ARCTICA – AQUARIUM SERIES 

TROUBLESHOOTING 

 
 
 

 

There are many factors that may affect the cooling performance of your Arctica chiller. In 
order to determine the cause we recommend the following: 

 

 

Perform Static Test 

 

Read FAQ

 

Contact us for further assistance 

 
 

Static Test 

Performing a Static Test will allow the chiller to operate without any external factors such as heat 
load from equipment, volume load of water capacity, or pump water flow. The main purpose of 
this test is to establish that the controller, relay,  fan motor, compressor, and temp probe are in 
working order without being linked to the actual tank set up. 

 

Step 1 
Turn off the pump that flows through the chiller 

This test only requires the small amount of water already within the heat exchanger. 

 

Step 2   
Program the controller to 60F for the set point 

Press the up or down arrow and hold until the number starts to blink, then release and press the 
down arrow until the temperature on the controller reads 60F and then release. It will blink and 
then the temperature will show a solid color. It is now set to 60F; it will take approximately 5 
minutes or less for a functioning chiller to bring the temp down to 60F due to the small amount of 
water volume in the heat exchanger. 
 

Step 3 
Observe Components Operation 

A.

 

Controller:

:

 The “Cool” lamp indicator on the controller should be blinking. This means 

the controller will send the command to the relay to turn on the fan motor and 
compressor after about 2 minutes. The “Cool” lamp will illuminate and stop blinking at 
this time. 

B.

 

Relay: 

Verify that the fan motor & compressor turns on when the “Cool” lamp is 

illuminated solid. 

C.

 

Fan Motor:

 Place your hand behind the rear of the chiller exhaust. Verify that there is 

air flow and that the temperature of the air flow after a few minutes is warm not cool. 

D.

 

Compressor:

 Place your hand on the top of the chiller and verify you can feel a slight 

vibration from the compressor. 

E.

 

Temp Probe:

 Verify that the temperature on the controller is not eradicate and is 

dropping in temp not rising. 

 
 