Flame detection device for
oil and gas flames

INTRODUCTION

The IRD 1020.1 detector is used to supervise gas or oil
flames. This flame monitoring device should be connected
to a Satronic oil burner control box. Monitoring is based on
the infra-red flicker principle, in other words, the flickering
infra-red light of the flame is detected. The steady radiation
from, for example, the glowing refractory layer on the inside
of the boiler, has no effect on the detector. The IRD 1020.1
replaces the IRD 1020 and 920.
When exchanging the IRD 1020, care must be taken that the
corresponding IRD 1020.1 with the same imprint (blue or
white) is used (see page 3 and 4).
When exchanging the IRD 920, care must be taken to wire
the sensor correctly (see page 3), and the existing holder
must be exchanged with the magnetic holder M93.
For replacement of the IRD 920 with IRD 1020.1 is the
sensor cable also needed.

The infra-red flicker detector can be used with any one of the
following control boxes:

IRD 1020.1

DKG 972
DLG 974, 976
DMG 970, 971, 972, 973
TFI 812.2
MMI 810, 811, 812, 815, 816, 962
TMG 740-2, 740-3
SGU 930, 930i

IRD 1020.1 D DVI 980, 982

MMG 810, 811
FFW 930
DKG 972
DLG 974, 976
DMG 970, 971, 972, 973
TFI 812.2
MMI 810, 811, 812, 815, 816, 962
TMG 740-2, 740-3
SGU 930, 930i

CONSTRUCTIONAL FEATURES

The infra-red sensor and the pre-amplifier are hermetically
sealed in glass and along with the electronics form an
integrated unit in the flame detector. Wiring is by way of a
plug connection. The sensitivity control and two LED’s for
indication of the flame signal are situated on the rear of the
flicker detector.

Infra-red flicker detecto

r IRD 1020.1

TECHNICAL DATA

Supply voltage

220 / 240 V (-15... +10%)
50 Hz (50 - 60 Hz)

or

110/120 V (-15... +10%)
50 - 60 Hz (

±

5%)

Nominal current input

approx. 4 mA

Power consumption

1 VA

Ambient temperature

-20

°

 C to +60

°

 C

Insulation standard

IP 41

Mounting attitude

any

Weight

40 g

Flame viewing attitude

side-on or end-on according
to type

Spectral response

800 - 1100 nm

(with daylight filter)

maximum 950 nm

Frequency range

15 Hz.... 250 Hz (-12 dB)

Sensitivity adjustment range

approx. 1 : 20 (26 dB)

Switch-on delay

< 3.5 sec.

(after connecting
operating voltage)
Response time

< 0.1 sec.

Cut-out time

< 1 sec.

Approved ambient parameter

max. 95% at 30

°

 C

- for operation

-20

°

 C... +60

°

 C

- for storage

-20

°

 C... +80

°

 C

Build-up of ice, penetration of
water and condensing water are inadmissible
Approvals according
to European standards

EN 298, as well as all other
relevant Directives and
standards

EN1C-0118SZ20 R1005

Summary of Contents for IRD 1020.1

Page 1: ... 930 DKG 972 DLG 974 976 DMG 970 971 972 973 TFI 812 2 MMI 810 811 812 815 816 962 TMG 740 2 740 3 SGU 930 930i CONSTRUCTIONAL FEATURES The infra red sensor and the pre amplifier are hermetically sealed in glass and along with the electronics form an integrated unit in the flame detector Wiring is by way of a plug connection The sensitivity control and two LED s for indication of the flame signal ...

Page 2: ... harsh vibration and receives no hard knocks It is necessary for the magnetic IRD M93 flange to be mounted on a flat surface to avoid any mechanical stress which could otherwise damage it COMMISSIONING AND MAINTENANCE During commissioning and after servicing the flame monitoringsystemshouldbecheckedforfaultlessoperation as follows 1 Check that the detector is connected properly Wrong connectionsar...

Page 3: ...t or faulty wiring b Sensitivity set too low c Detector positioned wrongly receives no light d Detector or viewing window dirty e Defective detector f IRDflangeM93defective cracksorothermechanical defects g wrong IRD flange special magnetic IRD flange M93 is needed IRD 1020 1 Control box type TFI 812 DKG 97 DMG 97 DLG 97 Terminal no 8 8 8 Terminal no 1 1 2 Terminal no 9 9 9 Control box type MMI Te...

Page 4: ...16533 Mounting flange Flange M93 230V 59093 Sensor cable Plug type 3 wire 0 6 m with tag wire ends 7236001 The above ordering information refers to the standard version Special versions are also included in our product range Specifications subject to change without notice FLICKER DETECTOR IRD 1020 1 VARIANTS 35 3 26 4 5 15 1 48 ø20 5 4 17 14 104 29 50 44 ø13 5 21 8 HOLDER M93 Satronic IRD 1020 1 S...

Reviews: