READ AND FOLLOW ALL INSTRUCTIONS

1a)

K-Star Heater may be installed indoors or outdoors at least 6”
from any object. Ensure that the installation allows access for electrical 
and plumbing connections and that the Thermostat control is 
conveniently located.

The installation of current leakage collectors should be done as 
per Figure 01 before permanently positioning Heater.

Heater must be installed after the filter and before the Air Injector 
or  Automatic Chlorinator.

b)

A leakage current collector must be installed at the water inlet,
and another at the outlet of the unit, and these shall be electrically 
insulated from the unit. The installation of the collectors shall be
such that all water entering and leaving the unit flows through the 
two collectors, as shown in Figure 01. The length of the leakage current
collectors shall be made of a corrosion resistant metal and shall be
provided with a copper lug brazed to the collector body.

Hand tighten only. Do not use high force with a pipe wrench.

FIGURE 01.

LEAKAGE CURRENT COLLECTOR DIAGRAM

C)

The Heater shall be installed as per Figure 02. The water inlet and outlet 
are connected to straight connectors of the heater.

FIGURE 02

2

361 Rowntree Dairy Road, Unit 4 
Woodbridge, ON Canada L4L 8H1

Tel: 905.264.6496  Fax: 905.264.6508
Email: [email protected]

INSTRUCTION MANUAL

“K-STAR” ELECTRIC

POOL & SPA HEATERS

APPROVED LR 51670

MODELS:

K-5 / K-10 / K-15

KS-5 / KS-10

Summary of Contents for K-5

Page 1: ...insulated from the unit The installation of the collectors shall be such that all water entering and leaving the unit flows through the two collectors as shown in Figure 01 The length of the leakage current collectors shall be made of a corrosion resistant metal and shall be provided with a copper lug brazed to the collector body Hand tighten only Do not use high force with a pipe wrench FIGURE 01...

Page 2: ...del Amps Fuse 240V G F L Size Wire Size 90 Copper Only Collector Ground Wire Copper Only K 5 KS 5 21A 30A 10 10 K 10 KS 10 42A 60A 6 6 K 15 63A 80 100A Use Supply conductor suitable for 75º C Use Supply conductor suitable for 75ºC 3 MECHANICAL INSTALLATION DIAGRAM SHOWING BY PASS Caution i Do not store chlorine near or in the same room as heater ii Valves must not be installed in the piping on the...

Page 3: ...n of moisture or water into electrical components At all times the unit must be properly ventilated to avoid condensation FIGURE 05 WIRING DIAGRAMS below 5 supplying this equipment Addition bonding lugs are provided and marks Bonding Lugs To reduce the risk of electric shock connect the bonding lugs in accordance with the Canadian Electric Code Part 1 c It is mandatory that all Electrical Pool hea...

Page 4: ...onnection reconnection charges The above warranty shall be considered void if i The installation instructions are not followed ii Unit is powered without any water circulation iii The power is disconnected and unit is not thoroughly drained at the time of winterizing iv The Unit has been mishandled Warranty Registration must be done within ten days of the purchase of the unit by mailing warranty c...