background image

X-XX UL

® U.S. Registered Trademark
Copyright © 1996 Honeywell Inc.   •   All Rights Reserved

R4184D; R8184G,M,N,P

Protectorelay

 

®

 Oil Primary Controls

APPLICATION

The  intermittent ignition R4184D and R8184G,M,N,P Oil
Primary Controls operate the oil burner, oil valve (if
desired) and the ignition transformer in response to a call
for heat from the thermostat.

The R8184M also provides automatic, nonrecycling control
of cooling systems and low voltage thermostat.

The R8184P provides 15-second valve on delay and
selectable 0-, 2-, 4-, 6-minute blower off delay for hydronic
and warm air systems. Select models have 30-minute
blower off delay timing.

All models use the C554A Cadmium Sulfide (cad cell)
Flame Detector to monitor the burner flame and shut down
the system on ignition failure or on flame failure during the
run cycle. A manual reset button is provided to reset the
safety switch after lockout. Clock thermostats (not
available on R8184P) that power the clock through the
primary control transformer lose time during lockout unless
backup batteries are installed.

All models (except the R8184G1310 and R8184G1328)
are Underwriters Laboratories Inc. component recognized
and meet flammability test requirements for a final
enclosure.

NOTE:

R8184P is intended for use on oil burning
appliances that do not require a safety rated
prepurge and postpurge function as defined in
UL 296. The valve on delay and blower off delay
in this control are only intended to help establish
draft and reduce oil after drip-related problems.

INSTALLATION

When Installing this Product…

1. Read these instructions carefully. Failure to follow

instructions can damage the product or cause a
hazardous condition.

2. Check ratings given in the instructions and on the

product to make sure the product is suitable for your
application.

3. Make sure the installer is a trained, experienced

service technician.

4. After completing the installation, use these instruc-

tions to check out the product operation.

CAUTION

1.

Disconnect the power supply before beginning
installation to prevent electrical shock or
equipment damage.

2.

Be sure the combustion chamber is free of oil
or oil vapor before starting the system.

Location

Mount on a 4 x 4 junction box, directly on the main
burner housing or inside the appliance cabinet. See
Fig. 1.

Be sure that operating temperatures are between
-40

°

F and +130

°

F (-40

°

C and +54

°

C). Select

R8184G,P models have a maximum temperature of
150

°

F (66

°

C), but must be mounted parallel to the

ground to achieve 150

°

F (66

°

C). See Fig. 2.

CAD 
CELL LEADS

LINE 
VOLTAGE LEADS

MOUNTING
SCREW HOLE

RED RESET
BUTTON

4 x 4 JUNCTION
BOX

HOLE OR KNOCKOUT FOR
CAD CELL LEADS

LOW VOLTAGE
TERMINAL STRIP

1

STRIP WIRES 3/8 in. (9.5 mm); INSERT FROM SIDE, ABOVE OR BELOW.

T-T TERMINALS ON R8184G;  T1-T2 TERMINALS ON R8184N.

ATTACH WITH NO. 8 MOUNTING SCREWS (OBTAINED LOCALLY).

1

2

2

2

3

M1643C

Fig. 1. Wire and mount 130

°

F (54

°

C) maximum ambient

temperature oil primary control.

INSTALLATION INSTRUCTIONS

69-0618-3

Summary of Contents for R4184D

Page 1: ... on delay and blower off delay in this control are only intended to help establish draft and reduce oil after drip related problems INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow instructions can damage the product or cause a hazardous condition 2 Check ratings given in the instructions and on the product to make sure the product is suitable for you...

Page 2: ...AY CONTROL SAFETY SWITCH HEATER 1K TRIAC BILATERAL SWITCH CAPACITOR R1 1K2 1K1 1 1 IGNITION LIMIT THERMOSTAT OIL VALVE OPTIONAL BURNER MOTOR L2 L1 HOT Alarm Contact Rating 25 VA at 24V 50 60 Hz Mounting 쐃 If necessary use the control as a template to mark and drill new mounting holes 쐇 Mount the control using no 8 screws obtained locally Low Voltage Wiring Connections After mounting make low volta...

Page 3: ... VOLTAGE THERMOSTAT OIL VALVE OPTIONAL BURNER MOTOR L2 L1 HOT Fig 4 Typical hookup for R8184G JUNCTION BOX THERMOSTAT BLACK ORANGE WHITE RED RED R2 SAFETY SWITCH SAFETY SWITCH TO REMOTE ALARM CIRCUIT M5172A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED TO USE R8184 WITH LINE VOLTAGE CONTROLLER JUMPER T T TERMINALS AND CONNECT LINE VOLTAGE THERMOSTAT IN SERIES WITH LIMIT...

Page 4: ...1 HOT L2 1 1 Fig 6 Typical hookup for R8184M Fig 7 Typical hookup for R8184N JUNCTION BOX THERMOSTAT BLACK ORANGE WHITE R2 SAFETY SWITCH M717A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED TO USE R8184N WITH LINE VOLTAGE CONTROLLER JUMPER T1 T2 TERMINALS AND CONNECT LINE VOLTAGE THERMOSTAT IN SERIES WITH LIMIT CONTROLLER CAD CELL F1 T1 T2 F2 R8184N PROTECTORELAY CONTROL...

Page 5: ...LOW SWITCH AQUASTAT CONTROLLER BURNER MOTOR IGNITION TRANSFORMER VENTER MOTOR CAD CELL F R W RC Y G C R8184P PROTECTORELAY HYDRONIC CONTROL 4 LIMIT THERMOSTAT M10021 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 2 IGNITION TRANSFORMER CAN BE CONNECTED TO VALVE OR BURNER MOTOR 3 OMIT ON SYSTEMS WITHOUT POWER VENTING RED ORANGE BLACK VIOLET WHITE L1 HOT F L2 LINE 1 3 2 ...

Page 6: ...r running turn off the power to the system by tripping the circuit breaker or removing the fuse 쐋 Burner should stop 쐏 Restore power Burner should start If system does not operate as described go to the TROUBLESHOOTING AND MAINTENANCE section TROUBLESHOOTINGAND MAINTENANCE IMPORTANT 1 Only a trained experienced service technician should perform the troubleshooting procedure 2 This control contains...