Installation manual

SmartLevel

SPS24060S

SPS24160S

Power supply station

Installation manual

EN 54-4

EN 12094-1

0051

1438

0051-CPR-0433

0051-CPR-0434

ISO 9001 Quality Management

certified by BSI with certificate number FM530352

Содержание SmartLevel SPS24060S

Страница 1: ... manual SmartLevel SPS24060S SPS24160S Power supply station Installation manual EN 54 4 EN 12094 1 0051 1438 0051 CPR 0433 0051 CPR 0434 ISO 9001 Quality Management certified by BSI with certificate number FM530352 ...

Страница 2: ...by INIM Electronics This power station must be installed in accordance with the instructions described in this manual and in compliance with the laws in force All power stations from the SmartLevel series are EN54 4 and EN12101 10 compliant All power stations from the SmartLevel series and all accessory items and special functions have IMQ Sistemi di Sicurezza certification unless otherwise stated...

Страница 3: ...ler 7 2 8 Technical support 7 2 9 Conventions 8 2 10 CE Mark 9 2 11 Warranty 9 2 12 Safety laws 9 2 13 Replacement and disposal of used devices 10 Chapter 3 Device management 11 3 1 Product handling and storage 11 3 2 Unpacking the device 11 Chapter 4 Technical description 12 4 1 Station 12 4 2 Internal devices 13 4 3 Signalling LEDs 14 4 4 Technical specifications 15 Chapter 5 Installation instru...

Страница 4: ...4 Table of contents Power supply stations ...

Страница 5: ...lies power to remote loads such as fire door magnets sounders emergency signs linear smoke detectors Note The SmartLevel power supply station is EN54 4 compliant and specifically the amendment EN 54 4 1997 A2 which includes a test regarding the internal resistance of the batteries Main features front panel with signalling LEDs 1 24V output 2 fault relays loop connection The SmartLevel can operate ...

Страница 6: ...ly Refer to paragraph 5 4 Thermal probe Loop all the peripheral devices of the system must be connected in parallel to the loop circuit 2 pole shielded cable The circuit is considered a loop because the wiring path starts at the loop out terminals passes through all the protected areas connects all the system devices in parallel and returns to the loop in terminals The panel controls and communica...

Страница 7: ...ompliance with the local fire code in force 2 5 Recommendations INIM Electronics recommends that the entire system be checked completely at regular intervals refer to paragraph 2 6 System test 2 6 System test This system has been designed to provide the highest standards of reliability and performance Malfunction of any of the system devices may cause the system to be incapable of reaching the int...

Страница 8: ...graphic conventions relating to the interface refer to paragraph 4 3 Signalling LEDs Note The detached notes contain important information about the text Attention The attention prompts indicate that total or partial disregard of the procedure could damage the connected devices Danger The danger warnings indicate that total or partial disregard of the procedure could injure the operator or persons...

Страница 9: ...er il controllo del fumo e del calore EN 54 4 1997 A1 2002 A2 2006 NB No 0051 Caratteristiche essenziali Prestazione S S A P e n o i z a t n e m i l a i d e n o i z a t s e r P S S A P o t n e m a n o i z n u f i d à t i l i b a d i f f A Durabilità dell affidabilità di funzionamento S S A P a c i m r e t a z n e t s i s e r resistenza alle vibrazioni PASS S S A P a c i r t t e l e à t i l i b a t...

Страница 10: ...ed devices Replacement When replacing obsolete devices disconnect the devices concerned then complete the connections of the new devices in compliance with the instructions printed on the respective leaflets In order to avoid short circuits take all the necessary precautions when removing used batteries Disposal Do not burn used electronic devices or allow them to pollute the environment countrysi...

Страница 11: ...e disposed of in compliance with the local laws and bylaws in force The metal enclosure of the device is packed carefully inside the cardboard box Note The lead batteries are not included Be sure you have the batteries on hand before starting When you remove the four screws and metal frontplate you will find The SmartLevel motherboard mounted on a plastic support which bridges the two sides of the...

Страница 12: ...l with signaling LEDs B Front cover C Securing screw location for the front cover D Plastic support for front panel and motherboard mounting E Plastic support anchor screw F About the motherboard G Power supply module H Backup battery housing I Cable entry J Anchor screw hole B D H G F E I I I J J A C E E E C C C B D I H G F E I I I J J A E E E H C C C C ...

Страница 13: ...s attached to the backplate of the metal enclosure The power supply type depends on the station model A LOOP Loop connection terminals B FAULT Voltage free fault relay contacts C MAINS Voltage free mains fault relay contacts D OUTPUT Output channel terminals 2 terminals and 2 terminals in parallel E Power supply module connectors DO NOT USE F Front panel signaling LEDs A B C D E E F A A D C B F B ...

Страница 14: ...ut if the jumper is removed earth faults will not be signaled LED Colour Signalling Note A Frontplate green Indicates the power station is working This LED will go Off in the event of joint primary 230V and secondary batteries power failure B yellow Indicates an active fault condition This condition activates the FAULT relay For further details see the LED activation on the power supply unit C yel...

Страница 15: ...x b 1 5 A 4 A Maximum battery current emission during primary power failure 1 5 A 4 A Maximum current for external loads and accessory devices 1 47 A 3 97 A Maximum battery charge current 0 6 A 1 2 A Minimum current Imin 30 mA Battery specifications 2 x 12V 7 Ah 2 x 12V 17 Ah 2 x 12 V 7 Ah YUASA NP 12 FR or similar with case flame class UL94 V2 or higher Maximum internal resistance of the batterie...

Страница 16: ... supply module Figure 6 Switching power supply A and Figure 8 Earthing system A For a safety standards compliant system the Line must be connected to terminal L the Neutral conductor to terminal N This station must be connected to a separate line on the Electrical Switchboard Mains power supply The line must be protected by a sectioning device which complies with local safety regulations fire code...

Страница 17: ...SmartLoop enclosure must be secured to the cable hooks on the backplate by means of plastic cable ties Use cable with double isolation for the connection to the electrical mains 6 Insert the two 12V batteries and connect them to the power supply module Figure 6 Switching power supply C 5 3 Connecting the batteries The enclosure provides housing for two 12V lead batteries 7 Ah for the SPS24060S mod...

Страница 18: ... will be reseted when the voltage restores to 24 6V Deep discharge shutdown If a mains failure event lasts for a long period causing the battery voltage to drop below 18V the power supply station will shutdown the batteries in order to avoid permanent damage 5 4 Thermal probe Attention In order to validate the IMQ SISTEMI DI SICUREZZA certification and comply with EN 54 4 requirements installation...

Страница 19: ...ct Replace both batteries Allow them to charge for several hours Check that the fault has cleared 6 2 Low Battery The batteries are running low This signal should be present only during primary power source failure Mains 230V Mains power must be restored in order to charge the batteries 6 3 Loop faults and testing The station shows the status of the loop and the presence of any fault or short circ...

Страница 20: ...nel do not use any kind of cleaning product or solvent 2 Check the functioning of the LEDs 3 Check the battery efficiency and change them if necessary 4 Check the integrity of all wires and connections 5 Ensure that there are no extraneous objects inside the control panel Note Points 1 and 2 can be carried out by authorized persons whereas all other points must be carried out by qualified technici...

Страница 21: ...Installation manual Maintenance 21 ...

Страница 22: ...22 Maintenance Power supply stations ...

Страница 23: ...Installation manual 23 ...

Страница 24: ...i Lavoratori 10 fraz Centobuchi 63076 Monteprandone AP ITALY Tel 39 0735 705007 _ Fax 39 0735 704912 info inim biz _ www inim biz ISO 9001 Quality Management certified by BSI with certificate number FM530352 ...