background image

Installation, Operation
and Maintenance Manual

PN 750-0064-REV. 44

JOSLYN

®

TRANSEND

INSTALLATION, OPERATION AND MAINTENANCE MANUAL ISSUED 6.01

®

Trans

End

Trans

End

Surge Suppression
Filter Systems

Trans

End

100

Trans

End

80

Trans

End

50

Trans

End

25

Summary of Contents for TransEnd 50

Page 1: ...tion and Maintenance Manual PN 750 0064 REV 44 JOSLYN TRANSEND INSTALLATION OPERATION AND MAINTENANCE MANUAL ISSUED 6 01 TransEnd TransEnd Surge Suppression Filter Systems TransEnd 100 TransEnd 80 TransEnd 50 TransEnd 25 ...

Page 2: ... your TransEnd system in a location that minimizes wire lengths and wire bends This positioning maximizes surge suppression and filtering while providing added protection for the connected loads Thank you for choosing the Joslyn TransEnd Surge Suppression System We look forward to fulfilling your facility wide surge suppression filter system needs Monday through Friday 8 00 a m to 5 00 p m EST 800...

Page 3: ...hrough the easy installa tion procedures However should you have questions about installing TransEnd please call Joslyn Technical Support at 800 238 5000 WARNING The TransEnd s Warranty is voided if the unit is dam aged as a result of improper installation or the installer s failure to verify the following conditions prior to installation Confirm that the voltage s and power configuration shown on...

Page 4: ...consistent with the guidelines above or 2 your conditions cannot be verified Call Joslyn Technical Support at 800 238 5000 if you have any questions TransEnd is to be connected in parallel with the electrical system and must be fed by an overcurrent protection device 20A circuit breaker or fuse in a power distribution panel Figures 1 4 show the relationship between the TransEnd device and these fo...

Page 5: ...DELTA FIG 2 3 Phase 3 Wire DELTA TRANSEND XXX 3DG G C EARTH GROUND CONDUCTORS FURNISHED WITH TRANSEND B N G PHASE A ORN BRED 20 AMP 3 POLE CIRCUIT BREAKER GREEN PHASE B PHASE C TRANSEND 120 240 3GHD N G XO BOND C EARTH GROUND CONDUCTORS FURNISHED WITH TRANSEND Note High Leg must be B Phase B N N G WHITE PHASE A 20 AMP 3 POLE CIRCUIT BREAKER ORANGE PHASE C GREEN ...

Page 6: ...UAL ISSUED 6 01 6 FIG 4 1 Phase 3 Wire SPLIT PHASE Mounting Four 5 16 inch holes are provided for mounting the TransEnd TRANSEND TRANSEND 120 240 2G 20 AMP 2 POLE CIRCUIT BREAKER GREEN PHASE B PHASE A WHITE 7 1 2 4 1 6 3 4 6 3 8 HUB FiG 5 Mounting Hole Detail ...

Page 7: ...optional Form C dry contacts use butt splices within the panelboard to connect the Form C leads to the user s monitoring circuits Alternatively install a junction box between the TransEnd and the panelboard to connect Form C leads to user s monitoring circuits See Fig 6 under Options page 8 Consult applicable local codes to ensure proper installation Measure the line to line voltage at the panel t...

Page 8: ...s Form C dry contacts for remote monitoring Upon failure of any phase the relay s N O and N C contacts will change state The contacts are rated at 110VDC 125VAC with maximum switching power of 30W DC 62 5VA AC 18 inches of 3 4 inch nonmetallic flexible conduit and a fitting that connects to the provided 3 4 inch hub 3 4 inch x 3 inch nipple that connects to the provided 3 4 inch hub The only opera...

Reviews: