USER MANUAL 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for krn100

Page 1: ... Copyright Reserved KONICS Co Ltd i USER MANUAL ...

Page 2: ...ii Copyright Reserved KONICS Co Ltd ...

Page 3: ...electing KONICS products Please familiarize yourself with the information contained in the Safety Precautions section before using this product This user manual contains information about the product and its proper use and should be kept in a place where it will be easy to access ...

Page 4: ...any guarantee concerning matters beyond the scope of this manual This manual may not be edited or reproduced in either part or whole without permission A user manual is provided as part of the product package Visit our home page www konics com to download a copy The manual s content may vary depending on changes to the product s software and other unforeseen developments within KONICS and is subje...

Page 5: ... Symbol Description Supplementary information for a particular feature Failure to follow instructions can result in serious injury or death Failure to follow instructions can lead to a minor injury or product damage An example of the concerned feature s use 1 Annotation mark ...

Page 6: ...r is ON It may cause electric shock Check input power specification and check power terminal number when wiring power cable It may cause a fire or damage by a fire Lithium battery is used in this product do not disassemble or burn up this unit It may cause an explosion Do not touch the product or connect terminal within 30 sec after turn off the power It may cause electric shock F G terminal shoul...

Page 7: ...nded to use insulation transformer and noise filter power in case of too much noise from power Attach noise filter on the grounded panel etc Wire between noise filter output part and power terminal of the product should be short as possible It may cause damage to the product malfunction by surge etc Before connecting temperature sensor thermocouple RTD and analog voltage current input set jumper p...

Page 8: ... side 19 1 4 3 Inside 20 1 4 4 Paper cassette 20 2 Specification 21 2 1 KRN100 21 2 2 I O card 23 2 3 Input specification and measuring range 25 3 Dimensions 27 4 Connection 29 4 1 KRN100 29 4 2 I O card 30 5 Installation 33 5 1 Installation place 33 5 2 Installation 34 5 2 1 Bracket mounting 34 5 2 2 Additional I O card connection 35 5 3 USB to Serial driver 36 5 3 1 Driver installation 36 5 3 2 ...

Page 9: ...put Bias Error correction 69 8 1 15 Span Gradient adjustment 70 8 1 16 Record Method Data storage method 71 8 1 17 Filter Type Input digital filter 71 8 1 18 Filter Counter The number of digital filter 72 8 1 19 Burnout Action Display setting for break 73 8 2 ALARM SETUP Alarm setting 74 8 2 1 Select UI Card Select universal card input 75 8 2 2 Alarm Set Copy Copy alarm parameter 75 8 2 3 Alarm Ty...

Page 10: ...106 8 5 9 Listing Language Language for list output 107 8 5 10 Alarm Speed Alarm record speed 108 8 5 11 Power On Status Record status when power ON 108 8 5 12 Run Status List printing at start recording 109 8 5 13 List Out Option List record option 110 8 5 14 Zone Dot Line Distance Dot line for zone division 111 8 5 15 CH Print Distance Record interval for each channel graph 111 8 5 16 Start Line...

Page 11: ...de 130 8 9 RECORD BACKUP_ SETUP Backup data record setting 132 8 9 1 Record Backup Backup data record 133 8 9 2 Backup Data List Backup data list 133 8 9 3 Start Date and Time Start time for data storage 134 8 9 4 End Date and Time End time for data storage 134 8 9 5 Backup Print Mode Backup data record mode 134 8 9 6 Select Print Mode Backup data recording mode setting 135 9 DAQMaster 137 9 1 Ove...

Page 12: ...Table of Contents xii Copyright Reserved KONICS Co Ltd ...

Page 13: ...rse and graphic user interface GUI with graphic display for easire and convenient use Combines functions of paper recorder and paperless recorder Enables to print the saved data of inner memory when run out of recording paper Data logger function Inner data backup with an USB memory High legibility and setting convenient by graph LCD 25ms high sampling 240mm h high speed record function 100mm pape...

Page 14: ...t Before using KRN100 check the component If any component is left out or damaged contact our company or seller KONICS service center 82 32 820 2343 1 2 2 Accessory 1 I O card 2 Communication converter Appearances of SCM 38I RS232C to RS485 converter and SCM US48I USB to RS485 converter are same ...

Page 15: ...2 X 5ea 12 12 channel KRN UI2 X 6ea Digital input 0 None 1 6ea KRN DI6 X 1ea 2 12ea KRN DI6 X 2ea Alarm TR output 0 None 1 6ea KRN AT6 X 1ea 2 12ea KRN AT6 X 2ea Alarm Relay output 0 None 1 4ea KRN AR4 X 1ea 2 8ea KRN AR4 X 2ea 3 12ea KRN AR4 X 3ea Transmitter power output 0 None 1 3ea KRN 24V3 X1ea 2 6ea KRN 24V3 X 2ea 3 9ea KRN 24V3 X 3ea 4 12ea KRN 24V3 X 4ea Communication output 0 None 1 RS485...

Page 16: ...tput 3 channel 4ea Communication output card KRN COM RS485 USB Ethernet communication channel 1ea C 1 Digital input card alarm output card transmitter power output card are connectable up to 4ea as mixed 3 Example of ordering To use universal input 10 channel digital input 4 channel alarm relay output 5 channel and RS485 communication output it is ordered as KRN100 10102 01 0S and connected I O ca...

Page 17: ...e moves to the center Use this to replace ink cartridge Using this key for going out from parameter setting group or setting manual channel switch mode It also executes to release auto channel switch mode and printer list output 3 sec function Using this key for moving parameter in setting mode setting manual channel switch mode and forced alarm reset 3 sec Using this key for moving parameter in s...

Page 18: ...ICS Co Ltd Function key Use this key to enter virtual keyboard in parameter setting Press key and Function key appears on lower screen as below figure Press or key as below Function key it operates the appropriate Function key s operation ...

Page 19: ...by combining digital input card alarm output card and transmitter power output card as below combination example KRN DI6 1ea KRN AR4 1ea KRN AT6 1ea KRN 24V3 1ea Total 4ea KRN DI6 2ea KRN AR4 1ea KRN AT6 1ea Total 4ea KRN AT6 1ea KRN 24V3 3ea Total 4ea Slot 1 to 6 for connecting universal input card KRN UI2 Power connecting part 100 240VAC 50 60Hz Above back side image is connected every otuput ca...

Page 20: ...oved from KRN100 Remove the recording paper cassette for recording paper replacement ink cartridge replacement 1 4 4 Paper cassette Recording paper holder Movement holder of recording paper when recording Recording paper storage part Storage part for recorded recording paper Front cover of recording paper storage Open recording paper guide for recording paper replacement New recording paper storag...

Page 21: ... period 1 to 3 600 sec Storage interval time to inner log file is 1 sec Inner memory 512MByte USB memory User purchased recognizes max 32GByte enables to use cable up to 1 5m Function Record color Record zone Input special function Input digital filter Reservation set Summer time Delay alarm Record speed change Data storage Backup data record etc Dielectric 2 500VAC 50 60Hz for 1 min power termina...

Page 22: ...tion category II Environ ment 2 Temperat ure 0 to 50 Storage 20 to 60 without ink cartridge Humidity 35 to 85 RH Storage 35 to 85 RH If using this unit at place with high humidity it may cause paper jam Please do not use this unit at place with high humidity Approval Unit weight Approx 1 7 to 2 0kg 1 For more information of universal input please refer to 2 2 I O card 2 Environment resistance is r...

Page 23: ... DI6 Noncontact input ON Max 1V of residual voltage OFF Max 0 1 leakage current Contact input ON Max 1kΩ OFF Min 100kΩ Short Approx 4 Alarm output card KRN AR4 Alarm relay output Capacity 250VAC 3A 30VDC 3A 1 Form A resistance load Life Mechanical Min 50 000 000 operations Electrical Min 100 000 operations 3A 250V AC 3A 30V DC KRN AT6 Alarm TR output NPN Open Collector 12 24VDC 30 Max Transmitt er...

Page 24: ... CU50 200 T 200 1 0 DPT50 200 T 500 1 5 3 RS485 Ethernet communication output are not available at the same time 4 USB Device is available only for parameter setting 5 It is recommended to use shield cable to decrease noise when supplying power for transmitter If connecting or disconnecting input output card when power is ON it may cause malfunction To connect or disconnect input output card you m...

Page 25: ...to 1350 0 32 0 to 2462 0 273 2 to 1623 2 Resistance temperature detector RTD CU50Ω CU50 200 0 to 200 0 328 0 to 392 0 73 2 to 473 2 CU100Ω CU100 200 0 to 200 0 328 0 to 392 0 73 2 to 473 2 JPT100Ω JPT100 200 0 to 600 0 328 0 to 1112 0 73 2 to 873 2 DPT50Ω DPT50 200 0 to 600 0 328 0 to 1112 0 73 2 to 873 2 DPT100Ω DPT100 200 0 to 850 0 328 0 to 1562 0 73 2 to 1123 2 Analog Voltage 60 00 to 60 00 60...

Page 26: ...2 Specification 26 Copyright Reserved KONICS Co Ltd ...

Page 27: ...3 Dimensions Copyright Reserved KONICS Co Ltd 27 3 Dimensions 1 KRN100 Back side dimension is with installed I O cards to every slot 2 Panel cut out Use panel which is 2 to 8mm thickness ...

Page 28: ...3 Dimensions 28 Copyright Reserved KONICS Co Ltd ...

Page 29: ...is figure is back side of KRN100 04000 00 0S model Slot Description 1 to 6 Connects universal input card KRN UI2 7 to 10 Connect digital input card KRN DI6 alarm output card KRN AR4 KRN AT6 and transmitter power output card KRN 24V3 C Connects communication output card KRN COM ...

Page 30: ...ed KONICS Co Ltd 4 2 I O card Universal input card KRN UI2 Digital input card KRN DI6 Alarm output card KRN AR4 Relay output Alarm output card KRN AT6 TR output Transmitter power output card KRN 24V3 Communication output card KRN COM ...

Page 31: ...ing on input specification set the jumper pin of universal input card KRN UI2 channel 1 channel 2 as below figure Jumper pin Input specification Input break alarm 0 to 20 4 to 20 Enables only 4 to 20 TC RTD 60mV 200mV Enables 2V 1 to 5V 5V 1 to 10V Disables ...

Page 32: ...4 Connection 32 Copyright Reserved KONICS Co Ltd ...

Page 33: ...RN100 space each other by panel cut out Place where vibration is not severe If there is too much vibration it may cause malfunction such as print error For more information about vibration please refer to 2 Specification In case of temperature measurement with thermocouple temperature sensor at the place where temperature is fluctuated data error may occur You should warm up this unit over 30 min ...

Page 34: ... Installation 5 2 1 Bracket mounting 1st Install KRN100 on the processed panel as panel cut out diagram Mount fixing brackets on upper lower parts 2nd Tighten fixing brackets on upper lower parts to fix on the panel with phillips screwdriver Torque 0 4N m ...

Page 35: ...2 2 Additional I O card connection 1st To connect I O card additionally turn OFF the power of KRN100 Remove the proper slot cover to insert I O card with flat head screwdriver or knife 2nd Insert I O card to the proper slot and turn ON the power of KRN100 ...

Page 36: ...M is connected Supporing OS for USB to Serial driver is Windows XP 32 64bit Windows 7 32 64bit 5 3 1 Driver installation 1st Visit our homepage www konics com and downlaod KRN100_USB_Serial_Drivers Unzip this file to the desired folder 2nd Connect KRN100 USB port of communication output card KRN COM and PC USB port with USB cable A Mini 5P 1 5m 3rd Found New Hardware Wizard appears Select Install ...

Page 37: ...heck Include this locationin the search Click Browse and select the folder which has KRN100_USB_Serial_Drivers and click OK 5th If hardware compatibility message appears click Continue Anyway and it processes the next 6th At Completing the Found New Hardware Wizard click Finish and driver installation is complete ...

Page 38: ...hecking driver To check the driver right click My computer and select Properties on pop up menu System Properties dialog appears Select Hardware tab and click Device Manager Device Manager dialog appears Check Ports COM LPT KRN100 USB To Serial Converter COMx ...

Page 39: ...nner system memory booting is finished and KRN100 operates normally Screen for progressing initial setting Screen for checking error of inner system memory If there are lots of log data files booting time may take a long time Delete log data file For more information refer to 8 7 4 Memory Clear Delete memory Screen for error of inner system memory Above this figure if there is error of inner syste...

Page 40: ... start icon Marks if for starting recording measuring value of recordable channels Record stop icon Stops recording measuring value List record icon Flashes during list recording Reservation record icon Flashes during reservation recording FEED icon Flashes during feeding recording paper Backup data print icon Flashes during backup data printing 2 Digital mode icon Marks it for digital record mode...

Page 41: ...rt record signal of digital input DI is input Digital input DI stop record icon Marks it when stop record signal of digital input DI is input Digital input DI LIST output icon Marks it when LIST output signal of digital input DI is input Digital input DI record speed icon Marks it when changing record speed signal of digital input DI is input 6 Unlock icon Marks it for unlock status User general u...

Page 42: ... KONICS Co Ltd Backup data recording function by P END is same as RECORD BACKUP Backup Data List cannot be changed Starting print by P END Backup it prints the data but backup data file date file name and backup record starting line ...

Page 43: ...ers special characters by and keys No Front key Description 1 Press key once and English capital letters English small letters and special character virtual keyboard is switching 1 When pressing and holding key screen of Function key is displayed 2 2 Moves digit to select character of virtual keyboard 3 Enters set characters 1 Enterable characters are as below English capital letters English small...

Page 44: ...t key for 3 sec and it enters parameter setting group When entering parameter setting group setable parameter setting groups are displayed At parameter setting group press key to enter parameter setting For more information of parameter detail setup please refer to 8 Parameter detail setup ...

Page 45: ...7 Operation Copyright Reserved KONICS Co Ltd 45 7 Operation ...

Page 46: ...ays input measuring value of each channel as trend graph left and digital number right 4 channels are displayed per one screen To switch channel please refer to 7 1 2 Channel switch 2 Bar graph Displays input measuring value of each channel as bar graph left and digital number right You can easily check present measuring value within the set display range as level 4 channels are displayed per one ...

Page 47: ...s divided as 1 channel digital number 8 channels digital number 12 channels digital number Display of 1 channel digital number Displays 1 channel per 1 screen with big font size It has high visibility Display of 8 channels digital number Displays 8 channels per 1 screen Display of 12 channels digital number Displays 12 channels all channels per 1 screen ...

Page 48: ...ing value of all input channels by switching channel of display types You can set channel switch mode as auto channel switch or manual channel switch 7 1 2 1 Auto channel switch A screen displays 4 channels and automatically switches other screens by 3 sec period 1 Trend graph 2 Bar graph ...

Page 49: ...nual channel switch function 7 1 2 2 Auto channel switch mode Manual channel switch mode 1st When supplying re supplying power to KRN100 it is display currently display and auto channel switch mode 2nd If you want to change manual channel switch mode press key or key 3rd You can switch select the to be displayed channel by pressing key or key 4th In manual channel switch mode press key to change t...

Page 50: ... or stop state and it records the set information of each menu For more information please refer to 8 5 13 List Out Option List record option Even if you print the parameter set information with max record speed 240mm h it takes a lot of time It takes approx 40 minutes for 12 channels Be sure that for printing the list 3 Manual feed FEED In record STOP state press front key for over 3 sec record s...

Page 51: ...er please refer to 8 Parameter detail setup To enter parameter setting group Press key for 3 sec To move among setting group To move the setting To move upper parameter after setting Press key and Function key is activated which is placed at bottom right as below figure Press OK key or Cancel key Cancel Moves to upper parameter after not saving the setting OK Moves to upper parameter after saving ...

Page 52: ...7 Operation 52 Copyright Reserved KONICS Co Ltd 7 3 2 Parameter ...

Page 53: ...7 Operation Copyright Reserved KONICS Co Ltd 53 Dot lined parameters are affected by set value of other parameters ...

Page 54: ...7 Operation 54 Copyright Reserved KONICS Co Ltd ...

Page 55: ...fer to detail descriptions TC K Range Scale Point Decimal point TC RTD 0 0 0 0 0 Analog 0 0 0 0 00 0 000 0 0000 If special function is two unit 0 0 0 0 00 0 0 Display Temp Unit Display unit Temperature unit TC RTD K Analog Refer to detail descriptions High Low Range Graph Scale Upper Lower limit input value and graph scale value Low Input range Min graph scale value to upper limit input value Grap...

Page 56: ...r break OFF Up_Scale Down_Scale OFF Shaded parameters are affected by set value of other parameters Please refer to specific descriptions of each parameter When changing set value of Input Type input type parameter Range Scale Point Decimal point position Display Temp Unit Display unit Temperature unit Low Range Graph Scale Lower limit input value and graph scale value High Range Graph Scale Upper...

Page 57: ... for each channel KRN100 copies set values of the set completed channel to other channels Copyable parameters are as following Input Type Input specification Range Scale point Decimal point Display Temp Unit Display Temperature unit Low Scale Lower limit scale High Scale Upper scale Special Function Special function Two Unit Display the degree of a vacuum static pressure Reference Chanel Reference...

Page 58: ...ult ON 8 1 4 Pen Color Record color Designate record color when recordingmeasuring value Set range 1 Violet 2 Red 3 Black 4 Green 5 Blue 6 Brown Factory default Automatically set 8 1 5 Record Zone Record zone In case record mode is graph mode you can select record zone for to graph measuring value when recording Set range is set accoridng to the set value of 8 5 6 Divide Zone Record zone division ...

Page 59: ...ication and measuring range For jumper pin setting of universal input card KRN UI2 by inpust specification refer to 4 2 I O card Set range Refer to 2 3 Input specification and measuring range Factory default TC K 8 1 8 Range Scale Point Decimal point In case Input Type Input specification is temperature sensor thermocouple RTD set wheter to display decimal point to measuring value In case analog v...

Page 60: ...er0 2 F 18 Wt 33 mV 49 A 65 User1 3 K 19 mass 34 μV 50 kg cm2 66 User2 4 Kcal m3 20 Vol 35 kV 51 Pa 67 User3 5 Kcal 21 ppm 36 Ω 52 kPa 68 User4 6 cal 22 ppb 37 mΩ 53 MPa 69 User5 7 j 23 mol 38 μΩ 54 N m2 70 User6 8 Btu 24 Blank 39 s 55 N mm2 71 User7 9 l 25 lx 40 μs 56 inH2O 72 User8 10 ml 26 cd 41 VA 57 mmH2O 73 User9 11 t 27 lm 42 W 58 bar 12 gal 28 cd m2 43 kW 59 Torr 13 lb 29 rpm 44 MW 60 mmHg...

Page 61: ...it input value Set the actual used upper limit input value within input range of Input Type Input specification Set range Lower limit input value Low Range F S 5 to max input range value In case input range is 0 to 100 set range is 5 to 100 Factory default Set the displayed graph scale value on recording paper and LCD in temperature sensor input type Thermocouple RTD They does not displayed in ana...

Page 62: ...thin the input range of Input Type Input specification set upper limit graph scale value They does not displayed in analog input type Set range Lower limit graph scale value Low Graph Scale F S 5 to Max value of input range When TC K input range is 200 0 to 1350 set range is 122 5 to 1272 5 Factory default 1350 0 ...

Page 63: ...below figure for example measuring input value are a and b and the desired display value are A and B In this case about the input a and b it displays a A b B as linearly You can change display value about min max input value of measuring value In case input specification is 0 to 20 Set Low Scale Lower limit scale value 0 0 High Scale Upper limit scale value 10 0 20 0 30 0 20 0 Set Low Scale Lower ...

Page 64: ... Range Set range 99999 to 99999 9999 9 to 9999 9 999 99 to 999 99 99 999 to 99 999 9 9999 to 9 9999 Depending on Scale Point setting the range is different Factory default 2 High Scale Upper limit scale value Set scale value for upper limit input value High Range Set range 99999 to 99999 9999 9 to 9999 9 999 99 to 999 99 99 999 to 99 999 9 9999 to 9 9999 Depending on Scale Point setting the range ...

Page 65: ...ction is different Set range When input type input specification is temperature sensor thermocouple RTD None Difference analog voltage current Linear Root Squre Two Unit Two Unit is displayed when Input Type input specification is set as 0 to 20 4 to 20 Factory default None Below graph s patterns are liner root square for analog input Lower limit input value 5V Upper limit input value 5V Lower lim...

Page 66: ...lies lower limit scale and upper limit scale to lower limit input value and upper limit input value and displays this values In case lower limit input value 5V Upper limit input value 5V and in case lower limit scale 1000 upper limit scale 1000 if current input value is 2V display value is 400 Display value Input value Lower limit input value Upper limit input value Lower limit input value Upper l...

Page 67: ...imit scale Lower limit scale Lower limit scale 20 7 10 2 2000 1000 5 Two Unit For compound pressure if input pressure is lower than atmospheric pressure 0 it displays the degree of a vacuum with Hg unit If input pressure is higher than or same as atmospheric pressure 0 it displays positive pressure with kg unit When using Two Unit function lower limit value is fixed as 760mmHg and kg cm 2 value is...

Page 68: ... unit value same unit Y Use pressure 1 033 Ex Use pressure is 0 Y is 1 033 4 Output value for zero 4 00 Set range In case Input Type Input specification is temperature sensor thermocouple RTD None Difference In case Input Type Input specification is analog voltage current Linear Root Square Two Unit Two Unit is activated for current input 0 to 20 4 to 20 Factory default None Range Unit changing po...

Page 69: ...or area and measured subject area This function calculates and corrects this errors Several kinds of temperature sensor has specified grade High accuracy type is high price and ordinary product is generally used To correct input by measuring error from each helps more accurate temperature measurement For using this error correction function you should accurately measure the deviation from input pa...

Page 70: ...scale value Upper limit scale value Gradient adjustment value 0 00 10 00 0 500 0 00 to 5 00 0 00 5 00 1 000 0 00 10 00 1 000 0 00 to 10 00 0 00 10 00 1 000 0 00 10 00 1 500 0 00 to 15 00 0 00 15 00 1 000 In case Low Scale Lower limit scale value and High Upper limit scalevalue are fixed and Span Gradient adjustment is only set reverse gradient When Input range is 0 to 10V Low Scale Lower limit sca...

Page 71: ...ing value during record period Log Speed Maximum Max value Saves max measuring value during record period Log Speed Set range Instant Average Minimum Maximum Factory default Instant 8 1 17 Filter Type Input digital filter In some applications the fluctuating measuring input causes the display value to fluctuate In this case accurate display record is disable This function is able to make display v...

Page 72: ...tal filter this parameter is activated Set range 1 to 128 Factory default When the set value of input digital filter is 4 it does moving average input sampling values for 0 1 sec 100ms and displays this value D1 S1 D2 S1 S2 2 D3 S1 S2 S3 3 Display values of D1 D2 D3 is the initial operation before averaging 4 sampling values D4 S1 S2 S3 S4 4 D5 S2 S3 S4 S5 4 D6 S3 S4 S5 S6 4 D7 S4 S5 S6 S7 4 D8 S5...

Page 73: ...it structure 1 max or min value in graph record state it displays BURN Up Scale When input break after moving display value only upward records max value in graph record state it displays BURN Down Scale When input break after moving display value only downward records min value in graph record state it displays BURN Set range OFF Up Scale Down Scale Factory default OFF According to circuit struct...

Page 74: ...Hi Alarm2 Type to Alarm4 Type None Alarm Ref Channel Alarm reference channel None CH S UI Alarm Option Alarm option 1 None Latch StBy La St None Alarm Value Alarm set value 1 F S of INPUT TYPE by channel Digit Alarm1 Value 1350 0 Alarm2 Value to Alarm4 Value Alarm Hysteresis Alarm hysteresis 1 F S of INPUT TYPE by channel Digit 0 0 Alarm ON OFF Delay Alarm ON OFF output delay time 1 0 to 3600 sec ...

Page 75: ... KRN UI2 Set range CH S UI Activated connected universal input 2 channels per input card Factory default Automatically set 8 2 2 Alarm Set Copy Copy alarm parameter You do not need to set same parameter settings repeatedly for other channels This function is to copy set value of alarm parameter of the set channel and applys it to other channels Copiable parameters are as below Alarm Type Alarm ope...

Page 76: ...eference channel is same or higher than alarm set value alarm output turns ON 5 Deviation lower limit alarm DV Lo Alarm set value 10 Alarm set value 10 If the deviation between display value and the display value of reference channel is same or lower than alarm set value alarm output turns ON 6 Input break alarm SBA S In case input is not connected or input cable is break during controlling alarm ...

Page 77: ...graph Records also alarm and time information at right Alarm ON at the same time from over 2 channels Records alarm sign of corresponding channel s graph Records only time information at right Over 2 alarms ON from 1 channel Records alarm sign and CH1 AL the number of alarm 14 00 33 form If alarm occurs at digital memo time memo information includes alarm information Therefore as below figure alar...

Page 78: ...n upper limit alarm DH 4 Deviation lower limit alarm DL 5 Input break alarm SB 6 No recording paper PE 7 Several alarm ON AL It is used when printing 2 channels in one line Set range OFF PV Hi PV Lo DV Hi DV Lo SBA P End Factory default Alarm1 Type PV Hi Alarm2 Type to Alarm4 Type None 8 2 4 Alarm Ref Channel Alarm reference channel Designate reference channel which is standard of deviation upper ...

Page 79: ...n only select Latch Alarm latch 2 Condition of re applied standby sequence Power ON changing the set alarm temperature forced alarm reset Set range None Latch StBy La St Factory default None In case for input break alarm SBA no recording paper alarm P END standby sequence or alarm latch and standby sequence option does not operates and you cannot set it In case of alarm by alarm latch to reset ala...

Page 80: ...m second alarm conditions it operates as standard alarm 8 2 6 Alarm Value Alarm set value Set alarm set value based on alarm output operation mode it executes alarm operation Set range Using set input from Input Type Input specification within display range Factory default Alarm1 value 1350 0 Alarm2 Value to Alarm4 Value ...

Page 81: ...settings When input value is changed near SV alarm output is often Set hysteresis and it can be prevent from often alarm output Set range 0 0 to 9999 9 Decimal point position is different by the set decimal point position of input Factory default 0 0 The below graph is when Alarm Type Alarm operation mode is set as absolute value upper limit alarm Alarm Value Alarm set value is set as 200 and Alar...

Page 82: ...n Alarm On Delay Even after standby the set time when alarm ON condition alarm ON channel flashes on screen if it is still alarm condition alarm output turns ON Alarm ON channel flashes on screen Alarm OFF Delay Even after standby the set time when alarm reset condition alarm ON channel display is hold if it is still alarm reset condition alarm output turns OFF Alarm ON channel resets the display ...

Page 83: ...d type and displays it In this parameter TR output type is displayed as TR S AL and RELAY output type is displayed as RELAY S AL These parameter s meaning is as below S The number of module connected SLOT AL Alarm output channel number Number in parenthesis the number of designated alarm as output in the specified channel Set range None S AO Factory default None 8 2 10 Select Alarm Card Select ala...

Page 84: ...ys as Alarm Status and it is connected Relay or TR Type s output card information One card for relay has 4 outputs Alarm 1 Status to Alarm 4 Status for TR has 6 outputs Alarm 1 Status to Alarm 6 Status Relay output card KRN AR4 is connectable up to 3 and TR output card KRN AT6 is connectable up to 2 at Slot7 to 10 Alarm output turns ON or OFF by total 4 alarm conditions and relay TR output are abl...

Page 85: ...enter DIGITAL INPUT SETUP Parameter list Parameter Set range Factory default Select DI Card Select digital input card S7DI S8DI S9DI S10DI Automatically set DI Type Select digital input None Run Memo ListOut Speed Alarm Reset None DI Reset No Reset alarm number None ALL S AL DI Status Operation status Edge Level Shaded parameters are affected by set value of other parameters Please refer to specif...

Page 86: ... card KRN DI6 to be selected KRN100 searches connected digital input card automatically on slot and recognizes the number of digital input card as soon as power is ON Channel name is as below S Slot number DI Set range S7DI S8DI S9DI S10DI Factory default Automatically set S9DI This means connected digital input card on 9th slot ...

Page 87: ...d Option Standard Option Alarm Reset Forced alarm reset In case alarm option is alarm latch alarm output is reset by force Alarm Reset 1 At every min signal input width over 0 3 sec it executes the function repeatedly 2 The appropriate icon is displays on the screen digital input function is operating 3 When digital input operation status is set as Level in RUN mode you cannot operate starting sto...

Page 88: ... If digital input is re input the reverse function operates Level When digital input is short over 0 3 sec the set function operates If digital input is open over 0 3 sec the operation is stop Set range Edge Level Please refer to 8 3 2 DI Type Select digital input Factory default In digital input setting when DI Type is set as Run or Seed and DI Status is set as Edge overlap setting is available B...

Page 89: ...mmunication address 1 to 127 1 RS485 Port Use RS485 communication Enable Disable Enable Baud Rate Baud rate 2400 4800 9600 19200 38400 9600 Parity Bit Communication parity bit None Odd Even None Stop Bit Communication stop bit 1 2 2 Termination Set Terminating resistance Disable Enable Disable Response Wait Time Communication response wait time 5 to 99ms 20ms Protocol Communication protocol Modbus...

Page 90: ...se wait time 5to99 ms Start Bit 1 bit fixed Data Bit 8 bit fixed Parity Bit None Odd Even Stop Bit 1 2 bit Protocol Modbus RTU Modbus TCP Modbus RTU 1 When connecting through the network such as network hub HUB and gateway etc there is no distance limit but it is recommaned to use min network Please use communication cables which is satisfied the below conditions RS485 communication Shield Twist P...

Page 91: ...rminal of communication module and the grounding of computer When electric optional does not occur between computer and recorder grounded it is effective to minimize noise influence 3 Connects shield for one of SG terminal of communication module or the grounding of computer It can minimize noise effect in case of connecting non polarity condenser in series It is recommended to use SCM US 48I USB ...

Page 92: ...ed communication address setting in same communication line does not allow Set range 1 to 127 Factory default 1 8 4 2 RS485 Port Use RS485 communication Set whether using RS485 communication If you set RS485 Port s set value as Enable Ethernet Port s set value is changed Disable automatically Set range Enable Disable Factory default Enable 8 4 3 Baud Rate Baud rate Designate baud rated Set range 2...

Page 93: ... 8 4 5 Stop Bit Communication stop bit Designate communication stop bit Set range 1 2 unit bps Factory default 2 8 4 6 Termination Set Terminating resistance Desigante wheter using terminating resistance You do not need to external terminating resistance 120Ω because KRN100 is enable to use terminating resistance by parameter setting Set range Enable Disable Factory default Disable ...

Page 94: ... 99 unit ms Factory default 20ms 8 4 8 Protocol Communication protocol It supports Modbus RTU Remote Terminal Uint as communication protocol Data Length 8bit Data interval 24bits or less Error Detection CRC 16 Set range Modbus RTU Factory default Modbus RTU 8 4 9 RS485 Com Write RS485 communication write Set whether changing the set value of KRN100 parameter by RS485 communication To read the set ...

Page 95: ...ange Enable Disable Factory default Disable You can monitor or set parameter KRN100 with DAQMaster or the related Modbus program Modbus Poll etc For more information refer to KRN100 user manual for communication Modbus TCP communication The following is based on Windows XP 1st First of all connect Ethernet slot of KRN 100 communication output card KRN COM and LAN slot of PC with LAN cable 2nd Exec...

Page 96: ... of PC 4th Set KRN100 Ethernet Port Use Ethernet communication as Enable at COMMUNICATION SETUP Communication setting of KRN100 Set IP Address IP address as installation environment PC KRN100 IP Address 192 168 1 1 192 168 1 2 Subnet Mask 255 255 255 0 Default Gateway 192 168 1 1 IP address set for Modbus TCP communication is complete ...

Page 97: ...55 255 255 255 Factory default 8 4 12 Subnet Mask Subnet Mask To recognize network ID part and host ID part of IP address set 32 bit address allowing to IP packet receiver To enter correct set value whenever press keys it displays inputable subnet mask value is displayed Set range 0 0 0 0 to 255 255 255 255 Factory default 8 4 13 Default Gateway Default gateway Designate IP address to connect IP r...

Page 98: ...Enable Disable Factory default 8 4 15 USB Device Port Use USB communication Set whether using USBcommunication USB communication is available regardless of RS485 Port or Ethernet Port setting Set range Enable Disable Factory default Enable 8 4 16 USB Com Write USB communication write Set whether changing the set value of KRN100 parameter by USB communication To read the set value of each parameter...

Page 99: ...s 2hour Divide Zone Record zone division None 2 to 12 None Standard Period Standard record period 00m01s to 99m99s Option Period Option record period 00m01s to 99m99s Listing Language Language for list output Korea English English Alarm Speed Alarm record speed 10 20 40 60 120 240mm h 20mm h Power On Status Record status when power ON Hold Run Stop Hold Run Status List printing at start recording ...

Page 100: ...s current time hh mm ss display value by channel in set Memo Period Digital memo record period 2 Digital Records display value as numeric on recording paper It records current time hh mm ss display value by channel in set Standard Period Print Record period and also records current date Year Month Day and time in every 00 00 00 You can record digital memo manually by front key press key for 3 sec ...

Page 101: ... TwoCH 1 TwoCH It records 2 channels in one line and records occurring alarm as abbreviation In case of multi alarms it records as AL Print form is as below 2 OneCH It records 2 channels in one line and records occurring alarm as abbreviation Not as TwoCH it also records one channel s error message and occurring alarms in 4 alarms Print form is as below For the information about alarm abbreviation...

Page 102: ...ion record speed Recorder speed is indicated as feed length of recording paper per an hour mm h and it is activated only when Record Mode Record mode is set as Graph Graph After setting DI Type Select digital input as Speed select either Standard Speed standard record speed Option Speed option record speed by digital input When changing the set value of Standard Speed Standard record speed the set...

Page 103: ...00 not 10 20 Digital record time is 10 00 11 00 12 00 13 00 record end time If digital memo period is set as 10 min and record start time is 09 23 first record time is 09 30 not 09 33 Digital record time is 09 30 09 40 09 50 10 00 record end time Depending on record speed and the number of record channels memo period setting time is limited Record speed unit mm h Digital memo period setting time w...

Page 104: ... Record speed 1 min 5 min 10 min 15 min 30 min 1 hour 2 hour 3 hour 4 hour 8 hour 16 hour 24 hour 10 X X X X X X 20 40 60 120 240 Digital memo period setting time when record channel is 9 to 10CH Record speed 1 min 5 min 10 min 15 min 30 min 1 hour 2 hour 3 hour 4 hour 8 hour 16 hour 24 hour 10 X X X X X X 20 40 60 120 240 Digital memo period setting time when record channel is 11 to 12CH Record s...

Page 105: ... record zone by channel in Record Zone setting at Input Setup It is easy to check measuring value due not to duplicated record zone with divided record zone by channel which is set in Record Zone setting at Input Setup If there is too many division for record zone record value check accuracy is low Set range None 2 to 12 Factory default None Set value of record zone division None Set value of reco...

Page 106: ...o 99m 59s 3 to 4 02m 00s to 99m 59s 9 to10 05m 00s to 99m 59s 5 to 6 03m 00s to 99m 59s 11 to 12 06m 00s to 99m 59s Factory default 8 5 8 Option Period Option record period When Record Mode Record mode is set as Digital set record period for current time hh mm ss and measuring value by channel min sec through digital input Speed set Set range 00m 01s to 99m 59s Depending on the number of recording...

Page 107: ...up Copyright Reserved KONICS Co Ltd 107 8 5 9 Listing Language Language for list output Desigante recorded langauge when list output Language Example of recording English Korea Set range English Korea Factory default English ...

Page 108: ...nput occur at the same time digital input is ignored and it records with the set value of Alarm Speed Alarm record speed When alarm is reset it returns to Standard Speed Standard record speed In graph mode record speed is change by Standard speed Alarm and Option Speed Backup data is printable only with Standard speed Therefore original graph mode printout and backup graph mode printout may be dif...

Page 109: ...to print setting list when starting recording When printing list icon for record in section 1 is changed as and flashes After printing list with 240mm h record speed it processes record with changed set record speed Please refer to List Out Option List record option for the set list item Set range ON OFF Factory default OFF ...

Page 110: ...t input value LO RNG upper limit input value HI RNG display unit UNIT input digital filter FILT Option Records standard parameters and option parameters Input specification INPUT channel name TAG lower limit input value LO RNG upper limit input value HI RNG display unit UNIT input digital filter FILT alarm mode ALM alarm set value VALUE alarm number RELAY communication interface NETWORK USB E_NET ...

Page 111: ...or zone division is printed in violet Set range None to 8 0mm Set with 0 8mm interval Factory default 4 0mm 8 5 15 CH Print Distance Record interval for each channel graph Designate the interval for printing channel number of each graph as below figure It is activated when Record Mode Record mode is set as Graph Set range No Print to 100 0mm Set by 10mm interval Factory default 20 0mm 1 2 3 Set th...

Page 112: ...actiaved when Record Mode Record mode is set as Graph Set record period of High Low Range Graph Scale High Low input value and graph scale value Set range Disable 1 to 24hour Factory default Disable During Range printing the other data except graph is not recorded within pritted range Be sure that if there is too many channel numbers or if Range Print Time interval is too short with low speed vari...

Page 113: ...ummer Time Summer time Disable Enable Disable Summer Time Period Summer time period 01m 01d 00h to 12m 31d 23h Reservation Type Reservation record Disable Single Repeat Disable Reservation Period Reservation record period 2000y 01m 01d to 2099y 12m 31d Reservation Time Reservation record time 00h 00m 00s to 23h 59m 59s Alarm Sound Alarm sound OFF Min Standard Max OFF Sampling Rate Sampling period ...

Page 114: ...ou set the date the day of week is automatically set and time is displayed in 24 hours format Based on set date and time it records and saves the data Set range Date 2000y01m01d to 2099y12m31d Time 00h00m00s to 23h59m59s Factory default Set as factory default 8 6 3 Date Type Date type Set KRN100 system date display method on the screen and record method on the recording paper You can select one di...

Page 115: ...and displays S mark in front of the date and time on LCD screen or in front of the date on recording paper Set range Disable Enable Factory default Disable 8 6 5 Summer Time Period Summer time period Designate summer time daylight saving time period When Summer Time is set as Enable it is activated Designate Start date Time and End Date Time Set range 01m01d 00h to 12m31d 23h Factory default When ...

Page 116: ...Repeat ON OFF From start recording date to end recording date it records data at from the set start time to the set end time End time must be later than Start time Reservation Period Reservation record period setting Start Date 2011 1 1 End Date 2011 1 3 Reservation Time Reservation record time setting Start Time 12 00 00 End Time 23 59 59 It records data every at from 12 00 00 to 23 59 59 in from...

Page 117: ... 2000 01 01 to 2099 12 31 Factory default 8 6 8 Reservation Time Reservation record time Designate reservation record time When Reservation Type Reservation record is set as Repeat Repeat ON OFF or Single Single ON OFF it is activated to designate Start Time Start time and End Time End time Set range 0 00 00 to 23 59 59 Factory default If reservation record Reservation record is set and during res...

Page 118: ... default OFF 8 6 10 Sampling Rate Sampling period Designate sampling rate Sampling period of measuring value Set range may be different by the number of connected universal input card KRN UI6 Set range When connecting 1 to 2 universal input card KRN UI2 25 125 250ms When connecting 3 to 6 universal input card KRN UI2 125 250ms Factory default 125ms Min sampling period for TC R U S T sensors is 50m...

Page 119: ... is lower because of the occuring alarm record in the middle of save period during recording When setting as 0s for Log Speed save period recording operates normally but the data does not saved at inner external memory If no recording paper P END alarm occurs there is no designated data and backup data is not recorded 8 6 12 Backlight LCD backlight brightness Designate LCD backlight brightness as ...

Page 120: ...pms User3 pms User4 pms User5 pms User1 pms USB User2 pms USB User3 pms USB User4 pms USB User5 pms USB None Save Set File Save parameter setting file None Default pms User1 pms User2 pms User3 pms User4 pms User5 pms User1 pms USB User2 pms USB User3 pms USB User4 pms USB User5 pms USB Select Memory Status Memory capacity 0 to 100 display range 0 Memory Clear Delete memory Cancel All Clear Clear ...

Page 121: ...lized as factory default Save the current set parameter as Save Set File parameter setting file storage at first and initialize it for the provision User1 pms to User5 pms User1 pms USB to User5 pms USB file is selected all parameter setting information of KRN100 is changed as the set value of the selected parameter save file Set value changing may be also affected to every setting of KRN100 s ove...

Page 122: ...a is created when it is over 100 Mbyte Below table is save time for 100Mbyte data by the number of input channels The number of CH Saved time The number of CH Saved time 1 channel Approx 50 days 7 channels Approx 25 days 2 channels Approx 43 days 8 channels Approx 23 days 3 channels Approx 37 days 9 channels Approx 21 days 4 channels Approx 33 days 10 channels Approx 20 days 5 channels Approx 30 d...

Page 123: ...n Special function High Low Range Graph Scale High Low input value and graph scale value Low Scale High Scale Lower Upper limit scale value Alarm Type Alarm operation mode Alarm Alarm No Alarm output alarm number Record Mode Record mode Divide Zone Record zone division Standard Speed Standard record speed Memo Period Digital memo period Log Speed Save period Summer Time Summer time Supporting file...

Page 124: ...age space is used all as 100 Set value Description Overwrite Deletes the oldest backup data file in order and saves new data Important backup data should be backup at first Stop Stop saving Stops backup data It does not save Backup data Even though new recording paper is replaced output function for backup data does not operate Set range Overwrite Stop Factory default Stop ...

Page 125: ...ory Move to USB Memory Saves selected backup data to an USB memory and deletes backup data of system memory Delete File Deletes backup data File Information Displays backup data information Displayed information is Name Path Size Log Channel Log Speed Prev Page Moves to previous page of file or directory list Next Page Moves to next page of file or directory list Up Directory Moves to parent folde...

Page 126: ...h keys preess key to enter USER INFORMATION SETUP Parameter list Parameter Set range Factory default Password Password mode Disable Enable Disable Login Admin Administrator log in 0000 to 9999 Change Admin Password Change password by administrator 0000 to 9999 User Lock Change user authority OFF LOCK1 LOCK2 LOCK3 OFF Information Check system information Display Firmware Upgrade Firmware upgrade Au...

Page 127: ... authorization to use all functions Enable With administrator s or user s log in and password allows operation authorization When setting the password lock icon is displayed In user general user mode lock icon marks as and in administrator mode it marks as Set range Disable Enable Factory default Disable Password mode setting Disable Enable is available without authority But Enable Disable changin...

Page 128: ... is not set yet default password is 0000 When entered administrator s password is wrong it displays Fail ASKey xxxx Please call our service center 82 32 820 2343 and tell us ASKey and you can check administrator s password 8 8 3 Change Admin Password Change password by administrator Change the previous password Changing password is able only when login status as administrator Set range 4 digit num...

Page 129: ...hange set value Set range OFF LOCK1 LOCK2 LOCK3 Factory default OFF Regardless of User Lock change user authority setting User general user mode cannot change firmware upgrade the set file initialize password mode disable functions 8 8 5 Information Check system information Check system information of KRN100 You can firmware version an USB memory capacity communication concerns slot connection sta...

Page 130: ...1st Visit our homepage www konics com to download KRN100 firmware file krn100 fwu 2nd Copy the downloaded firmware file to an USB memory s loot top directory and connect an USB memory to KRN100 3rd Check that firmware is recognized on USERINFORMATION SETUP Firmware Upgrade menu 4th Check currrent version s date and to be upgraded version s date Select Upgrade button and it starts firmware upgrade ...

Page 131: ...te normally Therefore please take proper measure to prevent malfunction of KRN100 system before starting firmware upgrade After completing firmware upgrade you must turn OFF and ON the power of KRN100 to operate normally In process of firmware upgrade when power turns OFF firmware upgrade is not complete When power turns ON again KRN100 operates with previous firmware version Try firmware upgrade ...

Page 132: ...Time Start time for data storage Date yyyy mm dd Time hh mm ss 0000 00 00 00 00 00 End Date and Time End time for data storage Date yyyy mm dd Time hh mm ss 0000 00 00 00 00 00 Backup Print Mode Backup data record mode Graph Select Print Mode Backup data recording mode setting Graph Digital Graph When printing with backup data the saved data in backup data is accurate but backup data printout may ...

Page 133: ...de the icon for record changes as and flashes KRN100 reads backup data to the end and starts recording Depending on backup data file size reading time may take longer When starting printing by Record Backup function starts recording as below figure Set range Start Stop Factory default Stop 8 9 2 Backup Data List Backup data list You can check saved Backup Data List Backup data list Backup Data is ...

Page 134: ...and time Set range Date yyyy mm dd Time hh mm ss Factory default 0000 00 00 00 00 00 8 9 4 End Date and Time End time for data storage Set storage end date and time for backup data You can set end date and time Set range is within start date and time to end date and time Set range Date yyyy mm dd Time hh mm ss Factory default 0000 00 00 00 00 00 8 9 5 Backup Print Mode Backup data record mode You ...

Page 135: ...al or Graph on current record setup For example in case original backup data is saved as Digital mode Backup Print Mode displays digital To print with Graph mode Select Print Mode set as Graph Graph mode s record speed follows the set record speed of graph mode in current record setup How to select record backup file 1st Move to RECORD BACKUP SETUP parameter setting group 2nd In Backup Data List p...

Page 136: ... If there are lots of files Up Directory Moves parent folder Into Directory Enter the folder 5th You can check save time information of the selected Backup Data Moves parent folder 1st Press key in selected file to activate selected screen Select Up Directory and it moves to parent folder 2nd To moving parent folder you can check folders by created date 3rd To move desired date folder press key at...

Page 137: ...unter product line of Autonics and recorder product line of KONICS DAQMaster provides graph user interface GUI for easy and convenient integrated several products parameter setting and data monitoring Visit our homepage www konics com to download DAQMaster user manual This KRN100 user manual describes only for dedicated KRN100 functions For more information about DAQMaster please refer to DAQMaste...

Page 138: ...he project this file has the saved setting status You can also construct project list for convenient project file management Monitoring data log It logs the data during monitoring and is able to save it as one of DAQMaster data file ddf or CSV file csv You can load the saved CSV file in Microsoft Excel directly You can also designate file name storage rules and storage folders for easy file manage...

Page 139: ...up You can download backup data which is saved in KRN100 inner memory from Record Backup section Directory form is year month day Click the relevant icon and check below list To download backup file click the file name with right mouse button and select Download Log File menu Backup files are strucured as tree type directory at KRN100 inner memory You can easily fine and download the desired file ...

Page 140: ...o for display output one for printing Image type Size Unit image for printing 32X10 Small unit Unit image in several channel for displaying 32X12 Middle unit Unit image in 1 channel for displaying 72X64 Large unit How to register user unit image 1st Make 3 sizes images file type bmp using image tools 2nd Double click the arrow area as below figure and select the desired image files If you not sele...

Page 141: ...Ltd 141 3rd Select image files by type and size click Download to download user images 9 3 3 Boot logo image setting You can set boot logo image to display during KRN100 booting After making 320x120 size image with image tools and download it ...

Page 142: ...function This function is output downloaded backup data by DAQMater or an USB memory 1st Execute Data Anal At taskbar click Start Program DAQMaster DataAnal or at DAQMaster menu click Tool Data Anal 2nd Data Anal program opens Click open file icon and select downloaded KRD file ...

Page 143: ...Open chart and drag the desired channel to check waveforms or values For more information please refer to DAQMaster user manual When checking backup data by DAQMaster it may not be 100 same with original print out Please use backup data only for reference ...

Page 144: ...9 DAQMaster 144 Copyright Reserved KONICS Co Ltd ...

Page 145: ...dge replacement 1st Press key for 3 sec in stop recording state and Ink cartridge moves to the center to be replaced easily Open front cover of KRN100 2nd Push down recording paper cassette lever placed at below recording paper cassette recording paper cassette is removed from KRN100 ...

Page 146: ...nsert new ink cartridge 10 2 Recording paper replacement 1st From 1st to 2nd steps are same as Ink cartridge replacement method Please refer to this Below figure is detached recording paper cassette 2nd Open new recording paper storage cover and finished recording paper storage cover of recording paper cassette ...

Page 147: ...NICS Co Ltd 147 3rd For better print recording paper should be loosen by entering the air If not as below figure it may cause paper jam 4th Remove finished recording paper in finished recording paper storage and replace ne recording paper ...

Page 148: ...Maintenance 148 Copyright Reserved KONICS Co Ltd 5th Put recording paper s holes circle oval at recording paper holder and close new recording paper storage cover and finished recording paper storage cover ...

Page 149: ...eserved KONICS Co Ltd 149 6th Push recording paper cartridge into KRN100 until click sound Close front cover of KRN100 7th Check recording paper operates normally by pressing front key with FEED function in stop recording state ...

Page 150: ...10 Maintenance 150 Copyright Reserved KONICS Co Ltd ...

Page 151: ...t memo period To cancel former data recording pause and re start record Change the settings about record for proper operation 5 In graph mode printout for line and letters is not clear and spread Replace ink cartridge 6 Recording paper s terminal mark red star shape is displayed Recording paper should be replaced Present recording paper lefts only 330mm from terminal mark 7 When power ON after boo...

Page 152: ...ed automatically Prints LL _H In case Input Type is analog current voltage if input value is higher than below 10 of upper limit input range _H is displayed with current value to notify that current value is higher than upper limit input range Ex When upper limit input range is 100 and current value is 102 it displays as 102_H _L In case Input Type is analog current voltage if input value is lower...

Page 153: ...11 Troubleshooting Copyright Reserved KONICS Co Ltd 153 ...