background image

Master Battery, S.L.

If you encounter any problem on the inverter, please find out the inverter S/N 

and contact us, we will try to respond to your question ASAP. 

Beta

 AC Coupled Inverter

 

Instruction Manual

Ver

1

.

0

Please adhere to the actual products in case of any discrepancies in this user manual. 

Master Bat

t

ery, S.L.

 

Paseo de Extremadura, 39

 

28935 Móstoles, Madrid, Spain

Tel: +34 918 021 649   
Fax: +34 917 750 542
Email: [email protected]
Web: www.masterbattery.es

Summary of Contents for RAI-3K-48ES-5G

Page 1: ...respond to your question ASAP Beta AC Coupled Inverter Instruction Manual Ver 1 0 Please adhere to the actual products in case of any discrepancies in this user manual Master Battery S L Paseo de Extremadura 39 28935 Móstoles Madrid Spain Tel 34 918 021 649 Fax 34 917 750 542 Email info masterbattery es Web www masterbattery es ...

Page 2: ...mmissioning 6 1 Preparation of Commissioning 6 2 Commissioning Procedure 7 Troubleshooting 32 5 5 Advanced Settings 2 3 Notice for Use 5 3 3 Terminal Connection 16 36 8 Maintenance 12 11 5 Operation 5 1 Main Menu 4 1 Select a Location for the Inverter 4 2 Mounting the Inverter 4 3 Assemble the Battery Cables 4 4 Assemble the AC Cables 4 5 CT Installation 4 6 Assemble Other Cables 4 7 LED Indicates...

Page 3: ...terminal x6 3 2 1 Introduction 1 Introduction 1 2 Packaging Please ensure that the following items are included in the package along with your inverter CT x1 Wifi a ntenna x 1 If anything is missing please contact your local Beta distributor Locking screws x2 Display Keys RAI 3K 48ES 5G User manual x1 Instruction Manual Beta AC Coupled Inverter Ningbo Ginlong Technologies Co Ltd Ver 1 0 CAN cable x...

Page 4: ...k from energy stored in capacitors of the Inverter do not remove cover for 7 minutes after disconnecting all power sources service technician only Warranty may be voided if the cover is removed without authorization CAUTION The surface temperature of the inverter can reach up to 75 167 F To avoid risk of burns do not touch the surface of the inverter while it s operating Inverter must be installed...

Page 5: ... inverter please refer to the instructions below before start connection 3 3 Terminal Connection Figure 3 2 Front panel display Dry Contact Port WARNING Please refer to the specification of the battery before configuration CAN CT Meter WIFI DRM COM AC backup port L N PE AC grid port L N PE Battery Battery 3 Overview 4 1 Select a Location for the Inverter Figure 4 1 Recommended installation locatio...

Page 6: ...m 300mm 300mm 300mm 300mm Figure 4 2 Inverter mounting clearance Install on a wall or strong structure capable of bearing the weight of the inverter 15kg 4 2 Mounting the Inverter The inverter shall be mounted vertically The steps to mount the inverter are listed below 1 Select the mounting height of the bracket and mark the mounting holes For brick walls the position of the holes should be suitab...

Page 7: ...verter Please make sure the labels on cable and inverter match up Step 4 Lock the 4 M4 screws and fix the cover onto the inverter Step 5 Connect the other side of the battery power cables to the battery Figure 4 7 WARNING Incorrect polarity of the battery cable may lead to permanent damage on the device Figure 4 8 BAT Battery BAT Battery M4 cross screws DO CT Meter WIFI CAN DRM COM WARNING To avoi...

Page 8: ...jacket and strip the wire insulation to a length of 10 12mm Figure 4 9 Step 3 Fasten the AC cables onto the terminals on the inverter Please make sure the correct polarity Ensure that the correct conductor is fastened 0 7 N m torque to the correct terminal Describe Wire diameter 6 12mm 6mm 12mm Traverse cross sectional area Exposure Length Numerical value 40 mm 10 mm 12 mm PE L N Step 4 Lock the 4...

Page 9: ...dence between the cables and the stitches of plug Pin5 and Pin6 of RJ45 terminal is used for the logic interface other Pins are reserved Pin 1 Reserved Pin 2 Reserved Pin 3 Reserved Pin 4 Reserved Pin 5 Switch_input1 Pin 6 Switch_input2 Pin 7 Reserved Pin 8 Reserved 1 8 RJ45 plug Rj45terminal 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 DRM logic interface Switch_input1 Switch_input2 Figure 4 16 Strip the insu...

Page 10: ...lled by LCD or APP Beta TechView For IOS system please go to AppStore to search for Beta TechView then download and install it For Android system please go to Google Play to search for Beta TechView then download and install it Besides it can be also installed by scanning the QR code on the back cover of this manual To use the APP to control the inverter you need to make sure the inverter is opera...

Page 11: ...Info 2 Syetem Info 3 Energy Records 4 BMS Info 5 CT Info The Beta AC Coupled Inverter main menu provides access to operational data and information The information is displayed by selecting Information from the menu and then by scrolling up or down There are 5 submenus in the Information 5 Operation Figure 5 2 Information list General Info Display Description Inverter SN 00000000000000 Device Batt...

Page 12: ...nsumption GridGetE Today 000 0kWh GridGetE Lastday 000 0kWh Grid SendE Today 000 0kWh Grid SendE Lastday 000 0kWh LoadE Total 0000000kWh LoadE Today 000 0kWh LoadE Lastday 0000000kWh Grid SendE Total 0000000kWh Figure 5 5 Information list BMS Info Display Description Battery V 00 00V Battery I 00 0A Battery voltage and current Battery charge discharge current limitation SOC and SOH of battery BMS ...

Page 13: ...password is 0010 Please press down to move the cursor press up to select the number 5 4 1 Alarm Message The display shows the latest alarm messages 100 Alarm000 ACOvercurrent T 02 21 22 15 D 0000 Figure 5 10 Alarm message The display shows the latest warning messages 100 5 4 2 Warning Message Msg000 T 00 00 00 00 D 0000 Figure 5 11 Warning message 5 4 3 Running Status This function is for maintena...

Page 14: ...er Def menu will access to the following submenu Figure 5 16 OV G V1 260V OV G V1 T 1S NOTE The User Def function can be only used by the service engineer and must be allowed by the local energy supplier OV G V1 240 270V OV G F1 50 2 53Hz 60 2 63Hz OV G V1 T 0 1 9S OV G F1 T 0 1 9S OV G V2 240 300V OV G F2 50 2 53Hz 60 2 63Hz OV G V2 T 0 1 1S OV G F2 T 0 1 9S UN G V1 170 210V UN G F1 47 49 5Hz 57 ...

Page 15: ...e backup port Enable or disable the voltage droop 5 5 4 1 Backup Settings Backup Voltage 230 0V Figure 5 23 Backup settings 5 5 5 Storage Energy Set Mode Off Grid Mode Figure 5 24 Storage energy set It includes Stg mode select which defines different working logic of the hybrid inverter There are two options in the Stg Mode Select Time charging and Off grid Another default mode is Auto mode Maximi...

Page 16: ... the Main Menu to access the following options 1 Meter CT Select 2 EPM ON OFF 3 Backflow Power 5 5 8 1 Meter CT Select There are 2 settings in this menu as below 1 CT 2 Meter 5 5 8 2 EPM ON OFF There are 2 settings in this menu as below 1 ON 2 OFF 5 5 8 3 Backflow Power This submenu is used for set allowed power that inverter can send to grid YES ENT NO ESC P_Backflow 0001W Figure 5 25 Backflow pow...

Page 17: ...ntioned above meet the requirements proceed as follows to start up the inverter for the first time 6 2 1 Switch on the AC backup and AC grid 6 2 2 Follow the picture below to select grid standard 6 2 3 Switch on the DC circuit breaker between inverter and battery 6 2 4 Optional When the battery equipped is Pylon Li ion Battery or BYD battery turn on the switch on the battery manually 6 2 5 The rel...

Page 18: ...t Sampling Error Grid Transient Overcurrent Battery Hardware Overcurrent OV G F Grid Overfrequency UN G V Grid Undervoltage OV G V Grid Overvoltage Check if the grid is correctly connected wait for the grid to be normal 33 Check if the grid is correctly connected wait for the grid to be normal Check if the grid is correctly connected wait for the grid to be normal Check if the grid is correctly co...

Page 19: ...le service Check if the battery overvoltage setting is reasonable if the battery reaches its end of life Restart the inverter if the fault still exists contact Beta after sale service Check if the battery is correctly connected or the battery contactor is disconnected Restart the battery Check if the battery overvoltage setting is reasonable if the battery reaches its end of life OV Vbackup Over L...

Page 20: ...ge V Frequency Hz AC Output Back up Ingress protection Operating temperature range Humidity IP65 0 100 No Condensing Environment Limit Altitude m Noise emission typical dB 2000 35 System Parameters Demensions WxHxD mm Weight kg Standby Losses W Cooling concept Topology Communication Display Dry port Standard warranty year Cetification 403 525 170 15 8 Natural High frequency isolation WiFi RS485 CA...

Page 21: ...up side 2 Loads is not powered 3 Loads is supplied from grid side If RAI needs maintenance then just switch AC Changeover Switch to position 3 as shown above Thus the loads will be supplied by grid AC Changeover Switch is a 3rd party item not supplied by Ginlong 9 1 Special Back up Connection 38 ...

Reviews: