ESCR
Quick Start Guide
La Marche ESCR Engine Starting Battery Charger:
Getting started
La Marche Mfg. (A U.S. Company)
106 Bradrock Drive, Des Plaines, IL 60018
Tel: 847.299.1188 Fax: 847.299.3061
www.lamarchemfg.com
WARNING: Please read the Important Safety Instructions before proceeding.
1
Remove Bottom Panel
Make Sure to check for any shipping damages before getting started.
1
2
Connect AC 120/208-240. Te
unit automatically detects the
AC input without changing any
taps or switches. Battery does
not need to be connected
during configuration mode.
3
To change setting, you must enter the
configuration mode by pressing the
CONFIG/OK red button located on the
front panel. The unit does not supply
output in the configuration mode.
Units are factory set at 12 Volt.
Reset Button
OK Button
Cell Type
6 Lead Acid
Float Voltage
2.25 Volts per Cell
Equalize Voltage
2.33 Volts per Cell
Equalize Timer
8hr - Equalize Timer
Manual - Equalize Cycle
Current Limit
105%
Temperature Compensation
Disabled
Alarm Setting
Alarm Delay - 5 Sec
Low VDC - 1.98 VDC
High VDC - 2.45 VDC
Low DC Current - 0.5 Amps
AC Failure
.
.
.
.
.
.
.
.
ESCR-40/20-12/24V-AV1:
ESCR-20/10-12/24V-AV1