background image

Revision Date: 26/03/2019

This manual is suitable for the following models:

KVF

   

Halton KVF Capture Jet™ Canopy with Supply Air and Side-Jet Technology

KVI

   

Halton KVI Capture Jet™ Canopy Side-Jet Technology

KVL 

 

Halton KVL Extraction Canopy

KVX

   

Halton KVX Extraction Canopy

Halton Capture Jet 3 – Proprietary Kitchen Ventilation Exhaust Hoods

OPERATION, CLEANING & MAINTENANCE

READ ALL INSTRUCTIONS BEFORE USE

Summary of Contents for KVF Capture Jet

Page 1: ...t Canopy with Supply Air and Side Jet Technology KVI Halton KVI Capture Jet Canopy Side Jet Technology KVL Halton KVL Extraction Canopy KVX Halton KVX Extraction Canopy Halton Capture Jet 3 Proprietar...

Page 2: ...Page Intentionally Left Blank Page 2 Due to continuous product research and development the information contained herein is subject to change without notice www stoddart com au www stoddart co nz...

Page 3: ...e Finish Corrosion Protection Recommended Cleaning And Maintenance Schedule Exposed Hood Surface Grease Pots Check and Empty KSA Cyclonic Filters Remove and Wash Exhaust Plenum Inspect and Clean Suppl...

Page 4: ...lways be observed Our units have been designed for high performance Read these instructions carefully and retain for future reference The manufacturer and distributor cannot be held responsible or lia...

Page 5: ...ntained herein is subject to change without notice www stoddart com au www stoddart co nz Overview Example only Exhaust hood configuration may vary due to customer specifications Introduction KSA Filt...

Page 6: ...ke up air supply through front rear perforated faces of the hood KVI M Island Position No provision for make up air supply through hood KVF M Island Position with provision for make up air supply thro...

Page 7: ...rticulate separation filters are the primary exhaust air treatment Exhaust Air Slide Damper is adjusted during commissioning only to balance air between multiple hood sections T A B points allow easy...

Page 8: ...integral part of the exhaust system To operate the hood specifically Turn on the room lights The lights in the hood are normally switched on together with the room lighting Check all filters are posit...

Page 9: ...sion should be thoroughly cleaned with warm soapy water and dried as soon as possible 4 Mild rust discolouration and or corrosion can be treated with a commercial cleaning agent that contains citric o...

Page 10: ...nally a service technician is required to periodically perform routine maintenance tasks This schedule is only a guide The frequency of cleaning will depend on the type and duration of cooking as well...

Page 11: ...or recycling 4 Wash the pot with hot soapy water before re fitting it to the hood 5 Replace the pot immediately as oil will continue to drip from the drain Note for hoods that have a drain tap instead...

Page 12: ...blind panels are positioned in same location 3 Lift each filter up and rotate bottom of filter toward you then lower filter down and out of the hood 4 Wash particulate off the filter in the pot sink w...

Page 13: ...ect every 3 months Moderate use 6 12 hours day inspect every 6 months Light use 6 hours day inspect every 12 months Ductwork cleaning is usually done by specialist cleaning contractors TR 19 suggests...

Page 14: ...lly and after service work by measuring the TAB pressure to confirm the exhaust airflow is within specification and ensure ongoing performance Maintenance Lights must only be replaced by a qualified t...

Page 15: ...e of the hood and use a screwdriver or similar to hold the clamps back If it is possible reach on top of the hood and hold the clamps back 2 Disconnect the light and replace it with a new one 3 If rep...

Page 16: ...e www stoddart com au www stoddart co nz 4 To replace the driver pull it through the hole undo the connections and replace it with a new one 5 Re fit all lights and drivers as they were before Ensure...

Page 17: ...e a balanced airflow to ensure exhaust and supply function efficiently 1 Using a manometer measure the pressure at the T A B Testing and Balancing point Do this for each exhaust plenum 2 Compare resul...

Page 18: ...for the hood to have a balanced airflow to ensure exhaust and supply function efficiently Using a manometer measure the pressure at the T A B Testing and Balancing point For hood models with a perfora...

Page 19: ...tted Hood and or ductwork requires cleaning Check they are correctly installed Check and clean the inside of the hood exhaust plenum s and ductwork If problem persists contact Stoddart Measured exhaus...

Page 20: ...ust air passing through the exhaust hood typically 50 65dBA is low in comparison to ambient noise levels in commercial kitchen typically 70 75dBA environments Closing the slide dampers increases the e...

Page 21: ...stoddart co nz Spare Parts Cleaning and Maintenance SPEH HAL KVI KVF 1 4 6 2 3 5 Item No Part Number Spare Parts Description 1 r e l l o r t n o C n a F t e J e r u t p a C 4 A 6 6 0 0 L A H H E P S...

Page 22: ...Due to continuous product research and development the information contained herein is subject to change without notice www stoddart com au www stoddart co nz Cleaning and Maintenance 1 2 3 4 5 SPEH H...

Page 23: ...Page 23 Due to continuous product research and development the information contained herein is subject to change without notice www stoddart com au www stoddart co nz...

Page 24: ...Zealand Business Number 6837694 New Zealand Sales Tel 0800 79 1954 Email sales stoddart co nz Service Spare Parts Tel 0800 935 714 Email service stoddart co nz Email spares stoddart co nz www stoddar...