background image

GeNeRAL

Meltric’s DN7c, DN9c and DN20c Series industrial,

multipin plugs and receptacles are designed to

ensure safety and provide reliable electrical connections.

Please follow the instructions below to ensure proper

installation and safe use of the product. 

There are inherent dangers

associated with electrical prod-

ucts. Failure to follow safety precautions can result in

serious injury or death. These instructions must be

followed to ensure the safe and proper installation,

operation and maintenance of the Meltric devices.

Before installation, disconnect all sources of power to

the circuit to eliminate the risk of electrical shock.

RATINGS

The DN9c and DN20c products are manufactured

and load-break rated in compliance with CSA

Standard C22.2 No. 182.1.  The DN7c product is

manufactured and rated in compliance with CE

Standards IEC 60309-1.  The product ratings are

indicated on the device’s labels.  Additionally the

DN9c and DN20c are HP rated for multiple HP loads

as long as any single HP load doesn’t exceed the

levels shown in Table 1.  Their short circuit withstand

levels and fuse ratings are shown in Table 2.

INSTALLATIoN

These products should be installed by qualified 

personnel in accordance with all applicable      

local, state and national electrical codes.  

Before starting, verify that the power is turned off; the

product ratings are appropriate for the application;

and the conductor sizes are within the capacities of

the terminals noted on Table 3.

General Notes & Precautions

1. Self-tapping screws are provided for use with

some polymeric accessories.  

NoTICe:

Once

they are seated, care should be taken in order

to avoid over-tightening them against the

plastic material.

2. Various handles, cord grips or strain relief

options may be used.  These instructions are

based on handles provided with integral,

multi-layer, bushing cord grips.

3. Wire strip lengths are indicated in Table 4.  Strip

lengths for cable sheathing will depend on the

specific application.

4. Wiring terminals are spring-assisted to prevent

loosening due to wire strand settlement, vibration

and thermal cycling.  

NoTICe:

They should not

be over-tightened.  Appropriate tools and

tightening torques are indicated in Table 5.

The DN9c and DN20c plugs and receptacles’ contacts

are labeled with F or S numbers respectively.  The 

F-number on the inlet has a corresponding S-number

on the receptacle.  See table 6 for details.

Assembly for In-line Connections

Do not overtighten terminal or self-tapping

screws. Tighten screws to the proper torque to 

ensure a secure connection.

When the DN9 and 50A DN7c products are used 

as in-line connectors, finger drawplates should be

installed on both the receptacle and plug in order to

provide the user with the leverage to connect the

device (finger drawplates are not available on DN20c

or 90A and 150A DN7c devices). 

NoTICe:

The longer screws provided with the finger

drawplates must be used when assembling devices

with finger drawplates because the shorter screws

provided with the handle are not long enough to

properly secure both the handle and drawplates to the

inlet or receptacle and achieve a watertight connection.

Adjust the bushing diameter to fit the cable by removing

the inner sections as required.  Insert the bushing

into the strain relief, then insert the assembly into the

handle and loosely install the compression nut.

Insert the cable through the handle, the thin black

(neoprene) drawplate gasket, the finger drawplate 

(if applicable) and the color coded gasket.  Strip the

cable sheath to provide a workable wire length, being

mindful that the sheath must extend into the handle

to achieve a secure cord grip.  Then strip the individual

wires to the lengths indicated in Table 2 and twist the

strands of each conductor together. 

Back out the terminal screws on the receptacle (or

inlet) far enough (but not completely) to allow the

conductors to pass.  Insert the conductors fully into

their respective terminals and tighten the terminal

screws with the appropriate tool to the torque 

indicated in Table 3.

Verify that the cable sheath extends beyond the strain

relief and into the handle.  Assemble the receptacle

(or inlet), the color coded gasket, followed by the 

finger drawplate, and the thin black (neoprene) 

drawplate gasket (if applicable) to the handle and

tighten the compression nut to secure the cable. 

Assembly for Mounted Receptacles (or Inlets)

In applications where the receptacles (or inlets) are

mounted to wall boxes, panels or other equipment,

optimal operation is achieved when the devices are

installed with the latch at the top. 

Insert the cable or wires through the wall box and cut

to allow adequate length.  Strip the cable sheath as

Compression

Nut

Handle

Strain

Relief

Color-Coded

Gasket

Receptacle

(or Inlet)

Bushing

Finger Drawplate Gasket

Finger Drawplate

Table 4 - Wire Strip Length – Dimensions A

Receptacle

Plug/Inlet

Device/Contacts

Inches mm Inches mm

DN7c (50A)   Contact

3/4

20

3/4

20

DN7c (90A)   Contact

1

25

1

25

DN7c (150A) Contact

1 3/16

30

1 3/16

30

DN9c 

Contacts

1/2

13

1/2

13

DN20c 

 Contacts

1/2

13

1/2

13

Mount with the latching pawl at

the top to counteract the weight

and strain of the plug & cable.

Mount the receptacle

at a downward angle

whenever possible.

Table 3 — Wiring Terminal Capacity* (in AWG)

Contacts

Device

Min

Max

DN7c (50A)

10

6

DN7c (90A)

8

2

DN7c (150A)

6

3/0

DN9c

16

10

DN20c

16

10

*Capacity is based on THHN wire sizes.

Table 5 - Terminal Screw Tightening Torques

Torque

Required Screwdriver

Device/Contact in-lbs N-m

or Allen Wrench

DN7c (50A)Contact

13.3

1.5 5/64” hex head 2mm hex head

DN7c (90A)Contact

30.0

3.5

1/4” precision tip

DN7c (150A) Contact

80.0

9.0

4 mm hex head

DN9c

Contact

4.50

0.5 5/64” hex head 2mm hex head

DN20c

Contact

4.50

0.5 5/64” hex head 2mm hex head

Table 6 - DN9c & DN20c Wiring

Plug/Inlet

Corresponding

Receptacle

Contact Nos.

mating pin

Contact Nos.

F1 (Ground)

S1 (Ground)

F2

S2

F3

S3

F4

S4

F5

S5

F6-19

S6-19

F20

S20

OPERATING INSTRUCTIONS

INSDN I

Meltric Corporation

 

4765 W. Oakwood Park

 Drive Franklin, WI 53132

 

Tel. : 800 433 7642 / Fax : 

414 433 2701

/ e-mail : [email protected] 

A manufacturer of products using

 

Marechal technology

meltric

.com

DN7C/DN9C/DN20C

MULTIPIN

Table 2 — Short Circuit Withstand Ratings

Device

Rating Fuse

Type*

DN9c

10 kA @ 480 VAC

DN20c

10 kA @ 480 VAC

*Ratings applies with fusing up to this amperage. Ratings are based

on tests performed with Ferraz Shawmut current limiting fuses.

RK1 NTD  35 A

RK5 TD   20 A

RK1 NTD  35 A

RK5 TD 20 A

Table 1 — Maximum HP at Rated Voltage Levels

1-Phase

3-Phase

Device 120 V

240 V

208 V

240 V

480 V

HP FLA HP FLA HP FLA HP FLA HP FLA

(A)

(A)

(A)

(A)

(A)

DN9c 1/3 7.2

1

8

2 7.8 3 9.6 5 7.6

DN20c 1/6 4.4 1/2 4.9 1 4.8 1 4.2 3 4.8

WARNING

Reviews: