background image

1

/

7

Stationary Battery Analyzer

Model No.

CTE-3000

Instruction Manual

Chapter 1: Description

1.Description

CTE-3000 is a stationary battery analyzer that measures the conductance and voltage of 12V lead acid

stationary battery to identify those that:

. Are good.
. Are serviceable
. Need to be replaced.

2. Specification

2.1 The analyzer measures the status of a battery in voltage and conductance values. It displays

conductance values in Siemens (S). Ampere hours (Ah) are a typical measurement of jar capacity; however,
they are difficult to measure without knowing the load to which the jars supply power. Lancol recommends
that you use a reference value to compare the conductance value to the test results. A reference value is a
typical conductance value for the type of jars you are testing. For more information about determining a
reference value, refer to

Chapter 2: Pre-testing.

Summary of Contents for CTE-3000

Page 1: ...es the status of a battery in voltage and conductance values It displays conductance values in Siemens S Ampere hours Ah are a typical measurement of jar capacity however they are difficult to measure...

Page 2: ...ange of 300 2200S batteries about 30Ah 300Ah Data Storage CTE 300 can store 100 groups of test results and you can output the test results to your computer with the USB cable Parts of the analyzer CTE...

Page 3: ...g For this reason the following options are listed in the order you should take to obtain a reference value 1 Consult your company documentation for previous reference values that were created for the...

Page 4: ...test all batteries of the group and use the average conductance value as your reference value Chapter 3 Testing 3 1 1 Connect Tester Shake the clamps back and forth to make sure they are well connect...

Page 5: ...up interface Default voltmeter is ON refer to figure 1 Figure 1 Startup Interface with Voltmeter on At the middle bottom of the startup interface it displays the voltmeter value which can be used as D...

Page 6: ...w Results view all of your tested results supported maximum 100 groups of testing results 3 4 2 Export Data You may output the tested results to your computer Firstly you should install the software P...

Page 7: ...to look for physical damage 60 80 Serviceable with maintenance Check for problems and refer to Test results or other information about the site to determine the cause of low readings Your company main...