual moisture sensor B3 1 Residual moisture sensor B3 1 Check the sampler A Check the residual moisture sensor B3 1 voltage circuit for high ohmic isolation status refer to Service mode summary 090 4 3 Descriptive Technical Documentation DTD no 12 9800 090 15 05 12 2006 US_am This information...

Page 78: ...uzzer tone for 2 minutes Cause Air paths clogged Insufficient air measurement refer to 090 2 5 Insufficient air detection Remedy A Clean the air paths Descriptive Technical Documentation 090 16 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 12 2006 US_am ...

Page 79: ...ashes rapidly 5 Hz If access is not successful the control automatically reverts to the normal programming mode Options A Select the programming function Press the Buzzer pad The buzzer pad shows the programming function via a flashing rhythm A Select the option Press the Start Stop pad The Drying LED shows the Option selected via a flashing rhythm x Warning For the dryer to function properly spec...

Page 80: ...10 min 3 Insufficient air alert refer to 090 2 2 6 Programming function Prompt to clean air ducts 1 off 0 more sensitive 1 standard 2 less sensitive 3 Acoustical acknowledgment of touch pad activation refer to 090 2 2 7 Acoustical acknowledgment 1 1 off 0 on 1 Characteristic curve setting refer to 090 2 2 8 Conductivity setting 1 2 normal 0 low 150 µS 1 Stand by refer to 090 2 2 9 Stand by 1 3 off...

Page 81: ...ment indicator The demo program starts running If access is not successful the control automatically reverts to the normal programming mode Options A demo program cycle lasts about 40 s then there is a short pause stand by and the demo program starts again A Operating simulation Interactive demo mode In interactive demo mode the appliance can be operated without a program being started Save and qu...

Page 82: ... flashes slowly 1 Hz Acknowledgement indicator The Start Stop LED flashes slowly 1 Hz If access is not successful the control automatically reverts to the normal programming mode Options A To select a service function Press the Buzzer pad A To start a service function Press the Start Stop pad x Note The component test switches off automatically 30 minutes after the last component is activated Serv...

Page 83: ...mic status isolation Requirement No electrical connection between drum and sensor rib 5 Steady buzzer tone 6 LED displays flash 0 5 Hz 7 Heater relay 2K1 1 on and Drive motor Fan motor M5 on 8 Heater relays 1K1 1 2K1 1 3K1 1 on Heater R1 R2 R3 on and Drive motor Fan motor M5 on 9 Sensor test 5 3 All sensors inactive Door lock A2 Door closed Switch closed buzzer on Door open Switch open buzzer off ...

Page 84: ...EW and fascia support panel Remove x Fig 2 A Take the fascia panel off A Remove the screws of the program selection module EW press in on the retaining tabs and take the electronic module off Descriptive Technical Documentation 090 22 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 12 2006 US_am ...

Page 85: ... the screws of the fascia support panel A Lift the fascia support panel out and remove it Descriptive Technical Documentation DTD no 12 9800 090 23 05 12 2006 US_am This information should not be duplicated or passed on without Miele approval All rights reserved ...

Page 86: ...Descriptive Technical Documentation 090 24 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 12 2006 US_am ...

Page 87: ...100 Electrical system x Descriptive Technical Documentation DTD no 12 9800 100 1 05 12 2006 US_am This information should not be duplicated or passed on without Miele approval All rights reserved ...

Page 88: ...s 1K1 1 2K1 1 3K1 1 Single anchor relays Rating 11 A Coil 12 V DC 200 Ω Heater relays 1K1 1 2K1 1 Table 1 Technical data Electrical system Descriptive Technical Documentation 100 2 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 12 2006 US_am ...

Page 89: ...ice 4 1 Fuses Replace T 9800 x Fig 1 Descriptive Technical Documentation DTD no 12 9800 100 3 05 12 2006 US_am This information should not be duplicated or passed on without Miele approval All rights reserved ...

Page 90: ...Descriptive Technical Documentation 100 4 DTD no 12 9800 This information should not be duplicated or passed on without Miele approval All rights reserved 05 12 2006 US_am ...

Reviews: