• ADVANCED SOLID STATE DESIGN

• TEST BUTTON FOR EASY DIAGNOSTICS

• POWER AND LOW WATER LED INDICATORS

• COMPACT SIZE ALLOWS FOR MOUNTING IN TIGHT SPACES

• DESIGNED FOR GAS AND OIL FIRED BOILERS

Step

���

Step

���

Low Water Cut-Off
For Residential
Hot Water Boilers

120 VAC Operating Voltage

Model 1150

Determine Mounting Location

The Safgard 1150 must be installed at or above the

minimum safe water level established by the boiler

manufacturer. The 1150 can be installed directly into

the boiler if a suitable tapping is available

. The

1150 can also be installed in the boiler piping using a

standard 3/4" tee

.

IMPORTANT: Check for adequate clearance

(minimum 1/4") from metal probe sensor to any

surface inside the boiler or pipe.
Do not install in a location that could hold or trap

water in the event of a low water condition.

Remove center

extended nut.

Apply pipe

sealing

compound to

probe threads

and install in

boiler or tee.

Tighten so that

the two smaller

extended nuts

are horizontally

aligned.

Mount the control box on the probe by aligning the

keyhole slots with the two extended nuts. Replace

the center extended nut. Secure the control box by

tightening all three extended nuts.

IMPORTANT: Extended nuts must be tightened

securely for proper grounding.

WARNING:

To prevent electrical shock or equipment damage, power must be off during installation or servicing of the control. To pre-

vent serious burns, the boiler should be thoroughly cooled before installing or servicing control. Only qualified personnel may install or
service the control in accordance with local codes and ordinances. Read instructions completely before proceeding.

Step

���

Model 1150 Instructions: Model 1150 Instructions  9/24/10  9:17 AM  Page 3

Summary of Contents for Safgard 1150

Page 1: ...or pipe Do not install in a location that could hold or trap water in the event of a low water condition Remove center extended nut Apply pipe sealing compound to probe threads and install in boiler or tee Tighten so that the two smaller extended nuts are horizontally aligned Mount the control box on the probe by aligning the keyhole slots with the two extended nuts Replace the center extended nut...

Page 2: ...20 VAC lead coming from the service switch Step Connect the second yellow wire CUT OFF from the Safgard 1150 to the L1 boiler connection Connect the black wire H from the Safgard 1150 to the hot 120 VAC lead coming from the service switch Connect the white wire N to the neutral 120 VAC lead Locate and break into the burner circuit Connect the yel low wires CUT OFF from the Safgard 1150 in series w...

Page 3: ...er should shut down 5 YEARS Remove the low water cut off every five years and clean all surfaces in contact with water TROUBLE SHOOTING IF THE BURNER DOES NOT SHUT DOWN when water is below the probe or when the TEST button is pressed 1 Turn off boiler power immediately and re check wiring 2 Turn off boiler power and drain system Remove low water cut off and check for adequate clearance no metal sh...

Page 4: ...y other loss or damage whether direct indirect incidental or consequential This war ranty is your EXCLUSIVE remedy and shall be IN PLACE OF any other warranty or guarantee express or implied includ ing without limitation any warranty of MERCHANTABILITY or fitness for a particular purpose This warranty may not be assigned or transferred and any unauthorized transfer or assignment thereof shall be v...