background image

 

 

  

  

  

  

  

 

 

 

 

 

Intel® Server Board S7200AP/APR 

Intel® Compute Module 

HNS7200AP/APR  

Product Family  

System Integration and Service Guide 

A document providing instruction on installation and removal of subassemblies.  

  

  

 

 

 

 

 

 

 

 

 

 

 

 

 

Revision 1.1  

April 2018 

 

Datacenter Systems Group 

Summary of Contents for HNS7200AP

Page 1: ...200AP APR Intel Compute Module HNS7200AP APR Product Family System Integration and Service Guide A document providing instruction on installation and removal of subassemblies Revision 1 1 April 2018 Datacenter Systems Group ...

Page 2: ... This page is intentionally left blank ...

Page 3: ...7 0 8 Update with Adams Pass Refresh information Jan 2018 1 0 Update Processor Information image modifications warnings updated April 2018 1 1 Updated Intel Xeon Phi x205 Product Family CPUs to official marketing name of Intel Xeon Phi 72x5 Product Family CPUs ...

Page 4: ... in trade This document contains information on products services and or processes in development All information provided here is subject to change without notice Contact your Intel representative to obtain the latest The products and services described may contain defects or errors known as errata which may cause deviations from published specifications Current characterized errata are available...

Page 5: ...ignes de sécurité Lisez attention toutes les consignes de sécurité et les mises en garde indiquées dans ce document avant de suivre toute instruction Consultez Intel Server Boards and Server Chassis Safety Information sur le site http www intel com support motherboards server sb cs 010770 htm Instrucciones de seguridad importantes Lea todas las declaraciones de seguridad y precaución de este docum...

Page 6: ... Do not to energize or power up any server node if the liquid cooling system is compromised in any way To reduce risk of damage to the cooling system use care when installing or removing server nodes Avoid excessive force when connecting disconnecting quick disconnects Keep cooling tubing clear of pinch points when sliding server nodes Installing or removing jumpers A jumper is a small plastic enc...

Page 7: ...s before performing any integration or service Hold all circuit boards and other electronic components by their edges only After removing electronic devices from the system or from their protective packaging place them component side up on to a grounded anti static surface or conductive foam pad Do not place electronic devices on to the outside of any protective packaging ...

Page 8: ...es provides a high level overview of the Intel Compute Module HNS7200AP In this chapter you will find a list of the compute module features and illustrations identifying the major compute module components Chapter 2 Hardware Installations and Upgrades provides instructions on adding and replacing the components Use this chapter for step by step instructions and diagrams for installing or replacing...

Page 9: ...on For product list and supported Intel spares and accessories Spares and Accessories List and Configuration Guide For server configuration guidance and compatibility Intel Server Configurator tool http serverconfigurator intel com For system power budget guidance Power Budget Tool http www intel com support Product Safety and Regulatory document Intel Server Products Product Safety and Regulatory...

Page 10: ...13 2 2 Cable Routing 13 2 3 Removing and Installing the Air Duct 14 2 3 1 Removing the Air Duct 14 2 3 2 Installing the Air Duct 15 2 4 Processor Assembly Installation and Removal 16 2 4 1 Assembling the Processor Heat Sink Module PHM 16 2 4 2 Processor Installation 22 2 5 Processor Removal 26 2 5 1 PHM Disassembly 27 2 6 Installation and Removal of the 1U LACC 29 2 6 1 Removal of the 1U LACC Asse...

Page 11: ... Board 57 2 15 1 Removing the Power Docking Board 57 2 15 2 Installing the Power Docking Board 57 2 16 Replacing the Fan 58 2 16 1 Removing the Fan 58 2 16 2 Installing the Fan 58 2 17 Replacing the Backup Battery 59 2 18 Installing and Removing the Intel Trusted Platform Module 60 2 18 1 Installing the TPM 60 2 18 2 Removing the TPM 60 2 19 Installing and Removing the VGA Video Debug Cable 61 2 1...

Page 12: ...Appendix D System Interconnects S7200AP H2000G 78 Appendix E Regulatory and Compliance Information 79 Appendix F Getting Help 80 Warranty Information 80 Glossary 81 ...

Page 13: ...3 Figure 25 PHM Alignment to Bolster Plate 24 Figure 26 Correct Placement 25 Figure 27 Installing the PHM 25 Figure 28 Uninstalling the PHM 26 Figure 29 Plastic processor socket cover Installation 26 Figure 30 PHM Disassembly 27 Figure 31 Releasing the Processor Carrier Clip from the Heat Sink 27 Figure 32 Releasing Processor from Carrier 28 Figure 33 1U LACC Assembly 29 Figure 34 1U LACC Assembly...

Page 14: ...nections 50 Figure 71 Disconnecting IFP Cables 51 Figure 72 Installing the Memory 52 Figure 73 Installing the Intel RMM4 Lite 53 Figure 74 Installing the Bridge Board 54 Figure 75 Removing the Bridge Board 54 Figure 76 Removing the Cable Connections from the Server Board 55 Figure 77 Removing the Server Board 55 Figure 78 Installing the Server Board 56 Figure 79 Connecting all Cables 56 Figure 80 ...

Page 15: ...y Feature Set 6 Table 5 Processor Carriers 17 Table 6 Processor Heat Sinks 22 Table 7 BIOS Setup Keyboard Command Bar 64 Table 8 System Environmental Limits Summary 66 Table 9 POST Progress Code Decoding LED Example 68 Table 10 MRC Fatal Error Codes 69 Table 11 MRC Progress Codes 70 Table 12 POST Progress Codes 71 Table 13 POST Error Codes and Messages 75 Table 14 POST Error Beep with LED Codes 77...

Page 16: ......

Page 17: ...ures and diagrams showing the location of important components and connections The two main boards are described in this document to include support for several chassis The document includes updates for Intel Server Board S7200APR refresh product that is supported in the Intel Server Chassis H2204XXLRE Figure 1 Intel Compute Module HNS7200AP Product Family Figure 2 Intel Server Board S7200AP Produ...

Page 18: ... TDP up to 230W 36 lanes of Integrated PCI Express 3 0 low latency I O Memory Support Six DIMM slots in total across six memory channels Registered DDR4 RDIMM Load Reduced DDR4 LRDIMM Memory DDR4 data transfer rates of 2400 2666 MT s 1 DIMM per channel Max memory 384GB Chipset Intel C610 Wellsburg Platform Controller Hub PCH External I O Connections Two USB 3 0 connectors Two RJ 45 10 100 1000 Mbi...

Page 19: ...Manager NOTE The Riser Slot 1 on the server board is designed for plugging in ONLY the riser adapter Plugging in a PCIe adapter directly into the riser slot may cause permanent server board and or PCIe card damage 1 1 2 HNS7200AP Compute Module Feature Set Table 2 Intel Compute Module HNS7200AP Product Family Feature Set Feature1 Description Server Board Intel Xeon Phi x200 Product Family Single p...

Page 20: ...de Support Intel Compute Module options HNS7200AP up to four Power Supply 2 x 2130W AC CRPS System Cooling 3 dual rotor 40 x 56 mm fixed fans per node PCIe support Two low profile PCIe cards on riser 1 and 2 Storage 8 x 2 5 SATA drive Note 2 5 SATA HDD installed in the 3 5 Drive Carrier 16 x 2 5 SATA drives Bridge Board Options 1 6G SATA only RAID 0 1 10 SW RAID ESRT2 System SKUs Support for H2312...

Page 21: ...d Connector One 2x7 pin header for system fan module One Aux Front Panel Connector Three 8 pin fan headers for third party chassis support One 4 pin CPU fan or liquid cooling pump support header One PSU Control Header One RMII header for Intel RMM4 Lite One internal RGB Video Header One Serial Port A Header PCIe Support PCIe 3 0 2 5 5 8 GT s Power Connections One 2x4 pin main power connector One 2...

Page 22: ...I O Intel Xeon Phi x200 Product Family Single processor socket P 3647 pins Thermal Design Power TDP up to 230W Air Cooled Heatsink 36 lanes of Integrated PCI Express 3 0 low latency I O CPUs with Integrated Intel Omni Path Fabric supported Processor TDP Support Maximum supported Thermal Design Power TDP of up to 320W Heatsink One 80x107mm 1U Heatsink CPUs 245W TDP Liquid Assisted Air Cooling LAAC ...

Page 23: ...ATA HDD installed in the 3 5 Drive Carrier Bridge Board Options 1 6G SATA only RAID 0 1 10 SW RAID ESRT2 System SKUs Supported for H2204XXLRE chassis only Note Intel Compute Module HNS7200APR is not supported in Intel Server Chassis H2312XXLR2 and H2216XXLR2 For additional details on chassis features refer to the Intel Server Chassis H2000G Product Family TPS 1 2 Back Panel Feature Identification ...

Page 24: ...x6 pin Minifit Jr main power output connector D 8 pin connector for fan 2 E 12 pin connector for main power input F 8 pin connector for fan 3 Figure 5 Power Docking Board Features 1 4 Bridge Board Feature Features Label Description A 2x40 pin card edge connector to the backplane B 2x40 pin card edge connector to the baseboard slot Figure 6 6G SATA Bridge Board Features ...

Page 25: ...u identify the components and connectors on the server board Intel Server Board S7200AP features shown All major features that are called out are common to both boards Figure 7 Intel Server Board S7200AP Features Figure 8 Intel Server Board S7200APR ...

Page 26: ...te off green red and amber according to the POST sequence The Status LED on the rear of the board shows the overall health of the system green blinking green blinking amber amber and off The Identification LED on the rear of the board helps identify the server from among several servers The ID LED is off by default and blue when activated by button or software ...

Page 27: ...e Update Mode is enabled These pins should be selected on 1 2 for normal system operation BIOS Default J2B1 If pins 2 3 are selected the BIOS settings are restored to the factory defaults on the next reset These pins should be selected on 1 2 for normal system operation BIOS Recovery If the system BIOS is corrupted an onboard backup copy of the BIOS can be loaded using the BIOS ...

Page 28: ... pins should be selected on 1 2 for normal system operation 1 8 Advanced Management Options 1 8 1 Intel Remote Management Module 4 Lite The Intel Remote Management Module 4 Lite plugs into a dedicated connector on the server board and provides additional server management functionality to the compute module The Intel Remote Management Module 4 Lite together with the dedicated management port provi...

Page 29: ...nd bottom assume that the reader is facing the front of the chassis as it would be positioned for normal operation 2 2 Cable Routing Each compute module is self contained and can be hot swapped without any impact to other compute modules When you add or remove components from the compute module enclosure ensure that cables are routed correctly before plugging in the compute module back into the ch...

Page 30: ... proper airflow within the compute module Intel Server Board S7200AP Section 2 3 applies to both server compute module 2 3 1 Removing the Air Duct 1 Press and hold both the left and right side buttons of the air duct See letter A 2 Rotate the air duct more than 45 degrees and pull it out See letter B Figure 12 Removing the Air Duct ...

Page 31: ...ed before installing the air duct 1 Align the front end of the air duct with the hinges on both sides of the fan bracket See letter A 2 Rotate the air duct See letter B and lower it down until the left and right side buttons snaps into place Figure 13 Installing the Air Duct ...

Page 32: ...properly assemble the PHM install it to or remove it from the server board These instructions assume that all the PHM components are new and the thermal interface material TIM is already applied to the bottom of the heat sink Required Tools T 30 Torx screwdriver Flat head screwdriver Adequate ESD protective gear wrist strap ESD mat CAUTION Refer to the Warning section at the beginning of this docu...

Page 33: ...able and figures for an overview of the different processor carrier and processors Table 5 Processor Carriers Carrier Clip Model iPN Carrier Clip Assembly Standard Processor Carrier Default Included with Systems H53249 00x Fabric Processor Carrier Accessory H53248 00x NOTE For reference only Intel part numbers iPN are not used for ordering purposes Intel parts that are available as a Spare or Acce...

Page 34: ...or Heat Sink on to a Flat Surface CAUTION Do not touch the sensitive contacts on the bottom side of the processor at any time during PHM assembly or installation In addition the pins inside the processor socket are extremely sensitive A damaged processor socket may produce unpredictable system errors 2 If present carefully remove the plastic protective cover from the bottom side of the processor N...

Page 35: ...Figure 18 Alignment Features CAUTION Handle the processor carefully Do not touch the bottom side contacts or components always grip the processor by its edges ...

Page 36: ...processor carrier clip until it snaps into place Figure 20 Processor Carrier Clip Sub Assembly CAUTION A processor can dislodge from the processor carrier clip if the assembly is grasped by the long narrow edges of the processor clip The processor carrier assembly should only be grasped using the shorter edges of the assembly 5 If present remove the protective film covering the TIM on the bottom s...

Page 37: ...l corner features are in alignment Figure 21 Orienting Processor Carrier Clip Sub assembly to Heat Sink 7 Push the processor carrier clip sub assembly down on to the processor heat sink until it snaps into place ensuring all four corners are secure Figure 22 Processor Heat Sink Module PHM ...

Page 38: ...2 4 2 Processor Installation Table 6 Processor Heat Sinks Intel Product Code iPC MM Description iPC AXXAPHS MM 942344 1U Standard Ex Al 80mm x 107mm Heat Sink Figure 23 Processor Heat Sink Location ...

Page 39: ...over removal NOTE The processor socket cover should be saved for future use CAUTION When re installing the socket cover make sure it properly snaps into place Improper installation will cause it to become loose and damage the processor socket 2 Install PHM to Processor socket a Align the mounting holes of the PHM located on diagonal corners to the bolster plate guide pins of the processor socket a...

Page 40: ...nly one orientation when installed as shown in the following figure Look for the wide and narrow holes for proper and accurate alignment Figure 25 PHM Alignment to Bolster Plate b Lower the PHM onto the processor socket assembly CAUTION Processor socket pins are delicate and bend easily Use extreme care when placing the PHM onto the processor socket ...

Page 41: ...e 26 Correct Placement 3 Secure PHM to the processor socket assembly a Using a T30 Torx bit screwdriver securely tighten 12 in lb each nut in the sequence shown on the label located on the top of the heat sink Follow the 1 2 3 4 sequence when tightening Tighten each screw prior to moving to the next Figure 27 Installing the PHM CAUTION Failure to tighten the heat sink screws in the specified order...

Page 42: ...he server board 1 Using a T30 Torx bit screwdriver loosen each heat sink nut in the sequence shown on the label affixed to the top side of the heat sink 4 3 2 1 See letter A Loosen each screw all the way prior to moving to the next 2 Lift the PHM straight up from the server board until free from the bolster plate guide pins See letter B 3 Figure 28 Uninstalling the PHM 4 If a processor is not bein...

Page 43: ... carefully release the bond between processor and heat sink as shown in the following illustration Figure 30 PHM Disassembly 3 Unlatch the hooks on each corner of the processor carrier clip to free the processor carrier from the heat sink 4 Carefully lift the processor sub assembly away from the heat sink Figure 31 Releasing the Processor Carrier Clip from the Heat Sink ...

Page 44: ...ssor from the processor carrier by carefully pushing back one of the latches located on the ends of the processor and rotating the processor up and out of the processor carrier Figure 32 Releasing Processor from Carrier ...

Page 45: ...id Assisted Air Cooling LACC solution for optimal thermal support The Intel Server Board S7200APR product family Technical Product Specfication TPS decribes the 1U LAAC in detail This section of the Service Guide describes the installation and removal of the 1U LACC coolling solution Note Passive Air Cooled Heatsinks are not supported on CPUs with TDPs equal to or higher than 245w regardless of th...

Page 46: ...he air duct See section 2 3 1 3 Disconnect the pump cable that is connected to the 4 pin CPU Fan Header J6J2 Figure 35 Disconnect the Pump Cable Fan Header J6J2 4 Next remove the LACC Heat Exchanger retaining brackets by removing the 4 screws Figure 36 Remove LACC brackets 1 ...

Page 47: ...bly The LACC cold plate assembly is modeled after the passive air heatsink assembly The sequence and method of removing the cold plate is exactly the same as the passive air heatsink Follow carefully the screw loosening sequence Refer to the passive air heatsink removal instructions in Section 2 5 for detail ...

Page 48: ...39 Remove Cold Plate Assembly 6 Carefully lift the LACC Assembly away from the node Use two hands to grasp the heat exchanger and cold plate to safely remove the LACC assembly Figure 40 Lift out LACC Assembly ...

Page 49: ... in Figure 41 5 The LACC cold plate assembly is modeled after the passive air heatsink assembly The sequence and method of removing the CPU and Carrier is exactly the same as the passive air heatsink This step is only required if the CPU requires replacement For simplification refer to the CPU and Carrier removal instructions in Section 2 5 for detail Figure 41 Releasing CPU and Carrier from Cold ...

Page 50: ... the passive air heatsink This step is only required if the CPU requires replacement or installation For simplification refer to the CPU and Carrier installation instructions in Section 2 4 for detail Figure 43 Install CPU and Carrier to Cold LACC Cold Plate 4 Carefully place and position the LACC assembly back into the system by using two hands Ensure that it is properly aligned and that the cold...

Page 51: ...sink assembly The sequence and method of tightening the cold plate screws is exactly the same as the passive air heatsink Follow the tightening sequence carefully Refer to the passive air cooled heatsink installation instructions in Section 2 4 for detail Figure 45 Install the LACC assembly into the system 6 Install the LACC Heat Exchanger retaining brackets by installing the 4 screws Figure 46 In...

Page 52: ...Figure 47 Install LACC brackets 2 Figure 48 Install LACC brackets 3 ...

Page 53: ...7 Connect the pump cable to the 4 pin CPU Fan Header J6J2 Figure 49 Connect the Pump Cable fan header J6J2 ...

Page 54: ... the 3 screws See A 4 Pull the riser straight up and out of the system See B and C Figure 50 Removing Riser 1 2 7 2 Install Riser 1 1 Power off the compute module and disconnect the power cable s 2 Remove the air duct See section 2 3 1 3 Align and insert Riser 1 into Riser Slot 1 See A 4 Ensure that the Riser is all the way down and fully seated See B 5 Tighten the 3 screws See C ...

Page 55: ...n the 3 screws See A 4 Pull and lift the riser straight up and out of the system See B and C Figure 52 Removing Riser 2 2 7 4 Install Riser 2 1 Power off the compute module and disconnect the power cable s 2 Remove the air duct See section 2 3 1 3 Align and insert Riser 2 into Riser Slot 2 See A 4 Ensure that the Riser is all the way down and fully seated See B ...

Page 56: ...n Card Riser 1 1 Power off the compute module and disconnect the power cable s 2 Remove the air duct See section 2 3 1 3 Remove Riser 1 See section 2 7 1 4 Remove the filler panel and attach the Add In Card to the riser card assembly 5 Insert the PCIe Add In Card into the riser slot See letter A Figure 54 Installing the PCIe Add In Card Step 1 ...

Page 57: ...1 on the server board See letter B Figure 55 Installing the PCIe Add In Card Step 2 7 Install and tighten the three screws See letter C Figure 56 Installing the PCIe Add In Card Step 3 2 8 2 Removing a PCIe Add In Card Riser 1 1 Loosen the three screws See letter A ...

Page 58: ...Card Step 1 2 Pull the Add In Card assembly up and out See letter B Figure 58 Removing the PCIe Add In Card Step 2 3 Remove the Add In Card from the riser See letter C 4 Re install the filler panel 5 Re install Riser 1 See section 2 7 2 ...

Page 59: ...CIe X8 or X16 riser for slot 2 for your configuration See the product configuration guide and technical product specification for details 1 Power off the compute module and disconnect the power cable s 2 Remove the air duct See section 2 3 1 3 Remove Riser 2 See section 2 7 3 4 Remove the filler panel and attach the Add In Card to the riser card assembly 5 Insert the PCIe Add In Card into the rise...

Page 60: ... riser assembly into the Riser Slot 1 on the server board See letter B Figure 61 Installing the PCIe Add In Card Step 2 7 Ensure that the Add In Card and Riser are fully seated See letter C 8 Tighten the three screws See letter D Figure 62 Installing the PCIe Add In Card Step 3 ...

Page 61: ... disconnect the power cable s 2 Remove the air duct See section 2 3 1 3 Loosen the three screws See letter A 4 Pull straight up on Riser 2 with the PCIe Add In Card assembly See letter B Figure 63 Removing the PCIe Add In Card Step 1 5 Lift out the PCIe Slot 2 Riser with Add In Card ...

Page 62: ...ections will provide procedures on how to install and remove the optional Intel Omni Path Fabric Processor Kit iPC AXX2PFABKIT and the Intel Xeon Phi Fabric processor The IFT Carrier card is installed in PCIe Riser Slot 1 Refer to the S7200AP Family Configuration Guide Spares Accessories List for ordering details Note The Intel Omni Path Fabric Processor Kit is not supported when Intel Xeon Phi 72...

Page 63: ...Carrier 2 10 2 Fabric Processor Kit Cables 1 The two cables are included with the kit Cables are labeled for illustration purposes Figure 67 Intel Omni Path Sideband Cable Connection Figure 68 Intel Omni Path Fabric Processor Cable ...

Page 64: ...rier ports face down in Riser Slot 1 when installed in the system Figure 69 Sideband Cable Connection 7 Install the IFT carrier card Note The IFT card should be installed in PCIe Slot 1 for normal operation with the Intel Xeon Phi Fabric processor The IFT carrier card is not supported in PCIe Slot 2 when the fabric CPU is installed When the Intel Xeon Phi Fabric processor is used in the server sys...

Page 65: ...he two IFP plugs into the IFT carrier slots on the board When installing the two plugs the latch release buttons are marked P1 and P2 will face down in the system As illustrated ensure that the connector marked P1 on the cable is inserted into the P1 connector and the P2 plug is inserted into the P2 connector See letter B Ensure that the cables are pushed fully forward and are fully engaged d At t...

Page 66: ...Figure 71 Fabric Processor and IFT Cable Connections ...

Page 67: ... carrier and the fabric processor See letter A B and C Figure 72 Disconnecting IFP Cables 2 See section 2 8 2 for instructions on how to remove the Intel Omni Path Fabric processor carrier card from Riser 1 3 See section 2 5 for instructions on how to remove the processor from the server board ...

Page 68: ... static package Place the DIMM within the DIMM slot guides Ensure the DIMM notch is aligned with the DIMM slot key See letter B 5 Insert the bottom edge of the DIMM into the socket See letter C When the DIMM is inserted push down firmly on the top edge of the DIMM until the retaining clips snap into place See letter D Ensure the retaining clips are firmly in place See letter E Figure 73 Installing...

Page 69: ...e server board next to the Riser Slot 2 5 Place the Intel RMM4 Lite over the connector and match the orientation of the Intel RMM4 Lite to that of the connector See letter A 6 Press the Intel RMM4 Lite down onto the connector Figure 74 Installing the Intel RMM4 Lite 2 12 2 Removing the Intel RMM4 Lite 1 Power off the compute module and disconnect the power cable s 2 Remove the air duct See section...

Page 70: ... end of the bridge board into the slot on the server board See letter B 5 Secure the bridge board to the side wall with the six screws See letter C Figure 75 Installing the Bridge Board 2 13 2 Removing the Bridge Board 1 Power off the compute module and disconnect the power cable s 2 Remove the air duct See section 2 3 1 3 Remove the six screws See letter A on the bridge board 4 Lift the bridge bo...

Page 71: ...6 Remove the PCIe Riser and Add In Card from the Riser Slot 2 if there is any See section 2 9 2 7 Remove the TPM if installed See section 2 18 2 8 Remove RMM if installed See section 2 12 2 9 Disconnect the cables from the server board See letter A Figure 77 Removing the Cable Connections from the Server Board 10 Remove the six screws from the server board See letter B 11 Move the board slightly f...

Page 72: ...to the compute module enclosure standoffs 3 Install and tighten the six screws See letter B Figure 79 Installing the Server Board 4 Connect all cable connections to the server board Figure 80 Connecting all Cables 5 Re install the bridge board See section 2 13 1 6 Re install the PCIe riser and Add In Card in Riser Slot 1 See section 2 8 1 7 Re install the PCIe riser and Add In Card in Riser Slot 2...

Page 73: ...ut of the enclosure See letter C Figure 81 Removing the Power Docking Board 2 15 2 Installing the Power Docking Board 1 Power off the compute module and disconnect the power cable s 2 Remove the air duct See section 2 3 1 3 Place the power docking board into the compute module base See letter A 4 Ensure that the two inside screws have the washer and are inserted first See letter B 5 Secure the pow...

Page 74: ...to release the fan 4 Grasp the fan from the top and pull it out of the fan bracket Figure 83 Removing the Fan 2 16 2 Installing the Fan 1 Remove the air duct See section 2 3 1 2 Place the fan into the fan bracket 3 After fans are seated push in on the blue rivets to secure them into the bracket 4 Connect the fan cables to the connectors on the power docking board Figure 84 Installing the Fan ...

Page 75: ...brikanten Brukt batteri returneres apparatleverandøren Explosionsfara vid felaktigt batteribyte Använd samma batterityp eller en ekvivalent typ som rekommenderas av apparattillverkaren Kassera använt batteri enligt fabrikantens instruktion Paristo voi räjähtää jos se on virheellisesti asennettu Vaihda paristo ainoastaan laitevalmistajan suosittelemaan tyyppiin Hävitä käytetty paristo valmistajan o...

Page 76: ...stalling the TPM 1 Power off the compute module and disconnect the power cable s 2 Remove the air duct See section 2 3 1 3 Remove the TPM from the package 4 Locate the TPM board connector on the rear of the server board near the internal video connector 5 Place the TPM over the board connector and ensure that the TPM connector and mounting hole is oriented correctly to the board mounting hole See ...

Page 77: ... Spares Accessories List for ordering details 2 19 1 Installing Video Debug Cable 1 Power off the compute module and disconnect the power cable s 2 Remove the air duct See section 2 3 1 3 Remove the Slot 1 Riser and the PCIe adapter if there is one installed See section 2 8 2 4 Remove the video cable from the package 5 Route the video cable through Riser 1 bracket as shown in Figure 86 Figure 87 V...

Page 78: ...emoving the Video Debug Cable 1 Power off the compute module and disconnect the power cable s 2 Remove the air duct See section 2 3 1 3 Follow the procedures to remove PCIe Riser 1 See section 2 7 1 4 After lifting Riser 1 up slightly out of the system unplug the VGA connector from the board 5 Carefully route the video cable through Riser 1 slot and out of the system 6 Re install Riser 1 and or th...

Page 79: ...BIOS Setup Guide for all BIOS supported options To enter the BIOS Setup using a keyboard or emulated keyboard press the F2 function key during boot time when the OEM or Intel Logo Screen or the POST Diagnostic Screen is displayed At initial system power on a USB keyboard will not be functional until the USB controller has been initialized during the power on self test POST process When the USB con...

Page 80: ...ed item must then be activated by pressing the Enter key Select Item The down arrow is used to select the next value in a menu item s option list or a value field s pick list The selected item must then be activated by pressing the Enter key Select Menu The left and right arrow keys are used to move between the major menu pages The keys have no effect if a submenu or pick list is displayed Tab Sel...

Page 81: ...also be executed remotely through a secure network connection using a Telnet Client and Terminal Services in Windows or using a Telnet Client and Remote Shell under Linux 4 3 Intel System Event Log SEL Viewer Utility The Intel System Event Log SEL Viewer Utility provides the ability to view system event records stored on the server management storage device of a server The utility displays the SEL...

Page 82: ...Vibration unpackaged 5 Hz to 500 Hz 2 20 g RMS random Shock and vibration packaged ISTA International Safe Transit Association Test Procedure 3A ESD 12 KV except I O port 8 KV per Intel Environmental Test Specification System Cooling Requirement in BTU Hr 2130 Watt Max 7263 BTU hour Disclaimer Note Intel ensures the unpackaged server board and system meet the shock requirement mentioned above thro...

Page 83: ...OST Code Diagnostic LEDs on the back edge of the server board During a POST system hang the displayed post code can be used to identify the last POST routine that was run prior to the error occurring helping to isolate the possible cause of the hang condition Each POST code is represented by eight LEDs four Green and four Amber The POST codes are divided into two nibbles an upper nibble and a lowe...

Page 84: ...Diagnostic LED codes displayed during memory initialization by the Memory Reference Code MRC the BIOS component responsible for it There are two types of POST Diagnostic Codes used by the MRC Fatal Error Codes and Progress Codes MRC Fatal Error Codes are necessary because if the Memory Initialization fails badly for some reason like no usable memory installed the system would not have the resource...

Page 85: ...ent RAS mode to retry 0xED DIMM Configuration Population Error 01h Different DIMM types RDIMM LRDIMM are detected installed in the system 02h Violation of DIMM population rules 03h The third DIMM slot cannot be populated when QR DIMMs are installed 04h UDIMMs are not supported 05h Unsupported DIMM Voltage 0xEF Indicates a CLTT table structure error Should a major memory initialization error occur ...

Page 86: ...n a 0xB5 Program registers on the channel level n a 0xB6 Perform the JEDEC defined initialization sequence n a 0xB7 Train DDR4 ranks n a 0x01 Read DQ DQS training 0x02 Receive Enable training 0x03 Write Leveling training 0x04 Write DQ DQS training 0x05 DDR channel training done 0xB8 Initialize CLTT OLTT n a 0xB9 Hardware memory test and init n a 0xBA Execute software memory init n a 0xBB Program m...

Page 87: ...in execution The following table provides a list of all POST progress codes Table 12 POST Progress Codes Progress Code Description SEC Phase 0x01 First POST code after CPU reset 0x02 Microcode load begin 0x03 CRAM initialization begin 0x04 Pei Cache When Disabled 0x05 SEC Core At Power On Begin 0x06 Early CPU initialization during Sec Phase 0x07 Early SB initialization during Sec Phase 0x08 Early ...

Page 88: ...I Host Bridge Init 0x69 DXE NB Init 0x6A DXE NB SMM Init 0x70 DXE SB Init 0x71 DXE SB SMM Init 0x72 DXE SB devices Init 0x78 DXE ACPI Init 0x79 DXE CSM Init 0x80 DXE BDS Started 0x81 DXE BDS connect drivers 0x82 DXE PCI Bus begin 0x83 DXE PCI Bus HPC Init 0x84 DXE PCI Bus enumeration 0x85 DXE PCI Bus resource requested 0x86 DXE PCI Bus assign resource 0x87 DXE CON_OUT connect 0x88 DXE CON_IN conne...

Page 89: ... reset 0x97 DXE SCSI detect 0x98 DXE SCSI enable 0x99 DXE verifying SETUP password 0x9B DXE SETUP start 0x9C DXE SETUP input wait 0x9D DXE Ready to Boot 0x9E DXE Legacy Boot 0x9F DXE Exit Boot Services 0xC0 RT Set Virtual Address Map Begin 0xC2 DXE Legacy Option ROM init 0xC3 DXE Reset system 0xC4 DXE USB Hot plug 0xC5 DXE PCI BUS Hot plug 0xC6 DXE NVRAM cleanup 0xC7 DXE ACPI Enable 0x00 Clear POS...

Page 90: ...ript 0x42 S3 Resume PEIM S3 Video Repost 0x43 S3 Resume PEIM S3 OS wake BIOS Recovery 0x46 PEIM which detected forced Recovery condition 0x47 PEIM which detected User Recovery condition 0x48 Recovery PEIM Recovery started 0x49 Recovery PEIM Capsule found 0x4A Recovery PEIM Capsule loaded ...

Page 91: ...to the Error Manager for this type of error so the user can take immediate corrective action or the system continues booting Note that for 0048 Password check failed the system halts and then after the next reset reboot will display the error code on the Error Manager screen Fatal The system halts during POST at a blank screen with the text Unrecoverable fatal error found System will not boot unti...

Page 92: ...Detection SPD failure Major 8563 DIMM_B1 encountered a Serial Presence Detection SPD failure Major 8566 DIMM_C1 encountered a Serial Presence Detection SPD failure Major 8569 DIMM_D1 encountered a Serial Presence Detection SPD failure Major 856C DIMM_E1 encountered a Serial Presence Detection SPD failure Major 856F DIMM_F1 encountered a Serial Presence Detection SPD failure Major 8604 POST Reclaim...

Page 93: ...a fatal error related to the CPU family core cache mismatch was detected The following Beep Codes are sounded during BIOS Recovery 2 Recovery started N A Recovery boot has been initiated 4 Recovery failed N A Recovery has failed This typically happens so quickly after recovery is initiated that it sounds like a 2 4 beep code The following beep codes are generated by the BMC Table 15 Integrated BMC...

Page 94: ...Appendix D System Interconnects S7200AP H2000G S7200AP H2000G 12x3 5 Drive Configuration and system interconnect Figure 92 System Interconnect ...

Page 95: ...egulatory and Compliance Information Refer to the Server Products Regulatory and Safety document for the product regulatory compliance reference The document can be downloaded from http www intel com support server ...

Page 96: ...s list for ordering upgrades or spare parts A searchable knowledgebase to search for product information throughout the support site 2 If you are still unable to obtain a solution to your issue send an email to Intel s technical support center using the online form available at http www intel com support feedback htm group server Lastly you can contact an Intel support representative using one of ...

Page 97: ...e DC Direct current the flow of electric charge is only in one direction DIMM Dual In line Memory Module a plug in memory module with signal and power pins on both sides of the internal printed circuit board front and back DQ Data Quality DQS Bi directional Data Strobe DXE Driver Execution Environment Component of Intel Platform Innovation Framework for EFI architecture EI Enhanced Intel ESD Elect...

Page 98: ...Module PERR Parity Error PHM Processor Heatsink Module POST Power On Self Test BIOS activity from the time on Power On until Operating System boot begins PSU Power Supply Unit QPI Intel QuickPath Interconnect QR Quad Rank memory DIMM organization DRAMs organized in four ranks RAID Redundant Array of Inexpensive Disks provides data security by spreading data over multiple disk drives RAID 0 RAID 1 ...

Page 99: ...r SFF Small Form Factor SFP The enhanced small form factor pluggable SFP is an enhanced version of the SFP that supports data rates up to 16 Gbit s SIO Super I O SMM System Management Mode SPD Serial Presence Detect SUP System Updated Package TDP Thermal Design Power TIM Thermal Interface Material TPM Trusted Platform Module TXT Intel Trusted Execution Technology USB Universal Serial Bus a standar...

Reviews: