background image

InstallIng the eMKB

The EMKB is a 100% digital momentary switch, avail-
able with 1 to 6 buttons per switch. It can be mounted 
in any standard switch box with a decorator style switch 
plate. This switch is NOT pre-programmed and must be 
addressed and programmed in the field.

Placement and Wiring

Connect to the digital lighting control bus using Cat. 5 
cable with RJ45 connectors. Note all items on the bus 
must be “daisy chained” and the beginning and end 
items on the bus must have a terminator. If this is being 
added to the bus in the middle this is not a problem. If 
added at the end of the bus make sure the terminator 
is removed from the previously last item to the new last 
item on the bus. 

If the ON LINE LED is not flashing re-check connections 

and crimps. 

Address and define per instructions in the EM1400 

Quick Hook-Up Guide and System and Software Start-

Up Manual. This would be defined as a (Number of 

Butons) button switch in the “PANEL SWITCH TYPES” 
Menu. 

Program the switch to control the appropriate loads. The 
Switch will be shown in the PROGRAM SWITCH menu. 
For more complete details on programming switches 
see the O & M Manual.

1.

2.

3.

4.

eMKB

DIgItal sWItCh

InstallatIOn

guIDe

lIghtIng COntROl eQuIPMent

InteRMatIC InCORPORateD • http://www.intermatic.com

EMKD4 Shown

Reviews: