IMPORTANT SAFETY INSTRUCTIONS • SAVE THESE INSTRUCTIONS

INSTALLATION INSTRUCTIONS

APPLICATION NOTES

1. 

Thoroughly read instructions before installing SPD unit.

2. 

This product is designed to protect against momentary transient overvoltage events.

3. 

This product may not protect against nearby lightning strikes.

4. 

This device features internal protection that will disconnect the surge protective component at the end of its useful life but will maintain power to the load-now unprotected. If this situation is undesirable 
for the application, follow the manufacturers instructions for replacing 

I

Module™

 

units.

5. 

Observe warnings and instructions on front panel and unit label of product.

DEFINITIONS

Type 2 SPD:

 

A typical type 2 SPD installation will be connected to the load side of the service panel and is intended to be installed with overcurrent protection to the SPD.

INSTALLATION:

1.  Verify system voltage. 

2.  Make sure SPD is correctly rated for your system. 

3.  Determine mounting location of SPD unit.

 

 The SPD unit should be located as close as possible to the load to be protected.

4.  Mount enclosure

 

- Remove dead front from SPD unit.

 

- Disconnect power to SPD unit at power source before installation.

 

- Remove needed knockout from SPD unit once wire routing has been determined.

 

- Only one conduit connection may be made to the SPD enclosure.

 

-  Mount enclosure using suitable fasteners in locations shown below. Do not rely on conduit fitting to support SPD unit.

5.  Follow wiring diagram for all connections. (located within instruction sheets and SPD unit).

 

- Lead lengths can be replaced at terminal; splicing of leads is not recommended.

 

- Cut all wires to a minimum suitable length while maintaining a 4” recommended bend radius.

 

- Do not coil excess wire.

 

- Make sure all connections are secure.

 

- Replace dead front.

6.  Energize SPD unit

 

- Flip circuit breaker to ON position at service panel or disconnect switch(es).

 

- Indicators: Each 

I

Module™ has a blue LED to indicate the SPD unit has power and a green LED to indicate that the 

I

Module™ is providing protection.

 8 1/2" 

 3 1/4" 

 1 5/8" 

Plastic outdoor enclosure

SERVICING INSTRUCTIONS: 

The 

I

Module™ units will absorb the energy of the surges to protect the connected load. If the green LED is OFF, the  

I

Module™ is no longer providing protection and should be replaced as soon as possible. 

All three of the removable 

I

Module™ units must be replaced every three years to maintain the connected equipment warranty.

TO REPLACE 

 

I

Module™ 

UNITS:

1. 

POWER MUST BE REMOVED FROM THE 

I

Module™ BEFORE REPLACING.

2. 

Disconnect power to SPD unit at service panel and/or disconnect switch(es) before servicing.

3. 

Remove 

I

Module™ to be replaced by firmly pulling straight out from SPD unit. The module door within the unit will close once the 

I

Module™ is removed.

4. 

Make sure 

I

Module™ is correctly rated for system.

5. 

Place new 

I

Module™ back into SPD unit. Make sure 

I

Module™ alignment key is oriented correctly when inserting.

6. 

Make sure the 

I

Module™ is fully seated.

7. 

Re-energize SPD unit.

8. 

Verify the blue and green LED’s within each 

I

Module™ are lit.

SPD

UNIT

Main Breaker

2-Pole, 30A circuit
breaker

Green (Ground)

Type 2 Installation

Black (Line)

Black (Line)

Neutral (White)

*C/B

GND (green)

Neutral (white)

Line (black)

Line (black)

SPD TYPE  2  WIRING DIAGRAM

120/240 VAC SINGLE-PHASE

SPD

*2 Pole 30 A circuit breaker in Service Panel.

IG2240-PK

TYPE 2 SURGE PROTECTIVE DEVICES

Blue LED: Power indicator

Green LED: Status indicator

Alignment key of module

ON: Protection is being provided.
OFF: IModule™ is no longer providing
protection. Replace IModule™ as soon
as possible.

I

Module™

Risk of Fire or Electric Shock

  •   Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
  •   Confirm 

Smart Guard 

™ is rated for the correct voltage per part number specified on your SPD enclosure.

  •   Installation and/or wiring must be in accordance with national and local electrical code requirements.
  •   Installation and service to be performed by a qualified licensed technician or electrician.
  •   For outdoor locations or wet locations (rain-tight), conduit hubs that comply with requirements of the UL514B (standard for fitting conduit 

and outlet boxes) are to be used.

  •   Bonding between conduit connections is not automatic and must be provided as part of the installation.
  •   KEEP DOOR CLOSED AT ALL TIMES when not servicing.

 

WARNING

Содержание Smart Guard IG2240-PK

Страница 1: ... 8 Plastic outdoor enclosure SERVICING INSTRUCTIONS The IModule units will absorb the energy of the surges to protect the connected load If the green LED is OFF the IModule is no longer providing protection and should be replaced as soon as possible All three of the removable IModule units must be replaced every three years to maintain the connected equipment warranty TO REPLACE IModule UNITS 1 PO...

Страница 2: ...nt d Equipment with additional telephone or data cable connections must be properly connected to an Intermatic Listed Surge Protection Device see www Intermatic com and e the Product s and Protected Equipment must not be opened modified exposed to extreme heat or cold submerged or subjected to abnormal use or service For purposes of this Limited Warranty a Power Transient shall mean over voltage r...

Страница 3: ...D ENTRETIEN L IModule absorbe l IModule absorbe l énergie superflue des surtensions afin de protéger la charge connectée Si la DEL verte est ÉTEINTE l IModule ne fournit alors plus de protection et doit être remplacé le plus rapidement possible Tous les trois IModule amovibles doivent être remplacés tous les trois ans afin de garantir la protection des appareils connectés REMPLACEMENT DE L IModule...

Страница 4: ...pas être ouverts modifiés exposés à la chaleur ou au froid intenses immergés ni soumis à une utilisation ou à un entretien inappropriés Aux fins de la présente garantie limitée une Transitoire électrique est une surtension résultant de pointes ou crêtes momentanées de tension sur la ligne d alimentation secteur d une amplitude que le Produit conformément à ses caractéristiques est conçu pour arrêt...

Страница 5: ...STRUCCIONES DE MANTENIMIENTO Las unidades del IModule absorberán la energía de la sobretensión para proteger la carga conectada Si el LED verde se encuentra en OFF apagado significa que el IModule ya no está brindando protección y se debe reemplazar cuanto antes Se deben reemplazar las tres unidades extraíbles del IModule cada tres años para mantener la garantía de los equipos conectados PARA REEM...

Страница 6: ...los Producto s y Equipo dañado no se deben abrir modificar exponer al calor o el frío extremo sumergir ni someterse a un uso o mantenimiento anormales Para propósitos de esta Garantía limitada un transitorio eléctrico se entenderá como sobretensión o sobrevoltaje causado por picos de tensión o sobretensiones momentáneos en una línea de alimentación CA de una magnitud que el Producto según sus espe...

Отзывы: