background image

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

ZEB2-1_DBL_LST_EN_0826.PDF • PAGE 1

A

Building Safety. Building Security.

Description

With the Zone Extension Board ZEB2-1 a Fire Detection 

Control Panel BC06-1 or BC06-2 can be extended from 

four to six detector zones. In the event of an alarm, the 

fi re detection control panel indicates the activation of 

the detector zone via LED. Depending on the detector 

type, each of the two detector lines can be individually 

parameterised as detector zone for fi re alarms or as 

detector zone for fault messages.

Alarms from manual call points and from automatic de-

tectors that are connected together to a detector line 

can be differentiated and thus evaluated differently by 

the fi re detection control panel, by means of an optional 

coding module.

Each  input  of  the  zone  extension  board  is  protected 

against overvoltage and thus provides high system sta-

bility.

•   Extends Fire Detection Control Panels 

BC06-1 and BC06-2 by further 2

conventional detector zones

•   Individual setting of detector zone 

function

•   Differentiation between the activation 

of automatic detectors and manual 

call points on the same detector line

•   Lines monitored for wire breakage, 

short circuit, and short to earth

Specifi cations

Current consumption at 24V 

typ. 14mA (line termination 5.6k

Ω

, without detectors)

 

typ. 7mA (line termination 47µF, without detectors)

Line voltage 

typ. 20V (line termination 5.6k

Ω

)

 

typ. 23V (line termination 47µF)

Line current 

typ. 3.7mA (line termination 5.6k

Ω

)

 

typ. 0mA (line termination 47µF)

Line termination 

5.6k

Ω

 or 47µF

Line resistance 

max. 50

Ω

 per core

Ambient temperature 

-5°C to +50°C

Dimensions L × W × H 

103 × 58 × 15 (mm)

Weight 

34g

Order number 

210210

Order name 

Zone Extension Board ZEB2-1

Reviews: