background image

 

 
VariTrans® P 27000-S007 
Universal Isolators 

Read these instruc

tions bef

or

e using the pr

oduc

t and r

etain f

or futur

e inf

or

ma

tion.

TA-251.103-KNE01   20120802

084762

84762

Summary of Contents for P 27000 H1-S007

Page 1: ...VariTrans P 27000 S007 Universal Isolators Read these instructions before using the product and retain for future information TA 251 103 KNE01 20120802 084762 84762 ...

Page 2: ...ecting it from each operating energy supply source The disconnecting means shall disconnect all current carrying conductors It must be easily accessible and clearly identifiable by the operator Mains supply must be protected by a fuse of 20 A max Caution Be sure to take protective measures against electrostatic discharge ESD when handling the devices The warning symbol on the device exclamation po...

Page 3: ...mponents may impair suitability for Class I Division 2 For the use in hazardous locations this equipment is to be installed into suitable enclosure providing a degree of protection not less than IP 54 Devices containing user accessible switches and or potentiometers the device must be installed into an end use enclosure with tool removable cover Conditions for safe use Haz Loc ...

Page 4: ...he units can be powered by voltages from 20 to 253 V AC DC Connection is made using pluggable screw clamp terminals Warning against misuse Do not operate the device outside the conditions specified by the manufacturer as this might result in hazards to operators or malfunction of the equipment 3 Configuration 3 1 Tools A screwdriver with a width of 2 5 mm is required to open and adjust the unit an...

Page 5: ...until they lock 3 3 Settings Adjust the output range using DIP switches S1 S2 and S3 as shown in the table below P27000H1 S007 Caution The special model P 27000 S007 may be used in this range only Input Output S1 1 2 3 4 5 6 7 8 9 10 0 10 V 0 20 mA ON ON ON OFF OFF OFF ON OFF OFF OFF Input Output S2 S3 1 2 3 4 5 1 2 3 0 10 V 0 20 mA OFF ON OFF ON ON OFF OFF OFF ...

Page 6: ... 62 Hz 2 5 VA overvoltage category II 4 Mounting The universal isolators are mounted on standard TS 35 rails 5 Electrical Connection Terminal assignments 1 Do not connect 2 Do not connect 3 Input 4 Input 5 Output 6 Output 7 Power supply 8 Power supply Wire cross section max 2 5 mm2 Multi wire connection max 1 mm2 two wires with same cross section AWG 30 12 tightening torque 0 7 Nm Wiring has to be...

Page 7: ...7 6 Dimensions Metal lock for fastening on top hat rail Fixed screw clamp terminals 111 99 All dimensions in mm ...

Page 8: ...n of Conformity is included in the documentation The Statement of Conformity for ATEX Zone 2 apparatus is included in the documentation GL Certificate No 42 843 02 HH Environmental Category D Test Standard Regulations of the Performance of Type Tests Part 1 EN 61010 1 8 Order Information Device Order No Pluggable screw clamp terminals P 27000 S007 Universal Isolator P 27000 H1 S007 ...

Page 9: ... error for AC 45 65 Hz sinus 1 meas value Temperature coefficient2 50 ppm K full scale Cutoff frequency approx 16 kHz Test voltage 5 kV input against output 4 kV output against power supply Working voltage3 basic insulation 1 kV for overvoltage category II and pollution degree 2 to EN 61010 1 For applications with high working voltages take precautions to prevent accidental contact and make sure t...

Page 10: ...distance to adjacent devices or sufficient insulation between them EMC4 2004 108 EC EN 61326 EN 61326 A1 Surge withstand 5 kV 1 2 50 μs to IEC 255 4 Ambient temperature Operation Transport and storage 10 to 70 C 40 to 85 C Ambient conditions Stationary application weather protected Relative air humidity 5 95 no condensation Barometric pressure 70 106 kPa altitude up to 2000 m Water or wind driven ...

Page 11: ... GRP A B C D T4 1 Higher output load on request 2 Average TC in specified operating temperature range 10 C 70 C 3 cULus certification Working voltage basic insulation up to 600 V working voltage reinforced insulation up to 300 V across input and output each for overvoltage category II and pollution degree 2 4 Slight deviations are possible while there is interference ...

Page 12: ...12 Knick Elektronische Messgeräte GmbH Co KG Beuckestraße 22 D 14163 Berlin Phone 49 0 30 801 91 0 Fax 49 0 30 801 91 200 Internet http www knick de Email knick knick de ...