This leaflet covers the Main Control(ler) Card
(VIG-MCC-24) which is designed for installation in
VIG1-24 and VIG1-72 Vigilon panels.
Technical data
Overall size
157mm height x 100mm width
Weight
96g (approximate)
Lithium Battery
CR2032 3V cell.
Replace the battery only with
the same or equivalent type.
Dispose of all used batteries
according to the
manufacturer’s instructions.
Operating
temperature
0
°
C to 45
°
C
Storage
temperature
-10
°
C to 55
°
C
Relative humidity
(non condensing)
up to 90%
Battery connection
The MCC has a battery insulation sleeve or disk
that must be removed before the card is fitted in the
backplane.
&
Once the battery insulation sleeve or
disk is removed from the MCC, the card MUST
NOT be placed on a metal surface as this may
result in damage to the components on the card.
Backplane
The MCC card must be installed in the correct
location in the backplane.
"
An IO Card is not required for the connection
of DKC and Commissioning tool. The DKC ribbon
cables now connects to P2 and P4 on the MCC and the
Commissioning tool connect to the USB port on MCC.
&
When handling the card always use
anti-static work procedures.
&
Always ensure the panel is completely
powered down before removal or fitting of cards
into the backplane. Power down the battery supply
before the mains supply. The power up should be
done in a reverse order.
4188-906_issue 2_02/09_new MCC
1
Data and Installation
Main Control Card
(VIG-MCC-24)
by Honeywell
BATT1
Lithium b side up
Remove insulation sleeve or
disk before installing the card
SW1
USB port
to accept
commissioning
tool connection
P2 socket to accept a
20-way ribbon
cable from the DKC
P4 socket to accept a
40-way ribbon
cable from the DKC
MCC card fits into the Backplane
slot marked P1 (MCC/LCC)
Reset
Switch
Chip
2211-143
V4.xx
Minimum
should be
V4.37
Master Controller Card (MCC)
to be fitted to socket
P1 CARD 0 on backplane
Secure the two ribbon
cables (at the fold) under the clamp
located on the backplane
40 way ribbon
20 way ribbon
Card guides
Backplane
Main Controller Card or
Local Controller Card (SUPPLIED)
Network or IO Card (Optional)
Loop Processor Card (SUPPLIED)
or RS232
Loop Processor Card or RS232
(Option)
Loop Processor Card or RS232
(Option)
Loop Processor Card or RS232
(Option)
Network or RS232 or
Loop Card#
Network or RS232 or
Loop Card#
#
for VIG1-72 only
P1
CARD 0
P2
CARD15
P3
CARD 1
P4
CARD 2
P5
CARD 3
P6
CARD 4
P7
CARD 5
P8
CARD 6
Backplane
Use the USB port on
the MCC to connect to
the Commissioning tool.