Plafond

Service & maintenance 

lindab  |  we simplify construction

Summary of Contents for Atrium C 33

Page 1: ...Plafond Service maintenance lindab we simplify construction ...

Page 2: ...lm needs to be removed before commissioning the products 1 3 Mounting instruction Please visit www lindqst com Select Documentation Finder Select Plafond Select Mounting 1 4 Air connection installation The primary air supply should be connected with instructions from a ventilation spe cialist Lindab s chilled beams can beneficially be used together with Lindab s Safe duct systems 1 5 Connection de...

Page 3: ...is covered by a plastic or rubber protection cover which should be removed before installation After removing the protection cover make sure that the pipe is intact and undam aged especially at the pipe end Crocked or in other ways imperfect pipe ends will result in leaks Deburr the pipe on the inside and the outside using a deburring tool before installation Mount a push on fitting to the pipe Ma...

Page 4: ...e work While mounting a compression fitting the pipe will be exposed to a big amount of force creating a risk of crushing the pipe To ensure that the pipe won t be crushed when mounting the compression fitting a copper insert should be inserted into the pipe Both flow and return pipe is covered by a plastic or rubber protection cover during transport which must be removed before installation After...

Page 5: ...connection pipes are internally soft welded why it s not allowed to solder the beam to the pipes 1 5 3 Flex hoses Our flexible hoses can be used with both compression and Tectite fitting We recom mend using Tectite fittings for easier and faster mounting Please ensure that all pipes and fittings are undamaged as even small dents and scratches potentially pose a risk of leakage in the system Always...

Page 6: ...de and the outside using a deburring tool before installation Mount a push on fitting to the pipe Make sure to press the fitting all the way onto the pipe After mounting the push on fitting mount the flexible hose Make sure that the flexible hose is pushed fully into the fitting Consult the installation guide for the specific fitting for further details on proper installation Push on fitting Push ...

Page 7: ...r Nozzles Number of nozzles Plugs Number of plugged nozzles Product ID Product number Sign To be signed when checked and commissioned on site 2 2 Measure air pressure and calculating the airflow Before calculating the airflow the static nozzle pressure must first be measured The static nozzle pressure is the air pressure available at the nozzles 2 2 1 Measure the static nozzle pressure To measure ...

Page 8: ... 2013 05 03 2 2 2 Calculating the airflow After measuring the static nozzle pressure calculate the air flow per nozzle q 0 0209 P q air flow per nozzle P static nozzle pressure After finding the air flow per nozzle find the needed number of open nozzles q tot q n open q tot total air flow n open open nozzles Alternatively read off the needed number of nozzles in the diagram below Diagram 1 Shows n...

Page 9: ...unt Use the specially designed Lindab Nozzle Plugs and Lindab plugging tool to plug the nozzles To plug a nozzle first locate the nozzles to plug Keep in mind that the closed nozzles should be diveded as equally along the beam as posible to reach a sym etric spread pattern Insert the plug into the nozzle Make sure that the plug is fully inserted The reconfiguration is now complete 2 3 1 Removing p...

Page 10: ... The interval of cleaning depends on the indoor environment where the beam is placed Under optimal conditions the Plafond beams only need cleaning every 5 years 3 1 Cleaning instructions Remove the faceplate Clean underneath the battery with a vacuum cleaner and a piece of wet cloth Only use lukewarm water and a mild detergent ...

Page 11: ...ation Finder Select Plafond Select Environmental declaration 4 3 Working and test pressure Lindab s waterborne products have been manufactured and tested according to the Pressure Equipment Directive 97 237EC The products are classified as SEP Sound Engineering Practice Pressure table Pressure class PN10 Max working pressure 10 bar Max recommended dynamic pressure 0 2 bar Max test pressure 16 bar ...

Page 12: ... must be filled with potable water that complies with the EC directive 98 83 EC pH value of water must be between approximately 6 9 pH The water velocities should not exceed 1m s and should be kept as close to the nominal flow as possible to minimize noise and optimize the energy yield There should be used in line strainers to remove dirt particles from the water If the water contains any additive...

Page 13: ...ystiedot www lindab fi Oikeus muutoksiin pidätetään DE Hier finden Sie aktuelle Produktinformationen Mon tageanleitungen und Telefonnummer E Mail Adressen der Ansprechpartner www lindab de Änderungen vorbehalten IT Qui potete trovare istruzioni di montaggio informa zioni sul prodotto ed un supporto tecnico qualificato Tel 011 9952099 e mail lindab lindab it www lindab it Soggetto a modifica senza ...