background image

 

LK-GA502 

Gas Detector 

 

Gas Alarm for   

Natural or Bottled (LPG) Gas 

With Relay Output 

User’s Guide 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

ATTENTION:

 Please take a few minutes to thoroughly read 

this manual, which should be saved for future reference and 
passed on to any subsequent owner. 
 

 

IMPORTANT! READ ALL INSTRUCTIONS BEFORE 
INSTALLATION AND KEEP THIS MANUAL NEAR THE 
ALARM FOR FUTURE REFERENCE. 

 

CONTENTS OF THIS MANUAL 

 
1 – DESCRIPTION 
2 – FEATURES 
3 -- TECHNICAL SPECIFICATION 
4 -- INSTALLATION INSTRUCTIONS 
5 -- OPERATION AND TESTING 
6 -- GAS SAFETY GUIDE 
7 -- HOME SAFETY GUIDE 
8 -- SERVICE AND WARRANTY 

1. DESCRIPTION 

The gas alarm is designed for single station use. Small 
and compact, the design and color makes it ideal for 
use in the home, small commercial properties, and 
recreational vehicles. It is intended to detect leakage of 
natural gas (methane gas), town gas, and bottled gas 
(propane gas). The unit is designed for DC wire-in 
applications. The gas alarm can be mounted high (for 
methane gas) or low (for propane (LPG) gas). It is 
equipped with a sturdy metal mounting bracket for 
quick, easy, and secure installation. 

 
2. FEATURES 

 

Detect all sorts of combustible gases, natural gas 
(methane), bottled gas (propane), LPG (Liquefied 
petroleum Gas), LNG (Liquefied natural gas), coal 
gas, including town gas. 

 

Easy to install, mounting bracket included. 

 

Loud 85dB alarm and LED warning light. 

 

High quality durable sensor. 

 

Self diagnostic function by MCU intelligent software. 

 

Excellent reliability & High stability. 

 

Ideal for all kitchens. 

 
3. TECHNICAL SPECIFICATIONS 

Unit Dimensions:        103mm (D) x 55 mm (H)  
Color:                                    Ceiling White 
Weight:                                  155g 
Operating Temperature:   -10°C to +50°C 
Ambient Humidity:               

95% RH 

Alarm Horn:              85dB at 3m (10 feet) 
Operating Voltage:        DC9-28V 
Power Consumption:      <1.5W (Standby), <5W (Alarm) 
Value of Detection Threshold (Lower Explosive Limit): 

Natural Gas: 7500ppm (15% LEL) 
LPG:      2000PPM (10% LEL) 
Coal Gas:    800PPM (2% LEL) 

Method of Alarm:    Flashing Red LED with 85dB alarm 
Warm Up Time:   approximately 60 Seconds 
Alarm Output: Relay Output (N/O 2A@DC24V) 
 

4. INSTALLATION INSTRUCTIONS 

The Gas Alarm is intended to detect leakage of natural 
gas, town gas and bottled gas. It is intended for 
installation in the home, small commercial properties, 
and recreational vehicles. 

 

Installation shall only be undertaken by technicians 
holding a certificate issued by an authorized 
distributor.  

 

For detecting natural gas (lighter than air), the 
alarm should be installed within 30 centimeters 
below the ceiling and the maximum distance away 
from the furnace or gas appliances is 8 meters. 

 

For detecting LPG (heavier than air), the alarm 
should be installed within 30 centimeters above the 
floor and the maximum distance away from the 
furnace or gas appliances is 4 meters. 

 

The alarm should not be located close to any 
obstacles preventing natural air circulation. It should 
also not be located in a draft or close to a cooker 
(cooking smells and other fumes can have a bad 
influence on gas detection). 

 

The detector can be connected with Security alarm 
panel as Figure1. Relay output signal can be 
changed from Normal Close(NC) to Normal 
Open(NO) by Jump JP1 on the PCB board. 

 

The detector can be connected with conventional 
alarm panel as Figure 2 or Figure3. 

For your convenience, 

  write down the following information. 

If you call Us for Service, these are the first questions 

you will be asked.

 

Gas Alarm Model Number (located on back of alarm):

 

Gas Alarm Assembly Number (Located on back of alarm):

 

Date of Purchase: 

 

Where Purchased: 

 

Reviews: