PRODUCT DESCRIPTION 

 
The Industrial Modem (CGM750) is a rugged industrial telephone modem designed for operation in harsh 
environments.  The modem supports all standard Hayes AT commands and S-registers; it can be set-up 
as an external modem on any PC.  The CGM750 is compatible with any telecommunications or dial-up 
networking software.  The board contains: 
 

• 

Modem and DAA chip set   

• 

RJ11 Jacks – Two AMP 520425-2 RJ11 jacks are provided. One jack is for Line and one is for 
Handset (Phone). 

• 

RS-232 Port  

• 

Switching DC to DC power supply  

 
 

SPECIFICATIONS 

 
 

Table 1 – CGM750 Specifications 

Telephone Line 

Max. Data Rate 

14.4 kbps (V.32) 

Compatibility 

V.32bis, V.32, V.22bis, V.22, V.23, V.21, Bell 212A and Bell 103 

Data Compression 

V.42bis and MNP 5 (default = disabled) 

Error Correction 

V.42 LAPM and MNP 2-4 (default = disabled)  

Ringer Equivalent 

0.1 

Line Jack 

RJ11 

Phone Jack 

RJ11 

RS-232 Port 

Max. RS232 Rate 

115.2 kbps  

RS232 Signal Support 

TXD, RXD, CTS, RTS, DCD, DTR, DSR, RI, GND 

RS232 Connector 

DB9 female, RS232 

Command Set 

All standard AT and S register commands  

General Characteristics 

Input Supply Voltage 

8 – 30 VDC 

Steady State Current 

80mA @ 24VDC (typical) 

Certification 

FCC Part 68 US: HRNMD01AHE200CGM,  

and Industry Canada ICCS-03 

Operating Temperature 

0 to 60 degree C. 

Storage Temperature 

-40 to 85 degree C. 

Humidity 

5 to 95% RH (Non-condensing) 

Mounting 

DIN rail 

Dimensions  

6.25” (158.75mm) x 3.12” (79.25mm) x 1.61” (40.89mm) 

 
 

18 August 2003 

 

 

 

 

 

 

 

 

    MAN0700-03  

 

SmartLnx

Industrial Modem  

HE200CGM750

Products Specifications and Installation Data

Summary of Contents for CGM750

Page 1: ...bis V 22 V 23 V 21 Bell 212A and Bell 103 Data Compression V 42bis and MNP 5 default disabled Error Correction V 42 LAPM and MNP 2 4 default disabled Ringer Equivalent 0 1 Line Jack RJ11 Phone Jack RJ11 RS 232 Port Max RS232 Rate 115 2 kbps RS232 Signal Support TXD RXD CTS RTS DCD DTR DSR RI GND RS232 Connector DB9 female RS232 Command Set All standard AT and S register commands General Characteri...

Page 2: ...PAGE 2 18 AUG 2003 MAN0700 03 3 INSTALLATION 3 1 Dimensions Figure 1 CGM750 Dimensions 400CGM001 6 25 158 75mm 1 61 40 89mm 3 12 79 25mm 8 30VDC PWR ...

Page 3: ...S 232 Port Pins Pin Signal Description Direction 1 DCD Data Carrier Detect Out 2 RXD Received Data Out 3 TXD Transmitted Data In 4 DTR Data Terminal Ready In 5 GND Ground 6 DSR Data Set Ready Out 7 RTS Request to Send In 8 CTS Clear to Send Out 9 RI Ring Indicate Out Table 5 LEDs DCD Data Carrier Detect Modem has detected carrier on phone line OH Off Hook Indicator Phone line is engaged RX Receive...

Page 4: ...4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 1 CTS RXD TXD DTR GND DSR RTS R1 DCD CTS RXD TXD DTR GND DSR RTS 9 PIN DB DCD R1 9 PIN DB 9 PIN PC COM CGM RS 232 004CGM004 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 1 CTS RXD TXD DTR GND DSR RTS R1 DCD CTS RXD TXD DTR GND DSR RTS 9 PIN DB DCD NC NC NC NC R1 9 PIN DB OCS CGM 004CGM003 ...

Page 5: ...r voltage and electrically noisy cables and devices 4 MODEM CONFIGURATION a Default Configuration The CGM750 modem is pre configured at the factory to automatically receive calls and communicate locally with many common automation devices PLCs etc For this reason the default factory modem init string is AT D0 K0S0 1Q1 which causes the modem to ignore its DTR input turn off handshaking flow control...

Page 6: ...E0S0 0V0X0 C1 D2 init string is sent to the modem followed by the appropriate additional INIT DIAL or ANSWER modem command as programmed into the function block The ATE0S0 0V0X0 C1 D2 init string tells the modem don t echo don t auto answer produce numeric simple result codes indicate connection by activating the DCD output and hang up if the DTR input becomes inactive Unfortunately the V0X0 porti...

Page 7: ...le codes and standards need to be followed in the installation of this product 6 TECHNICAL ASSISTANCE For assistance contact Technical Support at the following locations North America 317 916 4274 www heapg com Europe 353 21 4321 266 www horner apg com ...

Page 8: ...PAGE 8 18 AUG 2003 MAN0700 03 NOTES ...

Reviews: