background image

 

 

 

 

 

 

 

iMM Client / Server

User manual 3.265

2017

Summary of Contents for iMM Client / Server

Page 1: ...iMM Client Server User manual 3 265 2017...

Page 2: ...export pub 26 Bookmark System 27 Network settings 28 Recover network manager 29 Shutdown server 30 Restart server 31 Restart server regulary 32 NFS Server configuration 33 Bookmark HA BUS 34 iNELS3 36...

Page 3: ...93 Bookmark Intercoms 94 2N settings 96 New intercom account 97 Update asterisk settings 98 Intercom accounts 99 Bookmark Energy 100 Energy management 105 Create counter IDM3 107 Bookmark IR 110 IR se...

Page 4: ...iMM Server EN iMM Server Manual...

Page 5: ...video zone iDM iNELS Designer and Manager sw environment for iNELS configuration iMMClient video zones iMMControl Center iMM CC iMM configuration administrator available via web interface IP camera c...

Page 6: ...nt command for disconnection of certain device man command is used to format and display the man page for example man mount sudo shutdown now command shut down device iMM Client Serve from teminal sud...

Page 7: ...M cannot be triggered without the presence of active network connection Mouse and keyboard connection via USB Display device TV or PC monitor by means of HDMI or DisplayPort Audio output 3 5 mm jack a...

Page 8: ...1 2 2 Resolution adaptation The application can be run on LCD plasma TV or PC monitor with lower resolution than Full_HD If the resolution does not seem to be correct Application has to be re install...

Page 9: ...ect the desired option Shut Down or Shut Down and in new window Restart Pressing the button with symbol on the front VZ panel calls up a menu with options for switching off and restart of VZ 1 2 5 Set...

Page 10: ...address your ISP h Confirm by Save key enter the password and close all windows i Press F9 click on the network connection icon by the left mouse button and select Disconnect j After disconnection cli...

Page 11: ...r window c The system asks you to type your password confirm by Authenticate d The system will inform you on the course of download and installation of new updates e After the completion the wizard cl...

Page 12: ......

Page 13: ...2 Network File System NFS hereinafter configuration 2 Network File System configuration NFS has to be set in case you use multiple VZ If you use single VZ as iMM server NFS need not be configured...

Page 14: ...check in the quotation marks of the actual address example home imm 10 10 3 0 255 255 255 0 rw sync no_subtree_check for server there is ALWAYS zero at the end of the IP address h Save the changes in...

Page 15: ...rd rw user 0 0 h Save the file by pressing CTRL S and terminate the application by CTRL X i Now you need to restart iMM Client this will map automatically the needed folders from the server i When the...

Page 16: ...isk drive dev sda5 UUID 0a49bd69 20a7 490c 97db 6781bd794837 TYPE swap iMM client s mechanics dev sdb1 LABEL My Passport UUID F474B7AA74B76DCC TYPE ntfs External hard disk drive Note Instead of the sp...

Page 17: ...ncrete HDD Ex If the name of your HDD is for instance Verbatim the names in the below links change to mkdir media Verbatim iMM mkdir media iMM HDD iMM mkdir media iMM HDD iMM Video 2 dev null mkdir me...

Page 18: ...D iMM Music Music ln s media iMM HDD iMM Video Video ln s media iMM HDD iMM Pictures Pictures ln s media iMM HDD iMM Television Television ln s media iMM HDD iMM Cameras Cameras Note For visibility of...

Page 19: ...n find out The name of the folder by command cat etc fstab If the name differs you have to change the names in the list of commands After creation of shared folders change authorisation to these folde...

Page 20: ...s Video Video ln s mnt nas Pictures Pictures ln s mnt nas Television Television ln s mnt nas Cameras Cameras Then create a symbolic line for sharing by putting the following command in the terminal fo...

Page 21: ...settings Connection server iMM CC is activated upon entering the address http Iocalhost 8080 physically at iMM client in your internet browser Login by your password in factory instalation is default...

Page 22: ...kmark Server In bookmark Server you can control virtual servers services which are necessary for comunication third party For software diagnostic is possible each virtual server check status stop or e...

Page 23: ...iMM servers management iMM servers management In the section iMM servers management we can control the virtual servers running on the server via web interface...

Page 24: ...Bookmark Configuration Bookmark Configuration In bookmark Configuration is main settings impotrant for propertly function device iMM server Machine ID and Licence key are preset in factory default...

Page 25: ...U2 port 61682 CU3 port 9999 Version CU Format Example CU2 IPADDRESS COMUNICATION_PORT 10 5 15 12 8454 CU3 IPADDRESS HTTP_PORT COMUNICATION_PORT 10 5 15 12 8080 4562 Communication port Elkonet for iMM...

Page 26: ...oad export pub file from softare IDM to iMM Server and manual edit elements in web browser Functon for upload export pub is only for central unit iNELS 2 In the central unit iNELS3 will download expor...

Page 27: ...in Network manager in ubuntu We recommend setting a static IP address for iMM Other buttons offers Recovery network manager enable Network manager in Ubuntu Shutdown turn off iMM server Restart server...

Page 28: ...P addres Set static IP address deactivate LAN settings in Network manager function you can restore in menu Recovary network manager Set static IP address is recommended for stable use Information abou...

Page 29: ...Recover network manager Recover network manager Button Recover is use to restore lan settings Network manager which was deactivated by setting Static IP address in the Network Settings...

Page 30: ...Shutdown server Shutdown server Press down Shutdown button to power off iMM server from a web interface...

Page 31: ...Restart server Restart server Press down the Reset button to restart iMM server from a Web interface...

Page 32: ...regulary Restart server regulary In the section Restart server regulary we can set up scheduled restart the server at a specified time in a week Example settings restart server in monday six minut aft...

Page 33: ...NFS Server configuration NFS Server configuration Press down Update button to refresh NFS sharing settings in the file etc fstab from a web interface...

Page 34: ...ELS3 CU First enter the IP address of the central unit iNELS3 next fill password optional and note to finish press down button Add After saving the settings will download export from central unit and...

Page 35: ...Example add device KNX to rooms in bookmark Rooms This manual does not describe the setting elements KNX only link two systems among themselves...

Page 36: ...prefix consists of two parts first one is inels3 and second A last char A H distinguishes letter central unit between themselves For correct function with KNX would have filled a part of the KNX If th...

Page 37: ...fter saving the configuration file we find export group addresses from the program ETS3 or higher and upload KNX exports Check Configurations in the bookmark that contains a list of export elements KN...

Page 38: ...KNX add actor to rooms Add KNX element to the Rooms KNX elements put into a room in the same way as the elements iNELS KNX recognise by prefixing knx_ Example add KNX device to rooms...

Page 39: ...ue False 0 255 0 100 see KNX DPT link Example of data in a file supplemented Test_group cvs Group name Address Dimming 0 New Middle Group 0 0 Dim A 0 0 1 5 Dim B 0 0 2 5 Switching 1 New Middle Group 1...

Page 40: ...1 1 bit bool True False 5 8 bit num 0 255 5 001 8 bit num 0 100 6 8 bit num 128 127 232 3 byte num RGB 0 0 0 255 255 255...

Page 41: ...F devices and iMM is required smart box eLAN RF RF devices add to FP the same way as iNELS elements Just need to check the box below the list of RF devices To configure the RF devices a The list of su...

Page 42: ...Ovl d n RF prvk povolte v nastaven aplikace iHC MA iHC TA...

Page 43: ...ings Settings For control RF devices in menu Settings insert IP address device eLAN RF which must already be configured from the web interface or applications IHC MARF see manual eLAN RF Example setti...

Page 44: ...ones for iMM server Videozone Audiozone Giom a Virtual zone Options selected zones vodeozone Videozone for iMM clients create as zone if all switch set to no squeezebox Audiozone Audiozone R Squeezebo...

Page 45: ...View already stored zone...

Page 46: ...iom a Virtual zone vodeozone Videozone for iMM clients create as zone if all switch set to no squeezebox Audiozone Audiozone R Squeezeboxs Logitech and Laras giom Meteostation Giom 3000 virtual zone C...

Page 47: ...No zone defined No zone defined You do not have any saved zone to create a zone go to create New zone...

Page 48: ...Defined zones Defined zone In the section Defined zone are displays saved zones View already stored zone...

Page 49: ...Defined virtual zones Defined virtual zones In the section Defined virtual zones are show saved zones which can be edit Configure button...

Page 50: ...Configure Configure Configuration button to edit the selected virtual zone where we can continue to set the device ID in web interface eLAN IR or app iHC MAIR iHC MIIR Example...

Page 51: ...Example Device ID number set equipment is located in web interface eLAN IR in bookmark Devices Control device for Virtualzone must be stored in Elan IR Device you can setup via app iHC MAIR iHC MIIR...

Page 52: ...which recognizes the different technologies that the user is coming to your home and starts the scene enterHouse more datail obout this function in manual app iHC MA Example create a scene enterHouse...

Page 53: ...Monitoring arriving home which recognizes the different technologies that the user is coming to your home and starts the scene enterHouse more datail obout this function in manual app iHC MA For prope...

Page 54: ...Edit enterHouse or exitHouse Edit enterHouse or exitHouse Edit scene enterHouse or Exit House Example add elemets to scene enterHouse Example add elemets to scene exitHouse...

Page 55: ...s the status of Miele appliances if you are running is displayed in the table Security scan report for all video zones iMM Security scan can be set to monitor the status of selected elements in the ho...

Page 56: ...Trigger ralays Trigger ralays In the section Trigger relays is main configuration for security relay for notify about preset states devices and Miele appliances...

Page 57: ...y me if device obtains folowing state Notify me if device obtains folowing state In the section Notify me if device obtains folowing state you can set condition monitoring state relay Example Security...

Page 58: ...start script The event is performed if the element reaches the set value of the event You can use different kinds of elements relay DAC etc EventScript use ASCII protocol whitch must be turn on in IDM...

Page 59: ...inger Rules you can create event based on which the run script Example created event Depending on the setting ASCI protocol set value in hex or DEC example 50 in HEX is 80 DEC EventScript run with all...

Page 60: ...Bookmark Multiroom allows you to set the synchronized playback to several audio zone Mutiroom create inserting predefined zone s to multiroom Supported are Audiozone R Logitech Squeezebox a videozone...

Page 61: ...ltiroom In the section New multiroom created rooms which you can assign multiple audioz n for synchronized playback Supported are Audiozone R Logitech Squeezebox a video zone iMM Client Lara do not ye...

Page 62: ...Defined multirooms Defined multirooms In the section Defined multiroom you can modify and delete created multirooms...

Page 63: ...Add to Multiroom Add to Multiroom When editing room to display audio zones in selected room key Add to Multiroom we can add the selected zone into the Multi zone Example edit Multi zone...

Page 64: ...No zone defined No zone defined You do not have any saved zone Multiroom to create a zone go to menu create New multirooms...

Page 65: ...ird parties and their control through the application iHC Supported are LG Clims CoolMaster CoolMasterNet Air Pohoda Atrea Universal 0 10V LG Clims over the modul PI 485 over Advantech Adam 4571 CoolM...

Page 66: ...DK FJ GR HT MD KT LG MD Mitsubishi Electric Mitsubishi Heavy Panasonic Samsung Sanyo Toshiba Trane Compatibility indoor outdoor unit link ME MH PN SM SA TO TR Other Atrea Duplex 180 EC4 P 0 10 Duplex...

Page 67: ...n LG Clims is used to define air conditiong LG corporation Supported are units with communications board PI485 LG air conditioning must be installed via RS485 LAN for example through device Advantech...

Page 68: ...trol unit Coolmaster Test comunication If the air conditioner control unit is properly connected to Coolmaster the display alternately displays the temperature and mode Second step Moving on to set th...

Page 69: ...RT Example ncat in terminal Command Significance Command ncat 10 10 10 111 10102 Connection to Cooler Master Convertor Answer Returns the character command line Command stat2 List states Air condition...

Page 70: ...r Pohoda Is used to define Air recovery call Air pohoda and control through app iHC AirPohoda air recovery must be connected via RS485 LAN for example through device Advantech Adam 4571 Example saved...

Page 71: ...Atrea Is used to define Air recovery call Atrea and control through app iHC or FP Atrea Air recovery must be installed via RS485 LAN for example through device Advantech Adam 4571 Example save Air rec...

Page 72: ...Universal 0 10V Universal 0 10V Is used to define universal air conditiong using DAC 0 10V and control through app iHC Example save air condition...

Page 73: ...uration souboru rooms cfg for loading applications iHC More information in the manual iHC Rooms are actually virtual rooms groups which have the option to group the icons and zones for one or more scr...

Page 74: ...New room New room Used to define rooms for applications iHC Example imposed rooms Pro n zev m stnosti m eme pou t pouze znaky A Z a z 0 9 _...

Page 75: ...List Rooms List of rooms Listing stored rooms on the server for applications iHC...

Page 76: ...Edit Devices of rooms In menu Devices of room is used for editing rooms for application iHC Example add device to room House...

Page 77: ...le create scene For scene control can be programmed to use a script that can execute various functions defined in it It is necessary to keep an absolute path starting with and ending with the suffix s...

Page 78: ...Rename Rename In the section Rename you can change name of room for app iHC Example rename Room to na Living room...

Page 79: ...orts see manual for the camera If you do not fill HTTP or RTSP ports remain in default HTTP port 80 RTSP port 554 New camera Supported cameras are iNELS cam AXIS protokolu VAPIX2 od verze firmwaru kam...

Page 80: ...amera supported video stream only over rtsp protocol set up codec to MPEG4 both port HTTP port and iHC to 554 Service port is usually set up to 80 If the camera is behind NAT must be redirected port f...

Page 81: ...List saved cameras...

Page 82: ...Select the stream Select the stream In the section Select the stream you can choose specific camera streams assign to mobile app iHC Example...

Page 83: ...No camera defined No camera defined In this section will be displayed set cameras iMM server...

Page 84: ...List of cameras List of cameras Menu List of cameras show saved cameras iMM server and options for remove selected camera...

Page 85: ...okmark Miele set IP adresu device Miele gateway that serves remote control of appliances over powerline or ZigBee protocol Supported are XGW 2000 XGW 3000 Firmware 1 1 1 2 Set IP address MieleGateWay...

Page 86: ...control of appliances over powerline or ZigBee protocol Supported are XGW 2000 XGW 3000 Firmware 1 1 1 2 Set IP address MieleGateWay is stored in the file etc imm miele Relay for restart GW is used fo...

Page 87: ...ominus Bookmark Dominus we can setup acces details for ESS Milenium of which can be read states via the protocol Domiline subsystem and numbers and reaction on changes through using system bits in ele...

Page 88: ...ected within 5 minutes start SetWterm load or upload saved configuration create space for history ESS and transaction records eventually create other user and password controller update Calculation of...

Page 89: ...Y 1089 128 8 integral Z the remainder after division ie 1089 mod 128 65 switch windows calculator in scientific mode and use function mod...

Page 90: ...o a defined system bit Disturbed sensors system bit 1 Disturbed in alarm syst m bit 1 Detector in calm syst m bit 0 Example An alarm in the program SetTermW Disruption of the alarm in the event that i...

Page 91: ...Example Disturbed in alarm with the program SetTermW For detecting the movement of the sensor without alarms set the input type to Unused...

Page 92: ...Motion sensor function can simulate the input resistor 3 9K...

Page 93: ...ction Subsystems setup numbers subsystems for pairing with systemic bit in CU3 Subsystem means a secure area with sensors that can be locked or unlocked state Open system bit 1 Close system bit 0 Exam...

Page 94: ...ss data on the web interface 2N and Lock code set value to relay 2N intercom Connection server support set only one door intercom for open via DTMF Supported IP intercoms are 2N Helios Verso Helios Fo...

Page 95: ...n will recognize that this is a sound and allow the door opening preset Lock code if we choose a different name for intercom will behave like an ordinary contact and opening function must be set manua...

Page 96: ...on the web interface 2N and Lock code set value for switch to relay 2N intercom iMM server support set only one door intercom for open via DTMF Supported are IP intercoms 2N Helios Verso Helios Force...

Page 97: ...New intercom account In the section New intercom account creating VOIP accounts on server side for applications iHC Stream for cam 2N add in format rtsp IPADDRESS For view in application iHC must be...

Page 98: ...Update asterisk settings Update asterisk settings Button Apply settings activate the newly created accounts VOIP and restart asterisk PBX...

Page 99: ...sound and allow the door opening preset Lock code if we choose a different name for intercom will behave like an ordinary contact and opening function must be set manually in the mobile app For open s...

Page 100: ...d energy is shown in quantity but also in financial value The list of supported measuring devices which have a pulse output can be found here 1 Click on the System Configuration button icon of hammer...

Page 101: ...Creation of counter in iDM...

Page 102: ...Creation of action Counter incrementing...

Page 103: ...Action assignment to binary input where output from measuring instrument is connected Assign counter value in iMM Control Center...

Page 104: ...Example 1 kWh 100 K 100 pulz Base Unit kWh Impulses 100 per 1 kWh Price 1 per 1 impulse Create counter in sowftware IDM3 see Create counter IDM3...

Page 105: ...Energy management Energy management In the section Energy management select binary inputs for WATER GAS ELECTRICITY and adding them to unit impulse currency Example Energy management...

Page 106: ...Create counter see bookmark Energy...

Page 107: ...Create counter IDM3 Create counter IDM3 Create counter in software IDM3 In bookmark Managers select the System Manager and go to the tab Counters where we create a counter name...

Page 108: ...tion called Energy Increment Move the switch and central units to the desktop and double click on switch icon edit and select IN Digital input M3 80B In the Function tab select ADD connections make th...

Page 109: ...tab Function select Wire Manager select the input IN Energy through button the Edit function to adjust to Action Short down User function Energy Increment Add the created counter to iMMCC Energy mana...

Page 110: ...ferent ways before API 4 1 By means of virtual control in web browser that you optionally predefined In iMM you can call this virtual control up by pressing the panel button in the web interface IP co...

Page 111: ...part iMM in bookmark Zones http localhost 8090 zone in the section Control specify to IR type together with the set ID Equipment eLAN IR API version 4 you can check in your web browser http IPADDRESSe...

Page 112: ...ss device eLAN IR according versions API API version Verze firmwaru Before 4 1 6 406 and lower After 4 1 6 508 and higher The client part iMM tab Zones http localhost 8090 zone in the Control to speci...

Page 113: ...API version 4 you can check in web browser http IPADDRESS_eLAN IR api...

Page 114: ...before 4 In the section Elan set IP address device eLAN IR and port 61682 in default setup Setting control IR commands for turn off turn on volume up volume down put into bookmark zone on client side...

Page 115: ...Panel In the section Panel you can setup background color and window resolution in bookmark panel Setting control IR commands for turn off turn on volume up volume down put into bookmark zone on clien...

Page 116: ...bookmark Giom creating a scene according to data from the weather station call Giom IPADDRESS 8080 giom Scene will be activated if selected value is higher or lower then set and assigned to units Edit...

Page 117: ...ing the Mlocator software whitch can be downloaded in the manafacture s website link For proper function you must first set up Giom such a zone If you set up a password authentication for Giom web int...

Page 118: ...higher or lower then set and assigned to units Edit scene For proper function you must first set up Giom such a zone If you set up a password authentication for Giom web interface tick exception stat...

Page 119: ...Edit Edit Edit is used to create or edit scenes In the selected scene type is possible add or remove relay units Example Edit selected scene...

Page 120: ...Bookmark Manual Download manual In bookmark Manual is available for download the latest version of the manual in PDF format...

Page 121: ...Manual Download manual In the section Download manual click the button Download you can download the current version manual in PDF format...

Page 122: ...ngs to default state The first option offers is Reset all clients settings to default to reset iMM server to factory default ie remove all users settings The second option is Reset all devices depende...

Page 123: ...Reset all server settings to default Reset all server settings to default Reset all server settings to defalt is used to reset server iMM to factory default i e that all user settings will be erased...

Page 124: ...ndencies to default Reset all devices dependencies to default In the section Reset all devices dependencies to default remove settings which are depending on other functions iMM server for example rel...

Page 125: ...Bookmark Audit Bookmark Audit Bookmark Audit is used to show a download LOG option events for diagnostic purposes developer...

Page 126: ...Logged events Logged events In the section Logged events is used to show a download LOG option events for diagnostic purposes developer...

Page 127: ...Others TODO Insert description text here And don t forget to add keyword for this topic...

Page 128: ...rol and setting of heating program in IDM software In time weekly program administrator a part of export setting for visualisation Enable export heating circuits for visualization b After clicking on...

Page 129: ...Modes can be alternated by buttons on the right FP side Komfort Norm l Minimum tlum LO Configuration in software IDM3 Heating circuit configuration is done in the Managers tab and select the System M...

Page 130: ...ensor iNELS3_Thermostat c4i Thermostat produced in IDM heating cooling combined iNELS3_Blinds c4i Shutters Blinds driver for JA3 20B DC SA3 copy all the files to the location C Users user Documents Co...

Page 131: ...in IMMCC then DA3 22M_OUT1_000021 Y B 17039361 REAL PUB_INOUT put in the project iNELS3 Dimmer where change device name and put the address of the unit Device Address 17039361 Debug mode it is an opt...

Page 132: ...only for this purpose in program IDM Next we set the preset minimum temperature attenuation normal comfort for the heating and cooling area separated Commands if we only have a separate circuit we wi...