background image

HITACHI SPLIT-UNIT AIR CONDITIONER

INSTALLATION MANUAL

Indoor Unit

Outdoor Unit

RAS-R10EX

RAC-R10EX

 +  –  Screwdriver   

 Measuring Tape   

 Knife

Saw  

 ø 65mm Power 

 ●

 Drill Allen Key (    4mm)

 Wrench (14, 17, 19, 22mm) 

    ●

 Gas Leakage

Detector    

  Pipe Cutter   

  Plastic Tape    

  Pliers

 Flare Tool

Carefully read through the procedures of proper
installation before starting installation work.

The sales agent should inform customers regarding
the correct operation of installation.

Tools Needed For Installation Work

SAFETY PRECAUTION

Read the safety precautions carefully before operating the unit.

The contents of this section are vital to ensure safety. Please pay special attention to the following sign.

WARNING  ........  Incorrect methods of installation may cause death or serious injury.

CAUTION  .........  Improper installation may result in serious consequence.

Be sure that the unit operates in proper condition after installation. Explain to customer the proper way of operating
the unit as described in the user’s guide.

!

!

Air Exchanger And Exhaust Hose Installation

1

The air exchanger and exhaust function is included in this model. Please follow the installation
instructions when mounting.

FOR SERVICE PERSONNEL ONLY

<

I719: A 

>

WARNING

!

Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may
occur if you do the installation work yourself.

Please observe the instructions stated in the installation manual during the process of installation. Improper
installation may cause water leakage, electric shock and fire.

Make sure that the units are mounted at locations which are able to provide full support to the weight of the units.
If not, the units may collapse and impose danger.

Observe the rules and regulations of the electrical installation and the methods described in the installation manual
when dealing with the electrical work. Use wire which is specified for the air conditioner. A short circuit and fire
may occur due to the use of low quality wire or improper work.

Be sure to use the specified wire for connecting the indoor/outdoor units. Please ensure that the connections are
tight after the conductors of the wire are inserted into the terminals. Improper insertion and loose contact may
cause over-heating and fire.

Please use the specified components for installation work. Otherwise, the units may collapse or water leakage,
electric shock and fire may occur.

Do not mix any coolant other than R-22 into the cooling circulation path when mounting or shifting the unit. If it
is mixed with air, the high pressure in the circulation path will rise and this may result in broken copper pipes or
faults.

CAUTION

!

Be sure to use the earth line. Do not place earth line near gas or water pipes, lightning conductor and
the earth line of telephone. Improper earthing may cause electric shocks.

A circuit breaker should be installed depending on the mounting size of the unit. Without a circuit breaker, the
danger of electric shocks exists.

Do not install the unit near a location where there is flammable gas. The outdoor unit may
catch fire if flammable gas leaks around it.

Please ensure smooth flow of water when installing the drain hose.

above 100mm

 above 200mm

above 200mm

 above 100mm

 give clearance

as wide as possible

above 50mm

above 100mm

about 0.45m

above 300mm

must not bend

above 50mm when
installed on the
ceiling of balcony

above 200mm

2,300mm or more

4

5

3

6

Maximum pipe length 15m

Minimum pipe length 5m

above 100mm

1

2

THE CHOICE OF MOUNTING SITE 

 (Please note the following matters and obtain permission from customer before installation).

WARNING

!

The unit should be mounted at stable, non-vibratory location which
can provide full support to the unit.

WARNING

!

The outdoor unit must be mounted at a location which can sup-
port heavy weight. Otherwise, noise and vibration will increase.

CAUTION

!

No nearby heat source and no obstruction near the air outlet is
allowed.

The clearance distances from top, right and left are specified in
figure below.

The location must be convenient for water drainage and pipe
connection with the outdoor unit.

To avoid interference from noise please place the unit and its
remote controller at least 1m from the radio, television and inverter
type fluorescent lamp.

To avoid any error in signal transmission from the remote controller,
please put the controller far away from high-frequency machines
and high-power wireless systems.

The installation height of indoor unit must be 2.3m or more.

CAUTION

!

Do not expose the unit under direct sunshine or rain. Besides,
ventilation must be good and clear of obstruction.

The air blown out of the unit should not point directly to animals
or plants.

The clearances of the unit from top, left, right and front are specified
in figure below. At least 2 of the above sides must be open air.

Be sure that the hot air blown out of the unit and noise do not
disturb the neighbourhood.

Do not install at a location where there is flammable gas, steam,
oil and smoke.

The location must be convenient for water drainage.

Place the outdoor unit and its connection wire at least 1m away
from the antenna or signal line of television, radio or telephone.
This is to avoid noise interference.

INDOOR UNIT

Names of Indoor Components

Mounting Plate

Qty

No.

Item

The Length of Indoor

Unit Power Cord

Figure showing the Installation of Indoor and Outdoor Unit.

about 1.6m

about
0.9m

OUTDOOR UNIT

1

1

Purifying Filter

The difference in
height between
the indoor and
outdoor unit
should be kept
below 5m.

The connecting
pipe, no matter
big or small,
should all be
insulated with
insulation pipe
and then wrapped
with vinyl tape.
(The insulator will
deteriorate if it is
not wrapped with
tape).

The connection of in-
sulated drain hose.

Please use insulated
drain hose for the
indoor piping
(commercial product).

Be sure to
completely
seal any
gap with
putty.

Screw for holder of
Remote Controller

(3.1x16)

AAA Size Battery

Screw for Mounting
Plate

Direction of Piping

Dimension of Mounting

Stand of the outdoor unit

500

100

35

35

12

225

8

mounting stand

(unit : mm)

Holder for Remote
Controller

There are 4 directions
allowed, namely, horizontally
perpendicular to the unit,
vertically down from right,
horizontally out from right
and horizontally out to left.
Don’t form the piping
downward at the left of the
unit.

Remote Controller

Holder

2

5

3

1

4

2

5

2

6

1

7

1

8

1

9

20

Cut away shaded
portion, and finish
the edge of the
opening so that
there is no burr.

Connection

Horizontally
perpendicular
to the unit

1

Air Exchanger Filter

In case the pipe length is more than 8m, add refrigerant R22 at 10 gram
per every meter exceeds. However, pipe length shall not exceed 15m.

!

CAUTION

Binder

Qty

No.

Item

$

1

Left Horizontal
Pipe Connector

Left Backward
Pipe Connector

Right Connector

Right Downward
Pipe Connector

Right Horizontal
Pipe Connector

Left Downward
Pipe Connector

Right Horizontal
Pipe Connector

%

1

^

1

&

1

*

1

(

1

)

1

q

1

w

1

Ventilation pipe

0

1

Air Duct Filter

!

1

Insulation Sheet

@

1

Anti Insect Ventilate
Net

#

1

Rain Proof Ventilate
Protection Cap

e

1

Extension
Ventilation
Pipe

r

1

Outdoor Thermistor
Extension Wire

Do not alter the power cord.

Please install only with the customer’s consent

The air exchanger should not be operated under the following conditions:
(A)

When the air exchanger hose cannot be vented directly outside the room (mounting work specified for
the embedded ducting).

(B)

When there is a source of a questionable odor, smoke, or oily smoke in the vicinity of the opening of
the air exchanger hose, even if the mounting work directly vents the air exchanger hose outside the room.

The fresh air in should not be operated (only exhaust can be operated) under the following conditions:
(C) When there is space to vent the air exchanger hose between the internal and external walls, which leads

outside the room, even if the mounting work cannot directly vent the air exchanger hose outside the room
(conventional construction methods).

Please set the Air Exchanger Selection Switch according to the mounting configuration.

[Dimensions when Installing included Fittings]

Under the following conditions, the device can be installed with these fittings alone.

ø20 two way air exchange hose

Vented within 0.9m to the left and down or within 1.4m to the right and down.

Dimensions when installing the fitting for ø20 air exchanger hose

Within 1.4m

Within 1.4m

Within 0.9m

Within 0.9m

Backward piping

Vertically down from right
Horizontally piping from right

Backward piping from left
Vertically down from left

Horizontally piping from left

Remark

ø20 Air

Exchanger Hose

Net

When Air Exchanger cover
(HC-D55) is not using.

Extension

Pipe Connector

Part Name

Cap

Diagram Describing Backward Piping From Left

Diagram Describing Horizontally Piping From Right

Diagram Describing Vertically Down From Left

Air Exchanger Hose

Drain Hose

Refrigerating Pipe

Connecting Cable

Air Exchanger Hose

Refrigerating Pipe

Drain Hose

Air Exchanger Hose

Drain Hose

Refrigerating Pipe

Connecting Cable

Summary of Contents for RAC-R10EX

Page 1: ...power wireless systems The installation height of indoor unit must be 2 3m or more CAUTION Do not expose the unit under direct sunshine or rain Besides ventilation must be good and clear of obstruction The air blown out of the unit should not point directly to animals or plants The clearances of the unit from top left right and front are specified in figure below At least 2 of the above sides must...

Page 2: ...he possibility of damaged by mouse CAUTION 2 5mm Protection pipe Outdoor Indoor Seal with putty Sleeve of protection pipe WALL INDOOR UNIT Transform the piping while holding down the lower portion of pipe support by hand Drain Hose Drain Cap Wrap With The Tape Hanger Refrigerating Pipe Projection Pipe Drain Hose Two Way Air Exchange Hose Connecting Cord Hanger Projection Drain Hose Visible Outline...

Page 3: ...e connection to stop leakage Procedures of using Vacuum Pump for Air Removal As shown in figure on the right remove the cap of valve head and valve core and then connect them to the vacuum pump and sub division valve Fully tighten the Hi shuttle of the sub division valve and completely unscrew the Lo shuttle Run the vacuum pump for about 10 15 minutes then completely tighten the Lo shuttle and swi...

Page 4: ...ap Please tie the pipe and power line together with plastic tape as shown in the figure of installation of both the indoor and outdoor units Then fix their position with holders To enchance the heat insulation and to prevent water condensation please cover the outdoor part of the drain hose and pipe with insulation pipe Completely seal any gap with putty Insulation Material For Pipe Connection Sle...

Reviews: