background image

Thank you for choosing our KONICS products.

Please read the following safety considerations before use.

Controls & Measurement

KRN50 Series

사용자 매뉴얼

50mm 소형 하이브리드 기록계

KRN50 Series

KRN50 Series

50mm Small Hybrid Recorder

USER MANUAL

Summary of Contents for KRN50 Series

Page 1: ...r choosing our KONICS products Please read the following safety considerations before use Controls Measurement KRN50 Series 사용자 매뉴얼 50mm 소형 하이브리드 기록계 KRN50 Series KRN50 Series 50mm Small Hybrid Recorder USER MANUAL ...

Page 2: ... ii Copyright Reserved KONICS Co Ltd ...

Page 3: ...ng KONICS product Please familiarize yourself with the information contained in the Safety Considerations section before using this product This user manual contains information about the product and its proper use and should be kept in a place where it will be easy to access ...

Page 4: ... or reproduced in either part or whole without permission A user manual is not provided as part of the product package Visit our web site www konics com to download a copy The manual s content may vary depending on changes to the product s software and other unforeseen developments within KONICS and is subject to change without prior notice Upgrade notice is provided through out homepage We contri...

Page 5: ... Symbol Description Supplementary information for a particular feature Failure to follow instructions can result in serious injury or death Failure to follow instructions can lead to a minor injury or product damage An example of the concerned feature s use 1 Annotation mark ...

Page 6: ... before use Failure to follow this instruction may result in electric shock Do not connect repair or inspect the unit while connected to a power source Failure to follow this instruction may result in electric shock Check the terminal numbers before connecting the power source Failure to follow this instruction may result in fire or burning the unit Lithium battery is used in the unit Do not disas...

Page 7: ... rated switching capacity of the relay contact Failure to follow this instruction may result in insulation failure contact melt contact failure relay broken or fire When connecting magnet contact as relay contact output load attach a surge absorber at contact coil Failure to follow this instruction may result in product malfunction Do not use water or oil based detergent when cleaning the unit Use...

Page 8: ... during dielectric or insulation resistance test Failure to follow this instruction may result in electric shock Use insulation transformer and noise filter power for too much noise from the power Attach noise filter on the grounded panel etc Use short cables for noise filter output part and power terminal of the unit Failure to follow this instruction may result in product damage malfunction by s...

Page 9: ...Components 12 1 2 2 Sold separately 13 1 3 Ordering information 14 1 4 Part descriptions 15 2 Specifications 17 2 1 Input type and range 19 3 Dimensions 21 4 Connections 23 5 Installations 25 5 1 Environment 25 5 2 Installation method 26 5 2 1 Panel mounting 26 6 Functions 27 7 General operation and parameter setting menu 29 7 1 Operation mode 29 7 2 Operation procedure 29 7 3 Setting keys 30 7 4 ...

Page 10: ...ction and setup 36 8 2 1 Input type setup 36 8 2 2 Alarm function setup 47 8 2 3 Recording setup 59 8 2 4 Display information function 78 9 Communication 83 9 1 Modbus address map 85 10 Comprehensive device management program DAQMaster 91 10 1 Overview 91 10 2 Features 92 10 3 Dedicated function for KRN50 93 Table of contents ...

Page 11: ...orts RS485 communication and dedicated communication port to set or monitor parameters in real time by PC PLC Multi input with high accuracy 0 2 level RTD TC Voltage Current shunt 2 channel simultaneous recording in graphic mode and digital mode High visibility and easy setting by LCD dot matrix Supports various option I O function Small size W96 H96 L100 mm light weight ...

Page 12: ...ent and sold separately 1 2 1 Components KRN50 Mounting Bracket 2 User manual Chart paper 2 Resistance 50Ω 2 Before using KRN50 check the component If any component is left out or damaged contact our company or seller KONICS service center 82 32 820 2356 to 7 ...

Page 13: ...eparately SCM 38I RS232C to RS485 converter SCM US48I USB to RS485 converter SCM US USB to Serial converter Use Autonics SCM 38I SCM US48I or SCM US as communication converter SCM 38I RS232C RS485 converter and SCM US48I USB RS485 converter are same appearance ...

Page 14: ...on output 1 1 channel 2 2 channel 0 None 2 Alarm output 2 1 4 Alarm output 4 2 2 KRN50 0 0 4 4 0 Power supply Option output Alarm output Number of input channels Item CH2 control output CH1 control output 1 When selecting this for 2 CH model two alarm outputs for CH1 are available In other words you cannot set one for CH1 and one for CH2 2 It is selectable only for 2 CH model ...

Page 15: ...ng stop indicator turns ON when start recording RUN turns ON when stopping recording STOP Digital input indicator Turns ON when setting digital input Recording reservation RE indicator RE turns ON when recording reservation operates Recording paper status indicator turns ON if running out of recording paper during recording RUN Channel CH display part Displays input channel of currently displayed ...

Page 16: ...se digits 3 key Digital memo key key Recording Run Stop key key Used to move parameters to upper group or move digits Paper feeding key STOP printing parameter setting information key RUN PC loader port It is a PC loader port for serial communication to set or monitor parameters by PC Used to connect SCM US USB to Serial converter sold separately ...

Page 17: ...FF Min 100kΩ Non contact Input ON Residual voltage max 1V OFF Leakage current max 0 05mA Outflow current Approx 0 3mA Display accuracy 1 RTD At room temperature 25 5 0 2 F S 1 digit Out of room temperature 0 3 F S 1 digit TC K2 has same accuracy within 200 to 1350 of TC K1 TC Analog Record accuracy 0 5 F S Alarm output CH1 AL1 AL2 CH2 AL1 AL2 Relay output 250VAC 30VDC 3A 1a Alarm output hysteresis...

Page 18: ...ll Type Language Korean English Environ ment Ambient temperature 0 to 50 storage 20 to 60 Ambient humidity 35 to 85 RH storage 35 to 85 RH Approval Weight 2 Approx 700g approx 470g 1 At room temperature 25 5 Thermocouple J 200 T 100 0 2 F S or 2 7 select the higher one 1 digit Thermocouple R S C G 0 T 100 0 2 F S or 5 2 select the higher one 1 digit Thermocouple U T 200 T 100 0 2 F S or 3 5 select...

Page 19: ... C 0 to 2300 32 to 4172 G TT 2 1 TC G 0 to 2300 32 to 4172 L IC 1 TC L1 200 to 900 328 to 1652 0 1 TC L2 199 9 to 900 0 199 9 to 999 9 U CC 1 TC U1 200 to 400 328 to 752 0 1 TC U2 199 9 to 400 0 199 9 to 752 0 Platinel II 1 TC P 0 to 1390 32 to 2534 RTD Cu50Ω 0 1 CU50 199 9 to 200 0 199 9 to 392 0 Cu100Ω 0 1 CU100 199 9 to 200 0 199 9 to 392 0 JPt100Ω 1 JPT1 200 to 600 328 to 1112 0 1 JPT2 199 9 t...

Page 20: ...2 Specifications 20 Copyright Reserved KONICS Co Ltd ...

Page 21: ...s 21 Copyright Reserved KONICS Co Ltd 3 Dimensions unit mm 100 5 14 91 5 96 M3 Screw type terminal 113 5 Panel cut out N Quantity Panel thickness 1 to 4 mm 96 N 1 92 1 0 92 0 5 0 92 0 5 0 Min 110 Parallel mounting ...

Page 22: ...3 Dimensions 22 Copyright Reserved KONICS Co Ltd ...

Page 23: ...inals are for the standard model power terminal CH1 input terminal DI input terminal Dot line terminals are for the option model CH2 input terminal alarm output terminal communication output terminal The DC power model does not have F G When using 2 wire RTD short B and b terminals For current input external 50Ω B class 0 1 high accuracy resistor ...

Page 24: ...4 Connections 24 Copyright Reserved KONICS Co Ltd ...

Page 25: ...nit where ventilation is well In case installing several KRN50 space each other by panel cut out Place where vibration is not severe If there is too much vibration it may cause malfunction such as print error In case of temperature measurement with thermocouple temperature sensor at the place where temperature is fluctuated data error may occur You should warm up this unit over 30 min to acquire a...

Page 26: ...al block Input must be installed as far as possible from power line Terminal wiring must be divided from high voltage and high current power line in order to prevent from electricity failure and self induction noise Also please avoid parallel wiring or same wiring with power line It may be effective if dividing by means of pipe or duct or using shield cable or twisted pair cable Same compensating ...

Page 27: ...is able to output time date alarm information error message parameter list and so on Display Measured value is indicated by number on LCD display and time alarm error information etc are displayed Communication function It is able to use RS 485 communication and communication protocol uses Modbus RTU and communicates with the upper devices PC or PLC Data backup function Record Back up It is simila...

Page 28: ...6 Functions 28 Copyright Reserved KONICS Co Ltd ...

Page 29: ...d backup data recording mode This mode is to record the saved data by means of data logger function It is also unnecessary for operation stop 7 2 Operation procedure It is the introduction when this recorder operates initially Ready to record Put chart paper in paper holder after cutting the glued part chart paper is installed in recorder as factory default If necessary change time and date they a...

Page 30: ...t side shows the rest of the setting menu ii If moving from the upper setting menu to the next step menu please use 3 key iii If pressing key it is able to move from the current menu to the lower setting menu For moving from the lower setting menu to the upper setting menu please use key iv If moving from the lower setting menu to the next step menu please use 3 key v If entering into the setting ...

Page 31: ...ry setting value is saved and moving to the next lower setting menu ii The lower setting menu is able to be selected by 3 key and if pressing key moving to the upper setting menu iii If pressing key for 3 sec when the cursor is placed at the lower setting menu it is able to move to the setting mode from general operation mode and operate according to setting value ...

Page 32: ...it is saved and moved to the setting menu 4 Insert setting value After moving the cursor to the position user wants to the left by key it is able to change the value by 3 key Especially the fourth position of number is able to change to either number or sign If pressing key at the status of wrong value and save it when changing setting value it indicates Error code as above ...

Page 33: ... Rec Period Font CH1 Lo Range CH1 Lo Scale CH1 Dp Unit CH1 Hi Range CH1 Hi Scale CH1 In Bias CH1 Sc point CH1 Tag Name CH2 Lo Range CH2 Lo Scale CH2 Dp Unit CH2 Hi Range CH2 Hi Scale CH2 In Bias CH2 Sc point CH2 Tag Name For 2 CH model TC or RTD input type Analog input type key key key key key key key key key Parameter setup model All models Parameter setup model All models Parameter setup model K...

Page 34: ...7 General operation and parameter setting menu 34 Copyright Reserved KONICS Co Ltd ...

Page 35: ...ing range 00y01m01d to 99y12m31d unit Day is set automatically 3 Current time Time Setting range 00 00 00 to 23 59 59 Setting date and time i If pressing key for 3 sec it enters into the upper setting menu ii If pressing key after selecting Date Time Setup by 3 key it enters into the lower setting menu from the upper setting menu iii If pressing key after moving the cursor to Date by 3 key it ente...

Page 36: ...however if not it must be Off If the mode of any channel is Off this channel is not able to indicate channel indication and PV on display and to record anything If the mode of any channel is Off relevant input setting parameter of this channel is not indicated automatically Setting range On using recording Off not using recording Factory default Off unit Regarding saved data by record backup if CH...

Page 37: ...rily is able to select each input type for CH1 and CH2 separately E g set as CH1 DPT1 CH2 TC K1 Setting range temperature range of each input type and sensor Factory default TC K1 unit If changing input type saved data by record backup is removed and it starts saving the data from the modified current time Therefore please be careful for setup ...

Page 38: ... analog input type this parameter CH Temp Unit is not indicated When temp unit conversion relevant bias value is initialized and parameter setting value excluding bias value holds previous setting value Setting range Factory default unit 4 Graph low limit scale value CH Lo Graph This function is to set low limit scale value of graph within input range of each input type Setting range Min range by ...

Page 39: ...ctory default 1350 unit Digit When High Low graph setup with wrong value and pressing key for save error message is indicated as above Refer to Over Range Hi Lo of 8 2 4 Display information function 1 Error Then if pressing key again it returns to previous value Graph high low scale value setting In case of temp sensor input TC RTD this function is to set graph scale value for record to chart pape...

Page 40: ...e In case of the recording start position of digital memo even though graph high low limit scale range is exceeded actual value is recorded within high low limit input range 6 Low limit input range CH Lo Range This function is to assign and limit the actual using low limit input value within input range Setting range Min input range to high limit input value CH Hi Range F S 5 Factory default Min i...

Page 41: ... save error message is indicated as above Analog input scale setting In case of analog input type Voltage Current input user is able to assign input range High Low limit input value and this function is to support proper indication for user environment through scale value for assigned input range High Low limit input value setup Graph scale of chart paper is applied one to one according to setting...

Page 42: ...nput type this function is to set high limit scale value for assigned high limit input value If assigned high low limit input value is 0V to 5V and user needs 100 to 100 value user must set low limit scale value 100 high limit scale value 100 When input value is 0V PV displays 100 If input value is 5V PV displays 100 Setting range Within F S range 1999 to 9999 199 9 to 999 9 19 99 to 99 99 1 999 t...

Page 43: ...lue for analog input is changed when input type CH In Type setup previous record backup data is removed Backup data time initialization and start saving the data from the current modified time Therefore please be careful for setup 11 Record display unit CH Dp Unit This function is to set the unit for record and display If only input type parameter CH In Type is analog input it is indicated In case...

Page 44: ...arameter psi kgf m h mmHg mmH2O using with adding user unit OFF Factory default unit When record backup if using total 10 user font units us0 to us9 recent user font unit is dicated For example if previous us0 was and changed to recently when data output by record backup previous data with unit also records with recent unit Therefore one user font unit us0 to us9 should be used for several units ...

Page 45: ... measured and if measured accidental error value is not precise it will be larger Each channel is able to set for input bias CH1 In Bias CH2 In Bias In case of TC or RTD if temp unit conversion or input type change correction value will be initialized to 0 If actual temperature is 80 but display indicates 78 input correction value CH Input Bias should be set 2 for indicating 80 Setting range 999 t...

Page 46: ...ame for each channel when recording However LCD display channel name is fixed to CH1 CH2 It is to set for each digit 4 digit in setting range and selected English is always capital letters Setting range Blank 1 0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z Factory default CH unit ...

Page 47: ... object for control is much higher or lower When each channel alarm output operation relevant alarm indicating lamp CH1 AL1 AL2 CH2 AL1 AL2 on display is lighting During recording when alarm operation current time PV alarm information AL HI AL LO SBA B P End P print to chart paper HI LO of AL1 AL2 in printed AL1 AL2 for classify AL1 and AL2 separately ...

Page 48: ...L1 L alarm is ON Recording mark AL1 AL2 SBA Sensor Break Alarm When input is not connected or disconnected during recording alarm output is ON You can check the input break using external alarm output contact by buzzer or others Recording mark AL1 B AL2 B P End Paper end alarm If running out of recording paper during recording alarm output is ON measured value is saved at system memory When record...

Page 49: ...he second alarm condition alarm latch operates Factory default None unit 1 If user needs to cancel alarm latch function when current PV is out of the alarm range and when returning from sensor break alarm SBA or paper end alarm P End please press 3 keys for over 3 sec When PV is higher than alarm value after alarm operation on the status of alarm latch if alarm mode changes to Standby sequence fun...

Page 50: ... operation mode CH AL Type relevant channel parameter CH AL Lo CH AL Hi is interlocked and displayed When selecting high limit alarm mode PV Hi only CH AL High is displayed When selecting low limit alarm mode PV Lo only CH AL Low is displayed If input type setup CH In Type is changed CH AL High or CH AL Low value is changed to input range of input type setup CH In Type automatically If input type ...

Page 51: ...o Ltd 7 Alarm output hysteresis CH Alarm Hys As alarm output hysteresis hysteresis sets the interval between ON and OFF of alarm output Setting range 001 to 999 decimal point is placed same as input decimal point Factory default 001 unit Digit ...

Page 52: ...wever if alarm output starts out of relevant alarm condition range setting PV of the point of time of power on the first alarm output starts operating same as general alarm Refer to 2 Application condition When power on or changing alarm value alarm output operation mode alarm option Alarm latch function Once alarm output is on it will hold on even out of alarm output range Alarm output hold Cance...

Page 53: ...L High Low automatically is initialized to maximum value and minimum value When changing alarm output option alarm setting value holds as previously Thermocouple Input For setting mode of channel 1 Input type TC K1 200 to 1350 Hi Lo graph range 0 to 1000 and channel 2 Record off For alarm function of channel 1 AL1 low limit 100 Alarm option None AL2 high limit 600 Alarm option None For record mode...

Page 54: ...menu by pressing key If pressing key after moving to the lower menu of CH2 record it enters into the setting category then set to Off and press key to get out of this menu Also after moving to the lower menu of CH1 input type and entering into the setting category set to TC K1 and press key to get out of this menu iii Input High Low graph range setup Set CH1 Lo Graph 0 CH1 Hi Graph 1000 at the low...

Page 55: ...ressing key set AL1 Opt None AL1 High 600 vi After setting AL2 type PV Lo and saving it by pressing key set AL2 Opt None AL2 Low 100 vii After moving to the upper menu from the lower menu of alarm setup and selecting record setup press key to entering into the lower menu viii Set Record mode Graph Rec speed 960mm h Memo period 1min ix After completing all setup if pressing key for 3 sec it moves t...

Page 56: ...scale 0 0 to 100 0 Dp unit ppm and channel 1 Record off For alarm function of channel 2 AL1 High limit 70 0ppm Alarm option None AL2 Low limit 20 0ppm Alarm option None For record mode Record mode graph mode Recording speed 960mm h Memo period 1min Record mode setup is same as Example 1 If setup is as above recording will be as follows ...

Page 57: ...g key If pressing key after moving to the lower menu of CH1 record it enters into the setting category then set to Off and press key to get out of this menu Also after moving to the lower menu of CH2 input type and entering into the setting category set to 4 to 20mA and set CH2 Dp unit to ppm and press key to get out of this menu iii Input High Low scale setup Set CH2 Lo Scale 000 0 CH2 Hi Scale 1...

Page 58: ...om the lower menu of input type setup and selecting alarm setup press key to entering into the lower menu v After setting CH2 AL1 type PV Hi and saving it by pressing key set AL1 Opt None AL1 High 20 0 vi After setting CH2 AL2 type PV Lo and saving it by pressing key set AL2 Opt None AL2 Low 70 0 ...

Page 59: ...ording Run or Stop at the basis of current recording state If DI 1 Digital input 1 parameter sets Run it operates Recording Short Open by means of external DI 1 terminals No 16 18 If using DI 1 front key for recording run stop does not operate When RUN lamp is lightening When STOP lamp is lightening Once power ON recording is able to Run or Stop automatically when re power ON after electricity fai...

Page 60: ...tate chart paper is manually able to feed as fixed length Approx 10mm If pressing key continuously chart paper is able to feed as fixed length every 3 sec The latest record is placed behind of paper cutter at STOP state therefore cut the chart paper after manual paper feeding in order to check the latest record ...

Page 61: ... Memo Period setup 5 Recording speed Rec Speed This function is to set recording speed and it is able to set by feeding length per hour If only record mode Record Mode is graph mode Graph it is indicated Setting range 10 30 60 120 240 480 960 Factory default 10 unit mm h 6 Digital memo period Memo Period Recording period for recording current time hh mm ss and PV for channel to chart paper is set ...

Page 62: ...O O O O O O O If digital memo period is 60 min and recording start time is 09 20 the first digital memo time recording is not 10 20 but 10 00 at the basis of regular time Recording time 10 00 11 00 12 00 13 00 Until recording end If digital memo period is 10 min and recording start time is 09 23 the first digital memo time recording is not 09 33 but 09 30 at the basis of regular time Recording tim...

Page 63: ...eter setting value user is able to misunderstand therefore please be aware of this function when using it Regarding saved data by record backup if record mode setup function Rec mode Rec period Alarm speed is changed previous record backup data is removed Backup data time initialization and start saving the data from the current modified time Therefore please be careful for setup Recording speed 2...

Page 64: ...ing range 00m05s to 99m59s Factory default 01m00s unit min sec 10 Recording language Font This recorder is able to record in Korean and English and current date high low limit scale value and parameter list are recorded by setting language Setting range Korea English Factory default Korea unit Korea 현재시간 2009년03월19일 12시30분00초 English DATE 03 19 2009 12 30 00 11 Reservation recording After user set...

Page 65: ...rd setup recording RUN STOP function by 3 key 3sec DI 1 input terminal communication does not operate however if not recording RUN STOP function by 3 key 3sec DI 1 input terminal communication is able to operate Start time must not be same as stop time and if setting it Time Set message will be indicated on display Record Setup Record Mode Digital Record Speed 5sec Reservation Setup Start Time 12 ...

Page 66: ...8 Recording 66 Copyright Reserved KONICS Co Ltd ...

Page 67: ...cord DI 1 function is not able to operate and after reservation record stop this function is able to operate 15 DI 2 function Digital Input 2 This function is able to operate recording start by means of external digital input terminals No 17 18 If this mode sets Memo current time hh mm ss and PV for relevant channel are recorded at the time of inputting one signal to external digital input termina...

Page 68: ...nd Stop If setting reservation record the time of power on is reservation record start time but if not record stop will hold Setting range Run Stop Factory default Run unit 17 Printing the setting list when record start RUN On State This function is to set printing the setting list when record start simultaneously It is divided into List and Off Setting range List Off Factory default Off unit ...

Page 69: ...emo function again this function must be off and on by 3 key again Digital memo function is able to operate by means of external DI 2 input terminal No 17 18 If input has error HHHH LLLL BURN at the time of operating digital memo each relevant channel records HHHH LLLL BURN 19 Paper end If chart paper is exhausted during record recording operation will be stopped and paper end lamp P ED will light...

Page 70: ...Digital mode or Graph mode Therefore user is not able to change record setup of setting mode on P End state All Recording Printing all data saved in memory of from the time of paper end to current time Part Recording Printing some parts of data saved in memory of from the time of paper end after user sets recording printing time range Start time Stop time Cancel Not recording printing data in memo...

Page 71: ...8 Recording 71 Copyright Reserved KONICS Co Ltd ...

Page 72: ...re if user would like to print backup data after long time standby printing it after setting to present time for stop time or printing with indicating it on display after cancel and entering into the setting mode again as following figure As data saving capacity of this recorder is 18138 ea saving period is mentioned as next page according to recording mode Backup data record applies graph and dig...

Page 73: ...rd backup reading PV function is only able to be used among communication functions When changing setup as following previous backup data is removed and it starts saving since this time Therefore please be careful when setup influenced to record backup data Record mode setup When changing Rec mode Rec period or Time Alarm speed setting Input type setup CH1 or 2 Record CH1 or 2 In type When analog ...

Page 74: ...240mm h 2 sec Approx 6 hours Approx 10 hours 120mm h 4 sec Approx 12 hours Approx 20 hours 60mm h 8 sec Approx 24 hours Approx 40 hours 30mm h 16 sec Approx 48 hours Approx 80 hours 10mm h 48 sec Approx 6 days 153 hour Approx 10 days 241 hours 5 sec 5 sec 11542 5 sec Approx 16 hours 18138 5 sec Approx 25 hours 1 min 60 sec Approx 8 days Approx 12 days to to to to 60 min 3600 sec Approx 480 days Ap...

Page 75: ...8 Recording 75 Copyright Reserved KONICS Co Ltd ...

Page 76: ...ameter During record if pressing key for 3 sec after recording setting information of each menu recording PV again Record parameter Tag name Input Unit Range Scale Alarm mode Alarm setting value Communication function When starting record parameter setting information is able to be recorded according to printing the setting list parameter ...

Page 77: ...8 Recording 77 Copyright Reserved KONICS Co Ltd ...

Page 78: ...C RTD input After setting HI LO Graph value within sensor temperature range if PV is out of HI LO Graph value it will indicate PV only on LCD display and it will record PV with either HH or LL simultaneously as the c of following figure After setting HI LO Graph value same as sensor temperature range if PV is out of temperature range it will indicate and record HHHH or LLLL as the d of following f...

Page 79: ...eration as above above message will be indicated by relevant channel turn HH or LL message will be indicated when alarm does not operate 2 Display indicating mode In case of 2 channel model display mode is divided by normal mode 2 channel mode or 1 channel autorotation and manual mode 3 Display normal mode Display Mode 2 Channel mode 2CH As indicating input value PV of 2 channel CH1 and CH2 simult...

Page 80: ...t will be converted to normal mode When applying power or when returning after an electricity failure it will be indicated by mode setup 2CH or 1CH on display mode parameter automatically 5 LCD backlight This function is to set LCD backlight type and there are always lightening type and temporary lighting type Always lightening type Always It will lighten up during power on Temporary lightening ty...

Page 81: ...tup Record Setup Option Setup RS485 Setup Date Time Setup Record Backup_Data Environment Setup Enable to check set Enable to check disable to set Disable to check Even though selecting Loc1 Loc2 Loc3 Setting Lock parameters will be always indicated and it will be changed Factory default Off unit Even though setting parameter lock function up parameter will be initialized by parameter initializing ...

Page 82: ... to initialize all parameters in memory to factory default value If select setting value to Yes by 3 or key and press key all parameters will be initialized to factory default value and returned to operating mode If pressing key for 5 sec simultaneously it will operate Setting range Yes No Factory default No unit ...

Page 83: ...cating by front communication port In case of phone jack communication there may be reorganization error due to external noise or environment during connecting PC If error occurs re connect the device Use the phone jack only for setting Interface Comm protocol Modbus RTU Connection type RS485 Application standard Compliance with EIA RS485 Max connections 31units address 01 to 99 Comm synchronous m...

Page 84: ...ed to use SCM US48I USB to RS485 converter SCM 38I RS232C to RS485 converter SCM US USB to Serial converter of Autonics If using the converter not insulated FG and SG for long distance communication it may cause KRN50 damage or communication error It is recommended to use DAQMaster program for monitoring You can download DAQMaster program and communication manual at our website www konics com For ...

Page 85: ... CH2 AL1 Type 2 40110 CH2 alarm output1 operation 0 Off 1 PV Hi 2 PV Lo 3 SBA 4 P End PV Hi CH2 AL1 Opt 2 40111 CH2 alarm output1 option 0 None 1 Latch 2 StBy 3 La St None CH2 AL1 Low 1 2 40112 CH2 alarm output1 low limit SV Display range by input type Digit 200 CH2 AL1 High 1 2 40113 CH2 alarm output1 high limit SV 1350 CH2 AL2 Type 2 40114 CH2 alarm output2 operation 0 Off 1 PV Hi 2 PV Lo 3 SBA4...

Page 86: ...TC G 14 TC L1 15 TC L2 16 TC U1 17 TC U2 18 TC P 19 CU50 20 CU100 21 JPT1 22 JPT2 23 DPT50 24 DPT1 25 DPT2 26 A mV1 27 A mV2 28 A V1 29 A V2 30 A mA1 31 A mA2 TC K1 CH1 Temp Unit 1 40303 CH 1 temp unit 0 1 CH1 Lo Graph 1 40304 CH 1 graph low limit scale value Refer to the 8 2 1 4 5 Digit 200 CH1 Hi Graph 1 40305 CH 1 graph high limit scale value 1350 CH1 Lo Range 2 40306 CH 1 low limit input value...

Page 87: ...e Decimal Point 2 40329 CH 1 scale dot position 0 0 1 0 0 2 0 00 3 0 000 0 0 CH2 DP Unit 3 40330 CH 2 record display unit Same as addr 40311 CH2 In Bias 3 40331 CH 2 input correction 999 to 999 Digit 000 CH2 Tag Name 3 40332 to 40333 CH 2 channel name Same as addr 40313 to 40314 CH 2 1 Displays only when input type In Type is temperature sensor 2 Displays only when input type In Type is analog vol...

Page 88: ...00 6 57600 bps 9600bps Parity bit 40003 Parity bit 0 None 1 Odd 2 Even None Stop Bit 40004 Stop bit 0 1 1 2 Bit 2 Response Time 40005 Response time 50 to 990 msec 50 Com Write 40006 Communication write enable disable 0 Enable 1 Disable Enable 7 Date Time setup group Date Time Setup Parameter Addr Description Setting range Unit Default Date 40052 Year 00 to 99 40053 Month 00 to 12 40054 Day 00 to 3...

Page 89: ... 1 status DI1 Status 0 OFF 1 ON operates only for ON 0 10302 Digital input 2 status DI2 Status 0 OFF 1 ON operates only for ON 0 30001 CH1 display value PV 30002 CH1 BIT position Unit Unit group Status Display value dot position Unit 15 to 10 2 2 00 NONE 00 0 Unit group 9 to 4 01 HHHH 01 0 0 Status 3 to 2 10 LLLL 10 0 00 Display value dot 1 to 0 11 BURN 11 0 000 30003 CH2 display value PV 30004 CH...

Page 90: ...t 1 3 User 1 16 16 size 42033 to 48 User unit font 2 3 User 2 16 16 size 42049 to 64 User unit font 3 3 User 3 16 16 size 42065 to 80 User unit font 4 3 User 4 16 16 size 42081 to 96 User unit font 5 3 User 5 16 16 size 42097 to 112 User unit font 6 3 User 6 16 16 size 420113 to 128 User unit font 7 3 User 7 16 16 size 420129 to 144 User unit font 8 3 User 8 16 16 size 420145 to 160 User unit font...

Page 91: ...s thermometers panel meters pulse meters counters and KONICS recorders and indicators etc DAQMaster provides GUI control for easy and convenient management of parameters and multiple device data monitoring You can download DAQMaster and the user manual of DAQMaster at KONICS homepage www konics com This user manual describes only KRN50 functions of DAQMaster For more informatio about DAQMaster pro...

Page 92: ...as project files Opens project files to load the saved settings Provides a project list for simple and easy project file management Monitoring Data Log When monitoring data log files can be saved as either DAQMaster data files ddf or CSV csv files Open files saved in csv format directly from Microsoft Excel Define log data file naming saving rules and destination folders to make file management co...

Page 93: ...tures for KRN50 while in communication with DAQMaster 1 Accessing Record Backup Data To get the recorded data click button located on the right of Record Backup in the Property window To read memory information the device status must be Connected and not Run There are also cases in which you cannot read from memory depending on KRN50 parameter setting ...

Page 94: ...ps below i Run Memory Information in KRN50 Record Memory Data window It gets the information from currently saved memory ii Set Uploaded Data Size iii Run Upload Data iv You can cancel the operation while data is being uploaded When data reading is complete OK button is enabled v If you click OK recorded data will be shown in two screens the Grid and the Graph ...

Page 95: ...u to download images to KRN50 and change logo unit and boot images You can also reset images back to the original status This is also a self protocol so cannot download images during Run 1 Download logo You can change the company logo image on contents that are printed on recording paper Logo image should be 384 80 pixel of bitmap file ...

Page 96: ...ement program DAQMaster 96 Copyright Reserved KONICS Co Ltd 2 Download Units There are 0 to 9 user units The download procedure is select a unit list select a destination to save double click a unit image to add the image download ...

Page 97: ...97 Copyright Reserved KONICS Co Ltd 3 Download boot images The boot image logo image appears on LCD upon initial power supply to KRN50 You can change booting logo image which displays when KRN50 is power ON The image should be 128 32 pixel of bitmap file ...

Page 98: ... 820 2411 7 FAX 82 32 811 9700 Sales Dept 37 Venture ro 36beon gil Yeonsu gu Incheon South Korea 22011 TEL 82 32 820 2300 FAX 82 32 813 9981 E mail konics4 konics com A S center 37 Venture ro 36beon gil Yeonsu gu Incheon South Korea 22011 TEL 82 32 820 2356 7 FAX 82 32 813 9979 Recorders Indicators Converters Controllers Thyristor Power Controllers Temperature Sensors Pressure Transmitters Tempera...

Reviews: