manualshive.com logo in svg
background image

158PG1

1953

ITEM

PT
. NO.

DESC.

QUAN.

DR.:   SRB   1/25/2005      

INTERMA

TIC INCORPORA

TED

CHKD.:  RM 1/25/2005

SCALE:

NAME:     

INST SHT -  PG60-PG80-PG100 SERIES     

APPROVED

MA

TL.:     

WHITE P

APER ST

OCK

2    

REVISE DR

WG TO ALIGN TEXT (NO

ECO)

SRB

3/2/2005

2-RM 3/2/2005

FINISH:    

BLACK PRINTING INK

1      RELEASED  T

O ELEC. DA

T

A

HEA

T TREA

T

:

LET

.    REVISION

SIGN.

MODEL

SUPERSEDES:

NOTES:

ALL

PRINTING T

O BE 

AS PER INTERMA

TIC

APPROVED ARTWORK.

FRA .010 . DECIMALS 

AS SPECIFIED - 

1/2˚

ALL

DIMENSIONS MUST

BE MET

BEFORE PLA

TING.

DIM       

:

TO
L

11

8.

5

SEE B/M FOR 

ALL

P

ART NUMBERS & QUANTITIES

FRONT

BACK

FOLD LINES

INSTALLATION INSTRUCTIONS

and

OPERATIONS MANUAL

PanelGuard

®

PG60 - PG80 - PG100 Series

Electrical Panel Extension Hardwired Surge

ALARM

OPERA

TION

PROTECTIO

N MODES

CAUTION

; HIGH V

OLTAGE INS

IDE

SEVICE BY

 QUALIFIED

 PERSONN

EL ONL

Y

Red ALARM 

light ON or 

Audible Alarm 

ON 

indicate

loss 

of prote

ction. 

 Refe

r to 

the operatio

n manual for

 

troubleshoo

ting help.

Alarm

Neutral

L1

L2

L3

L1

L2

L3

Ground

Green lights

 ON indicat

power prese

nt and prote

c- 

tion circuits

 for each mo

de 

are operatin

g propely

One or more

 Green ligh

ts 

OFF indica

tes loss of 

power 

or protection

. Refer to th

operation m

anual for 

troubleshoo

ting help.

INTRODUCTION

The PG60-80-100 Series is designed to be installed in very close prox-
imity to the power bus of an electric distribution panel or electric panel-
board.   It can be used with most panels or panelboards in distribution
today.  The PG60-80-100 Series offers peak surge amperage protection
levels of 60 kA to 100 kA per mode.  It is designed to be easily mounted
above or below the panelboard.  Provisions have been made with a
reversible cover plate to keep the instructions and indicators in a user
friendly position.  Standard features include all mode protection,  multi-
mode LED indicators that show full protection, diminished protection and
lost protection for all phases. A form C relay for remote alarm indication,
audible trouble alarm with test and silence switch are also standard
equipment. 

The system is comprised of three sections; outer housing, cover plate
and inner module.  Each section is engineered to make the installer/ser-
vice technician's task as easy as possible.  A description of each section
and the function follows.

Outer Housing - Metal housing measuring 20" wide x 16" high x 6"
deep. The outer housing contains the inner housing. connection lugs for
each phase, neutral and ground, connections for the form C alarm relay
and the audible alarm test and silence switch.  

A 5/8" flange on the forward side of the housing has ten (10) threaded

holes that are used to attached the cover plate.  Four (4) mounting holes
are located in the back surface of the housing for mounting.  It is sug-
gested that all four (4) fasteners be used to secure the outer housing.

Cover Plate - Metal plate measuring 19 13/16" wide x 15 13/16" high.
The cover plate contains ten (10) holes located around the edges that
matched the threaded holes in the outer housing and are used to secure
the cover plate to the outer housing.  The cover plate is reversible and
has an identification label on both front and reverse sides. The labels
are mirror images of each other and selection of which side to use
depends upon the placement of the outer housing. (This process will be
explained in the installation section that follows.)

Inner Module - Metal box measuring 13 3/16" wide x 9 3/4" high x 4
15/16" deep including the mounting rails that are part of the module.
The inner module is fastened to the outer housing with four (4) bolts
through the mounting rails.  Module identification and wiring diagram
labels are attached to the inner module.  The inner module contains all
of the surge suppression, noise filtering, fusing, monitoring and reporting
components.  Copper bus bars and terminal lugs extend from the inner
module.  

NEC Section 285 requires that a SPD have a fault current rating equal
to or greater than the point of installation (switchboard or panelboard).
The PG60-80-100 Series is suitable for use on a circuit capable of deliv-
ering not more than 200,000 amperes (120/208-3Y, 120/240-2S,
120/240-3HLD, 277/480-3Y models).  480-3D models are rated at
25,000 amperes.  Should you require a 480-3D model with a higher fault
current rating consider Intermatic PG2500/PG3000/PG3500 Series
which are rated at 200 kAIC.

S

UPPLY

V

OLTAGE AND

 C

ONFIGURATION

240-2S

120/240 Single Phase 

208-3Y

120/208 Three Phase Wye 

240-3HLD 120/240 Three Phase H. L. Delta 
480-3Y

277/480 Three Phase Wye 

480-3D

480 Three Phase Delta

P

EAK

 S

URGE

 R

ATING

PG60

60 kA per Mode

PG80

80 kA per Mode

PG100

100 kA per Mode

Model #  PG100 - 208 - 3Y

INSTALLATION INSTRUCTIONS and OPERATIONS MANUAL

PG60-80-

100 SERIES  -  V.10-03

ALARM

OPERATION

PROTECTION MODES

CAUTION; HIGH VOLTAGE INSIDE

SEVICE BY QUALIFIED PERSON NEL ONLY

Red ALARM light ON or 
Audible Alarm ON indicates 
loss of protection.  Refer to 
the operation manual for 
troubleshooting help.

Alarm

Neutral

L1

L2

L3

L1

L2

L3

Ground

Green lights ON indicate 
power present and protec- 
tion circuits for each mode 
are operating propely. 
One or more Green lights 
OFF indicates loss of power 
or protection. Refer to the 
operation manual for 
troubleshooting help.

20.0”

6.0”

16.0”

TEN YEAR LIMITED PRODUCT WARRANTY

For

Intermatic PG60-80-100 Series

SURGE PROTECTION DEVICES

(1) What Is Covered By This Limited Warranty

Repair or Replacement of Product

Intermatic Incorporated ("Intermatic") warrants to the original purchaser only, the Intermatic model PG60-240-2S, PG60-208-3Y,
PG60-240-3HLD, PG60-480-3Y, PG60-480-3DLL, PG80-240-2S, PG80-208-3Y, PG80-240-3HLD, PG80-480-3Y, PG80-480-3DLL,
PG100-240-2S, PG100-208-3Y, PG100-240-3HLD, PG100-480-3Y and PG100-480-3DLL,  PanelGuard® Surge Protection Devices
(each a "Product") shall be free from defects in material or workmanship for a period of ten years (120 months) from date of pur-
chase or 126 months from date of manufacture.  If the purchaser discovers a defect in material or workmanship, the purchaser must
promptly submit a warranty claim.  Upon a determination by Intermatic that the Product is defective, Intermatic shall correct any
defect in material or workmanship by, at Intermatic's option, either repairing or replacing the defective Product.  Any repair, including
both parts and labor, shall be at Intermatic's expense.  The foregoing remedies are the purchaser's exclusive remedies for a breach
of warranty.  

For purposes of this Limited Warranty, a Power Transient shall mean over-voltage resulting from momentary voltage spikes or
surges on an AC power line of magnitude that the Product, according to its specifications, is designed to stop before such spikes or
surges affect downstream equipment. 

The Product must be installed in the appropriate application in complete accordance with the installation instructions.  All building
wiring and other connections to the Product must conform to all applicable national, state and local electrical codes; the Product
must not be opened, modified, exposed to extreme heat or cold, submerged or subjected to abnormal use or service.  All products
must be used in accordance with the instructions provided with the Product and the purchaser shall be solely responsible for select-
ing a Product model with specifications appropriate for the equipment to be protected.  Intermatic shall determine, in its sole discre-
tion, whether any Product returned by a purchaser has been used in accordance with its instructions, is an appropriate model for the
purchaser's use thereof, and whether the Product is defective.  

(2) What Is Not Covered By This Warranty  

Intermatic does not warrant (a) defects in the Product or damage to any equipment caused by the failure to properly install the
Product; (b) damage caused by use of the Product for purposes other than those for which it was designed; (c) damage caused by
disaster such as fire, flood and wind; (d) damage caused by unauthorized attachments or modification of the Product; (e) damage to
the Product occurring during shipment; (f) damage caused by electrical disturbances exceeding published product specifications or
(g) damage to the Product caused by any other abuse or misuse by the purchaser.

(3) Disclaimer of Warranty

THE FOREGOING WARRANTIES ARE IN LIEU OF ALL OTHER EXPRESSED WARRANTIES.   TO THE EXTENT ALLOWED BY
LAW, ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ARE LIMITED IN
DURATION TO THE DURATION OF THIS LIMITED WARRANTY.

(4) Limitation of Remedies

IN NO CASE SHALL INTERMATIC BE LIABLE FOR ANY SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES BASED
UPON BREACH OF WARRANTY, BREACH OF CONTRACT, NEGLIGENCE, STRICT TORT, OR ANY OTHER LEGAL THEORY.
SUCH EXCLUDED DAMAGES INCLUDE, BUT ARE NOT LIMITED TO, DAMAGE TO SOFTWARE, LOSS OF DATA, LOSS OF
PROFITS, LOSS OF SAVINGS OR REVENUE, LOSS OF USE OF THE PRODUCT OR ANY ASSOCIATED EQUIPMENT, COST
OF CAPITAL, COST OF ANY SUBSTITUTE EQUIPMENT, FACILITIES OR SERVICES, DOWNTIME, THE CLAIMS OF THIRD
PARTIES INCLUDING CUSTOMERS, DAMAGE TO PROPERTY AND PERSONAL INJURY.  SOME STATES DO NOT ALLOW
LIMITS ON WARRANTIES OR ON REMEDIES FOR BREACH IN CERTAIN TRANSACTIONS.  IN SUCH STATES, THE LIMITS IN
THIS PARAGRAPH AND IN PARAGRAPH (3) MAY NOT APPLY.

(5) Time Limit for Bringing Suit 

No action arising out of any claimed breach of warranty may be brought more than one year after the cause of action has occurred.

(6) No Other Warranties  

Unless modified in writing signed by both parties, this agreement is understood to be the complete and exclusive agreement
between the parties, suspending all prior agreements, oral or written, and all other communications between the parties relating to
the subject matter of this aggreement. No employee of Intermatic or any other partyis authorized to make any warranty in addition to
those made in this aggreement.

INTERMATIC INCORPORATED

SPRING GROVE, ILLINOIS

http://www.intermatic.com

158PG11953

FINAL CHECKOUT PROCEDURE

1.

CHECK all connections for correct location and torque.

2.

Make sure that the electrical panel and the SPD are clear of all tools, metal parts and personnel.

3.

Turn power ON to the electrical panel.

4.

Place Alarm Switch in the NORMAL position.

5.

Turn the power ON to the SPD.

6.

Check all PROTECTION STATUS Line indicator lights for proper illumination.

PROTECTION MODE indicators ON.
ALARM indicator OFF.

7.

Check output continuity for the Alarm Relay if used. 

(a) Common to Normally Open = greater than 10 M ohms, (b) Common to Normally Closed = 0 ohms.

8.

The Audible Alarm should be silent.

9.

Place Alarm Switch in SILENCE position: Audible alarm should sound. Return Alarm Switch to normal position. 

10. Place Alarm Switch in TEST position. Audible alarm should sound, the Red Alarm Indicator LED should be ON and the alarm relay

outputs should reverse state. Return the switch to the NORMAL position.

OPERATION

1.

The ALARM SWITCH should be in the NORMAL position for standard operating conditions.

2.

The COVER PLATE must be in position with all bolts secured to prevent access by unauthorized  personnel.

3.

The PROTECTION MODE indicator lights should be ON. 

4.

The ALARM indicator light should be OFF.

5.

Periodic functional checks of the system as required by local codes or procedures are conducted by performing steps 9 and 10  of
the FINAL CHECKOUT PROCEDURE. 

INSTALLATION INSTRUCTIONS and OPERATIONS MANUAL

5

PG60-80-100 SERIES  -  V.10-03

COVER PLATE INSTALLATION

The cover plate has labels on the front and back.
One side has the labels positioned for use when
the SPD is located at the top of the electrical
panel.  The second side of the cover plate is used
when the SPD is positioned at the bottom of the
electric panel.  MAKE SURE THAT THE PROPER
SIDE IS PLACED FORWARD AND ALL INDICATOR
LIGHTS ARE VISIBLE.

SPD mounted above the Panelboard
1.

Position the cover plate on the face of the outer

housing so that the mounting holes align with the
threaded holes and the indicator light positions in the
label align with the indicator lights in the inner mod-
ule.  
NOTE: In this application, the label with the LED indi-
cators will be at the top of the cover plate.

SPD mounted under the Panelboard
1.

Position the cover plate on the face of the outer

housing so that the mounting holes align with the
threaded holes and the indicator light positions in the
label align with the indicator lights in the inner mod-
ule.  
NOTE: In this application, the label with the LED indi-
cators will be at the bottom of the cover plate.

TECHNICAL ASSISTANCE

For application or technical assistance contact
Intermatic at 1-800-391-4555 or on the web at
www.intermatic.com.

Figure 6

TYPICAL INSTALLATIONS

circuit breaker

Alarm relay

wiring area

Alarm relay

wiring area

Ground bus

Wire pass-

through areas

Wire pass-

through areas

Neutral bus

Neutral bus

Main breaker

Main breaker

INSTALLA

TION INSTRUCTIONS and OPERATIONS MANUAL

2

PG60-80-

UNPACKING 

Open the carton, remove the PG60 - 100 Series unit and examine the outer housing and cover for shipping damage.  If damage is

observed, notify your supplier.  

Remove the cover plate by removing the ten (10) bolts that secure it and examine the inner housing, bus bars, connecting lugs and

the alarm device for shipping damage.  If damage is observed, notify your supplier.

BEFORE INSTALLA

TION

1.

All electrical wiring and connections should be installed by a

qualified electrician.  All wiring must comply with the National

Electrical Code (NEC) and local codes.

2.

This Surge Protection Device (SPD) incorporates a NEMA12

enclosure. 

3.

The installation and operation of any Surge Protection Device

(SPD) requires  proper grounding.  A

properly sized, insulated

grounding conductor is required.  The grounding conductor should be

the same wire size (gauge) as the phase and neutral conductors

used for the SPD. Refer to T

able 2 for recommendations.

4.

The service entrance and panel grounding configurations must

comply with the National Electrical Code and all local codes.

3.

Select a location opposite the incoming feed to the panelboard.

The SPD must be mounted in an area that provides sufficient work

-

ing space around the panelboard and SPD cabinet.

5.

The collar and/or conduit used to connect this SPD to the panel-

board must be sized correctly for the gauge and length of wire

required.  The length of conduit should allow no more than 1/16”

between the edge of the SPD cover plate and the panelboard cover. 

6.

TESTand verify system voltage to assure proper selection of

the Surge Protection Device (SPD) in accordance with the wiring dia-

grams shown below and on the labels located on the inner module.

If the voltage or the number of conductors does not agree with the

information supplied with the Surge Protection Device, contact your

supplier.  If you have questions about the proper use of this unit for

your application, contact Intermatic at the numbers listed under

TECHNICAL

ASSISTANCE on page 5 of this publication. 

PG60 - PG80 - PG100 Series

with cover plate removed. Unit in position

to be installed at the top of panelboard.

BUS BARS AND TERMINAL

LUGS ARE ENERGIZED

DURING NORMALOPERA

TING CONDITIONS. ONLY

A

QUALIFIED PERSON SHOULD PERFORM SERVICE.

WARNING

Wire  

Pass-

through 

area

Wire Pass-through area

Low voltage alarm

contact wiring area

AC Voltage wiring area

REAR

FRONT

20.0”

6.0”

9.195”

1.980”

3.438”

3.438”

5.75”

T able 1

INSTALLA

TION (above panelboard)

1.

Turn OFF and LOCK the electric power supply to the panel

-

board. 

2.

SELECTthe location where the Surge Protection Device

(SPD) will be mounted, above or below the electric panel.

Position the SPD adjacent to the electric panel with the bus bars

pointed toward the panel.  NOTE: If the SPD is mounted below

the electric panel, the labels on the inner housing will be invert-

ed.  Refer to INVERTED INST

ALLATION section below for infor

-

mation regarding the inverted installation. Align the SPD to allow

1/16” between the SPD cover plate and the cover of the panel-

board.  The SPD should be secured to a flat vertical surface that

can support the weight of the device.  

3.

T emporarily fasten the SPD to the vertical surface and mark

the location where a hole for the collar or conduit will enter.

Refer to T

able 1 for acceptable locations on the bottom of the

Outer Housing that can be drilled for wire entry.  Note that wiring

for the remote monitoring relay enters separate from the AC

power leads.  Remove the SPD unit and drill a hole of sufficient

size to accept the collar or conduit connector. 

Attach the collar or

connector to the SPD outer cabinet and mount the unit with the

collar or connector inserted into the knockout in the panelboard.

4.

Use the proper gauge wire to connect each of the lugs on

the SPD to the appropriate points on the electric panel.  See

T able 2  for recommended wire and breaker sizes. 

Use of a ded-

icated circuit breaker is optional since the SPD has integral

overcurrent fusing.

The SPD can be connected through feed-

thru lugs on a panelboard.  The SPD can be connected through

a breaker or direct tapped for Switchboard installations.Select a

position for the connection that results in the shortest lead

lengths between the SPD and the power bus.  Leads should be

kept as short as possible to insure optimum operation.  Measure

and cut all leads to proper length. Strip the ends of each lead

9/16" for the SPD terminal lugs and to proper length for the

breaker used. Connect the wire leads to the lugs on the bus

bars of the SPD.  T

orque the lugs 35 to 50 inch pounds per UL

486 torque tightening requirements.

NOTE:For safety

, observe proper wire marking 

conventions; BLACK for HOT , RED for HOT HIGH 

LEG, WHITE for NEUTRAL, GREEN for GROUND.

5.

Route the wire lead bundle through the collar or connecter

into the electric panel.  

6.

Connect the GROUND (green) lead to the ground bus in

electric panel. 

7.

If used, connect the NEUTRAL(white) to the neutral bus in

the electric panel. If installing at a main electrical panel, the neu-

tral and ground leads could terminate at a common bus bar in

the panel. 

8.

Connect the phase leads to the appropriate breaker in the

electric panel. 

NOTE:For HIGH LEG DEL

TA, make certain that the  

high leg is connected to the center bus bar position in 

the SPD. (Refer to Figure 3)

9.

Connect wires to the alarm relay leads if used. Alarm wires

should be routed through a hole in the outer housing that is sep-

arate from the power leads. If the alarm relay is not used, leave

the wires in the low voltage section, they will have no power and

do not need to be capped.  Refer to the alarm wiring drawings

on page 3 or on the wiring label on the inner housing for wire

designation. 

10.

CHECK all connections for correct torque.

INSTALLA

TION INSTRUCTIONS and OPERATIONS MANUAL

3

PG60-80-100 SERIES  -  V .10-03

277/480 VAC Three Phase W

ye

Figure 4

PG60-480-3Y

PG80-480-3Y

PG100-480-3Y

L1

L2

L3

N

G

Line to Line: 480v.; Line to Neutral: 277v

.; Line to Ground: 277v.

120/240 VAC Three Phase

High Leg Delta

Figure 3

PG60-240-3HLD

PG80-240-3HLD

PG100-240-3HLD

L1

L2

L3

N

G

Line to Line: 240v.; Line to Neutral: 120v

.; Line to Ground: 120v. 

** High Line to Neutral: 208v.; High Line to Ground: 208v

.

**

120/208 VAC Three Phase W

ye

Figure 2

PG60-208-3Y

PG80-208-3Y

PG100-208-3Y

L1

L2

L3

N

G

Line to Line: 208v.; Line to Neutral: 120v

.; Line to Ground: 120v.

PG60-240-2S

PG80-240-2S

PG100-240-2S

120/240 VAC Single Phase

L1

L2

N

G

Line to Line: 240v.; Line to Neutral: 120v

.; Line to Ground: 120v.

Figure 1

480 VAC Three Phase Delta

Figure 5

PG60-480-3DLL

PG80-480-3DLL

PG100-480-3DLL

L1

L2

L3

G

Line to Line: 480v.;  Line to Ground: 480v

.

INSTALLA

TION INSTRUCTIONS and OPERATIONS MANUAL

4

PG60-80-100 SERIES  -  V .10-03

Brown - c

Brown - c

Violet - n/c

Orange - n/o

Orange - n/o

Violet - n/c

Normal operating condition - relay energized

Alarm condition - relay not

energized

Figure 6

ALARM RELAY

CONNECTIONS

ALARM CONDITIONS

Alarm sounding and relay in "alarm state"

1.

The audible alarm will sound and the alarm relay output

will reverse state upon the loss of one or more protection com-

ponents. 

2.

CAUTION: The following steps should be performed only

by qualified personnel. Remove the ten (10) bolts holding the

cover plate in place.

3.

Move the Alarm Switch to the SILENCE position. 

The local

audible alarm should silence but the alarm relay output should

remain in the alarm condition until the unit is returned to normal

operating condition.

4.

Verify that the proper voltage is present at each of the ter

-

minal lugs.  CAUTION: LINE VOLT

AGE MAY

BE PRESENTA

T

THE TERMINAL

LUGS. 

5.

Turn the breaker OFF and then ON to reset the SPD.

6.

If the alarm condition will not clear upon reset and the line

voltages are present and are of the correct value, contact

Intermatic TECHNICAL

ASSISTANCE at the number given on

page 5 of this publication.

Alarm not sounding but relay in "alarm state"

1.

The  alarm relay output will change state but the audible

alarm will not sound under the following conditions:

a) Loss of power to the PG Series unit.

b) The circuit breaker in the electric panel that is feeding  

the SPD is turned to the OFF position or tripped.

c) A

fault exists in the remote monitor system.

2.

Check for PROTECTION STA

TUS indicator light illumina-

tion. If all of the Line indicator lights are ON and the Alarm indi

-

cator light is OFF , consult directions for trouble shooting the

remote monitoring system.

ALARM RELAY

SPECIFICATIONS 

Relay:

Single pole double throw.

Power Rating:120 V

AC - 500 mA

24 VAC - 1 

A.

Operation:

Energized during normal conditions.

De-energized during alarm conditions or loss 

of power.

INVERTED INSTALLA

TION  (under panelboard)

1.

Turn OFF and LOCK the electric power supply to the panelboard. 

2.

SELECTthe location where the Surge Protection Device (SPD) will

be mounted below the electric panel.  Position the SPD adjacent to the

electric panel with the bus bars pointed toward the panel.  NOTE: The

labels on the inner housing will be inverted.  Align the SPD to allow

1/16” between the SPD cover Plate and the cover of the panelboard.

The SPD should be secured to a flat vertical surface that can support

the weight of the device.  

3.

T emporarily fasten the SPD to the vertical surface and mark the

location where a hole for the collar or conduit will enter.  Refer to 

T able

1 for acceptable locations on the bottom of the Outer Housing that can

be drilled for wire entry.  Note that wiring for the remote monitoring relay

enters separate from the AC power leads.  Remove the SPD unit and

drill a hole of sufficient size to accept the collar or conduit connector

.

Refer to T

able 2 for suggested collar or conduit sizes.  Attach the collar

or connector to the SPD outer cabinet and mount the unit with the collar

or connector inserted into the knockout in the panelboard.

4.

Use the proper gauge wire to connect each of the lugs on the SPD

to the appropriate points on the electric panel.  See T

able 2  for recom-

mended wire and breaker sizes. Use of a dedicated circuit breaker is

optional since the SPD has integral overcurrent fusing.

The SPD can

be connected through feed-thru lugs on a panelboard.  The SPD can be

connected through a breaker or direct tapped for Switchboard installa-

tions.Select a position for the connection that results in the shortest

lead lengths between the SPD and the power bus.  Leads should be

kept as short as possible to insure optimum operation.  Measure and cut

all leads to proper length. Strip the ends of each lead 9/16" for the SPD

terminal lugs and to proper length for the breaker used. Connect the

wire leads to the lugs on the bus bars of the SPD.  T

orque the lugs 35 to

50 inch pounds per UL486 torque tightening requirements.

NOTE:For safety

, observe proper wire marking conventions;

BLACK for HOT , RED for HOT HIGH LEG, WHITE for NEUTRAL,

GREEN for GROUND.

5.

Route the wire lead bundle through the collar or connecter into the

electric panel.  

6.

Connect the GROUND (green) lead to the ground bus in electric

panel. 

7.

If used, connect the NEUTRAL(white) to the neutral bus in the

electric panel. If installing at a main electrical panel, the neutral and

ground leads could terminate at a common bus bar in the panel. 

8.

Connect the phase leads to the appropriate breaker in the electric

panel. 

NOTE:For HIGH LEG DEL

TA, make certain that the high leg is con

-

nected to the center bus bar position in the SPD. (Refer to Figure

3)

9.

Connect wires to the alarm relay leads if used. Alarm wires should

be routed through a hole in the outer housing that is separate from the

power leads. If the alarm relay is not used, leave the wires in the low

voltage section, they will have no power and do not need to be capped.

Refer to the alarm wiring drawings on page 3 or on the wiring label on

the inner housing for wire designation. 

10.

CHECK all connections for correct torque.

SUGGESTED WIRE and BREAKER SIZES 

Use the following table as a guideline for the PG60, PG80 and PG100 Surge Protection Devices.  All models have integral overcurrent fusing and

the use of a dedicated circuit breaker is optional

.  Lugs accept wire sizes from 10 A

WG to 2 A

WG.  Keep all leads as short and straight as possi-

ble, avoiding sharp 90 degree bends.  Increase wire size when lead length is extended.

T able 2

10 A

WG       30 AMP

8 A

WG       40 AMP

6 A

WG        50 AMP

4 A

WG       60 AMP

2 A

WG       80 AMP

   

  

 

 

 

   

   

   

   

   

   

   

   

   

   

   

   

   

   

   

   

   

   

   

   

   

   

   

   

   

   

   

   

   

Отзывы: